220kV Oil Immersed Power Transformer - Advanced Design from China Suppliers and Factory

General
The 220kV transformer features a full folding plate tank structure similar to that of a 110kV transformer, ensuring a more rational design that facilitates easy installation and inspection on-site. As a leading manufacturer, our factory combines years of design and manufacturing expertise, allowing us to deliver products that meet international advanced standards in reliability and performance. As a trusted supplier in China, we are committed to providing high-quality transformers that meet the diverse needs of our customers.

    General

    Through continuous improvement and alteration, our products are with characteristics of low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and fully-enclosed structure. The series covers two-winding and three-Winding off-circuit tap changing power transformer, on-load tap changing transformer and tap-changing auto transformer.

    Standard

    • IEC60076 (1-5) Power transformers
    • IEC60296 Specification for mineral insulating oil for transformers and switchgear
    • IEC60354 Loading guide for oil immersed transformer
    • IEC60317: Insulated Bushings
    • ANSI, IEEE, AS, GB etc.

    Technical parameter

    The energy efficiency level of 220 kV oil-immersed three-phase double-winding no-load tap-changing power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    31500 15 115 18 115 22 122 12~14
    40000 18 134 21 134 26 142
    50000 21 161 25 161 31 170
    63000 25 188 30 188 37 199
    75000 29 213 34 213 42 225
    90000 34 246 40 246 49 259
    120000 41 304 49 304 60 321
    150000 49 360 58 360 71 380
    160000 51 378 60 378 74 399
    180000 56 413 66 413 82 436
    240000 70 484 83 484 102 511
    300000 83 577 98 577 121 609
    360000 95 662 112 662 138 698
    370000 97 675 114 675 141 713
    400000 103 716 122 716 150 755
    420000 106 742 125 742 154 783
    The energy efficiency level of 220 kV oil-immersed three-phase three-winding no-load tap-changing power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    Set up voltage Set down voltage
    31500 18 138 21 138 26 145 H-M:22~24
    H-L:12~14
    M-L:7~9
    H-M:12~14
    H-L:22~24
    M-L:7~9
    40000 21 165 25 165 30 174
    50000 24 194 29 194 35 205
    63000 29 231 34 231 42 244
    90000 37 300 44 300 54 316
    120000 46 369 55 369 67 390
    150000 55 438 65 438 80 463
    180000 62 500 73 500 90 527
    240000 72 616 91 616 112 650
    300000 91 726 108 726 133 767
    The energy efficiency level of 220 kV oil-immersed three-phase double-winding LV-66kV no-load tap-changing power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    31500 17 129 20 129 24 136 12~14
    40000 20 150 23 150 29 159
    50000 23 180 27 180 34 190
    63000 28 211 33 211 40 222
    90000 36 275 43 275 53 291
    120000 45 330 53 330 65 349
    150000 53 387 63 387 78 409
    180000 61 438 72 438 88 463
    240000 75 543 88 543 109 573
    The energy efficiency level of 220 kV oil-immersed three-phase double-winding OLTC power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    31500 17 115 20 115 24 122 12~14
    40000 20 134 23 134 29 142
    50000 24 161 28 161 34 170
    63000 28 188 33 188 40 199
    90000 35 246 42 246 51 259
    120000 43 304 51 304 63 321
    150000 51 360 60 360 74 380
    180000 59 413 70 413 86 436
    120000 LV
    66kV 69kV
    45 303 53 303 65 320
    150000 53 355 62 355 77 374
    180000 62 406 73 406 90 428
    240000 77 504 91 504 112 532
    The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    31500 19 138 23 138 28 145 H-M:12~14
    H-L:22~24
    M-L:7~9
    40000 23 165 27 165 33 174
    50000 26 194 31 194 38 205
    63000 31 231 36 231 45 244
    90000 40 300 47 300 58 316
    120000 51 369 60 369 74 390
    150000 59 438 70 438 86 463
    180000 68 538 81 538 99 568
    240000 85 667 100 667 123 704
    The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC autotransformer power transformer
    Rated capacity
    kVA
    Level Ⅰ Level Ⅱ Level Ⅲ short circuit impedance
    %
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    No-Load Loss
    kW
    Load Loss (75℃)
    kW
    31500 11 92 13 92 16 97 H-M:8~11
    H-L:28~34
    M-L:18~24
    40000 13 113 16 113 19 119
    50000 15 134 18 134 22 142
    63000 18 161 21 161 26 170
    90000 22 211 26 211 32 222
    120000 28 263 33 263 41 277
    150000 33 311 39 311 48 329
    180000 37 358 44 358 54 378
    240000 46 462 54 462 66 487

    Frequently Asked Questions

    QWhat design characteristics do your 220 kV power transformers feature?
    Our 220 kV power transformers are designed for high performance and reliability, featuring low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and a fully-enclosed structure.
    QWhich international standards do your transformers comply with?
    Our products strictly comply with international standards including IEC60076 (1-5) for power transformers, IEC60296 for mineral insulating oil, IEC60354 for loading guides, IEC60317 for insulated bushings, as well as ANSI, IEEE, AS, and GB standards.
    QWhat tap-changing configurations are available in this series?
    The product line covers two-winding and three-winding off-circuit tap-changing power transformers, on-load tap-changing (OLTC) power transformers, and tap-changing autotransformers.
    QHow are the energy efficiency levels classified for these transformers?
    The energy efficiency is classified into three levels (Level I, Level II, and Level III). Level I represents the highest efficiency with the lowest no-load loss and load loss values under rated capacity.
    QWhat is the typical short circuit impedance range for 220 kV double-winding transformers?
    For most 220 kV oil-immersed three-phase double-winding power transformers (both no-load tap-changing and OLTC models), the standard short circuit impedance typically ranges between 12% and 14%.