220kV Oil Immersed Power Transformer - Advanced Design from China Suppliers and Factory
General
Through continuous improvement and alteration, our products are with characteristics of low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and fully-enclosed structure. The series covers two-winding and three-Winding off-circuit tap changing power transformer, on-load tap changing transformer and tap-changing auto transformer.
Standard
- IEC60076 (1-5) Power transformers
- IEC60296 Specification for mineral insulating oil for transformers and switchgear
- IEC60354 Loading guide for oil immersed transformer
- IEC60317: Insulated Bushings
- ANSI, IEEE, AS, GB etc.
Technical parameter
The energy efficiency level of 220 kV oil-immersed three-phase double-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 15 | 115 | 18 | 115 | 22 | 122 | 12~14 |
| 40000 | 18 | 134 | 21 | 134 | 26 | 142 | |
| 50000 | 21 | 161 | 25 | 161 | 31 | 170 | |
| 63000 | 25 | 188 | 30 | 188 | 37 | 199 | |
| 75000 | 29 | 213 | 34 | 213 | 42 | 225 | |
| 90000 | 34 | 246 | 40 | 246 | 49 | 259 | |
| 120000 | 41 | 304 | 49 | 304 | 60 | 321 | |
| 150000 | 49 | 360 | 58 | 360 | 71 | 380 | |
| 160000 | 51 | 378 | 60 | 378 | 74 | 399 | |
| 180000 | 56 | 413 | 66 | 413 | 82 | 436 | |
| 240000 | 70 | 484 | 83 | 484 | 102 | 511 | |
| 300000 | 83 | 577 | 98 | 577 | 121 | 609 | |
| 360000 | 95 | 662 | 112 | 662 | 138 | 698 | |
| 370000 | 97 | 675 | 114 | 675 | 141 | 713 | |
| 400000 | 103 | 716 | 122 | 716 | 150 | 755 | |
| 420000 | 106 | 742 | 125 | 742 | 154 | 783 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
Set up voltage | Set down voltage | |
| 31500 | 18 | 138 | 21 | 138 | 26 | 145 | H-M:22~24 H-L:12~14 M-L:7~9 |
H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 21 | 165 | 25 | 165 | 30 | 174 | ||
| 50000 | 24 | 194 | 29 | 194 | 35 | 205 | ||
| 63000 | 29 | 231 | 34 | 231 | 42 | 244 | ||
| 90000 | 37 | 300 | 44 | 300 | 54 | 316 | ||
| 120000 | 46 | 369 | 55 | 369 | 67 | 390 | ||
| 150000 | 55 | 438 | 65 | 438 | 80 | 463 | ||
| 180000 | 62 | 500 | 73 | 500 | 90 | 527 | ||
| 240000 | 72 | 616 | 91 | 616 | 112 | 650 | ||
| 300000 | 91 | 726 | 108 | 726 | 133 | 767 | ||
The energy efficiency level of 220 kV oil-immersed three-phase double-winding LV-66kV no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 17 | 129 | 20 | 129 | 24 | 136 | 12~14 |
| 40000 | 20 | 150 | 23 | 150 | 29 | 159 | |
| 50000 | 23 | 180 | 27 | 180 | 34 | 190 | |
| 63000 | 28 | 211 | 33 | 211 | 40 | 222 | |
| 90000 | 36 | 275 | 43 | 275 | 53 | 291 | |
| 120000 | 45 | 330 | 53 | 330 | 65 | 349 | |
| 150000 | 53 | 387 | 63 | 387 | 78 | 409 | |
| 180000 | 61 | 438 | 72 | 438 | 88 | 463 | |
| 240000 | 75 | 543 | 88 | 543 | 109 | 573 | |
The energy efficiency level of 220 kV oil-immersed three-phase double-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
|||
| 31500 | 17 | 115 | 20 | 115 | 24 | 122 | 12~14 | |
| 40000 | 20 | 134 | 23 | 134 | 29 | 142 | ||
| 50000 | 24 | 161 | 28 | 161 | 34 | 170 | ||
| 63000 | 28 | 188 | 33 | 188 | 40 | 199 | ||
| 90000 | 35 | 246 | 42 | 246 | 51 | 259 | ||
| 120000 | 43 | 304 | 51 | 304 | 63 | 321 | ||
| 150000 | 51 | 360 | 60 | 360 | 74 | 380 | ||
| 180000 | 59 | 413 | 70 | 413 | 86 | 436 | ||
| 120000 | LV 66kV 69kV |
45 | 303 | 53 | 303 | 65 | 320 | |
| 150000 | 53 | 355 | 62 | 355 | 77 | 374 | ||
| 180000 | 62 | 406 | 73 | 406 | 90 | 428 | ||
| 240000 | 77 | 504 | 91 | 504 | 112 | 532 | ||
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 19 | 138 | 23 | 138 | 28 | 145 | H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 23 | 165 | 27 | 165 | 33 | 174 | |
| 50000 | 26 | 194 | 31 | 194 | 38 | 205 | |
| 63000 | 31 | 231 | 36 | 231 | 45 | 244 | |
| 90000 | 40 | 300 | 47 | 300 | 58 | 316 | |
| 120000 | 51 | 369 | 60 | 369 | 74 | 390 | |
| 150000 | 59 | 438 | 70 | 438 | 86 | 463 | |
| 180000 | 68 | 538 | 81 | 538 | 99 | 568 | |
| 240000 | 85 | 667 | 100 | 667 | 123 | 704 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC autotransformer power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 11 | 92 | 13 | 92 | 16 | 97 | H-M:8~11 H-L:28~34 M-L:18~24 |
| 40000 | 13 | 113 | 16 | 113 | 19 | 119 | |
| 50000 | 15 | 134 | 18 | 134 | 22 | 142 | |
| 63000 | 18 | 161 | 21 | 161 | 26 | 170 | |
| 90000 | 22 | 211 | 26 | 211 | 32 | 222 | |
| 120000 | 28 | 263 | 33 | 263 | 41 | 277 | |
| 150000 | 33 | 311 | 39 | 311 | 48 | 329 | |
| 180000 | 37 | 358 | 44 | 358 | 54 | 378 | |
| 240000 | 46 | 462 | 54 | 462 | 66 | 487 | |
Frequently Asked Questions
QWhat design characteristics do your 220 kV power transformers feature?
Our 220 kV power transformers are designed for high performance and reliability, featuring low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and a fully-enclosed structure.
QWhich international standards do your transformers comply with?
Our products strictly comply with international standards including IEC60076 (1-5) for power transformers, IEC60296 for mineral insulating oil, IEC60354 for loading guides, IEC60317 for insulated bushings, as well as ANSI, IEEE, AS, and GB standards.
QWhat tap-changing configurations are available in this series?
The product line covers two-winding and three-winding off-circuit tap-changing power transformers, on-load tap-changing (OLTC) power transformers, and tap-changing autotransformers.
QHow are the energy efficiency levels classified for these transformers?
The energy efficiency is classified into three levels (Level I, Level II, and Level III). Level I represents the highest efficiency with the lowest no-load loss and load loss values under rated capacity.
QWhat is the typical short circuit impedance range for 220 kV double-winding transformers?
For most 220 kV oil-immersed three-phase double-winding power transformers (both no-load tap-changing and OLTC models), the standard short circuit impedance typically ranges between 12% and 14%.