220kV Oil Immersed Power Transformer - High Performance from China Suppliers and Factory
General
Through continuous improvement and alteration, our products are with characteristics of low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and fully-enclosed structure. The series covers two-winding and three-Winding off-circuit tap changing power transformer, on-load tap changing transformer and tap-changing auto transformer.
Standard
IEC60076 (1-5) Power transformers
IEC60296 Specification for mineral insulating oil for transformers and switchgear
IEC60354 Loading guide for oil immersed transformer
IEC60317: Insulated Bushings
ANSI, IEEE, AS, GB etc.
Technical parameter
The energy efficiency level of 220 kV oil-immersed three-phase double-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 15 | 115 | 18 | 115 | 22 | 122 | 12~14 |
| 40000 | 18 | 134 | 21 | 134 | 26 | 142 | |
| 50000 | 21 | 161 | 25 | 161 | 31 | 170 | |
| 63000 | 25 | 188 | 30 | 188 | 37 | 199 | |
| 75000 | 29 | 213 | 34 | 213 | 42 | 225 | |
| 90000 | 34 | 246 | 40 | 246 | 49 | 259 | |
| 120000 | 41 | 304 | 49 | 304 | 60 | 321 | |
| 150000 | 49 | 360 | 58 | 360 | 71 | 380 | |
| 160000 | 51 | 378 | 60 | 378 | 74 | 399 | |
| 180000 | 56 | 413 | 66 | 413 | 82 | 436 | |
| 240000 | 70 | 484 | 83 | 484 | 102 | 511 | |
| 300000 | 83 | 577 | 98 | 577 | 121 | 609 | |
| 360000 | 95 | 662 | 112 | 662 | 138 | 698 | |
| 370000 | 97 | 675 | 114 | 675 | 141 | 713 | |
| 400000 | 103 | 716 | 122 | 716 | 150 | 755 | |
| 420000 | 106 | 742 | 125 | 742 | 154 | 783 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
|---|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
Set up voltage | Set down voltage | |
| 31500 | 18 | 138 | 21 | 138 | 26 | 145 |
H-M:22~24 H-L:12~14 M-L:7~9 |
H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 21 | 165 | 25 | 165 | 30 | 174 | ||
| 50000 | 24 | 194 | 29 | 194 | 35 | 205 | ||
| 63000 | 29 | 231 | 34 | 231 | 42 | 244 | ||
| 90000 | 37 | 300 | 44 | 300 | 54 | 316 | ||
| 120000 | 46 | 369 | 55 | 369 | 67 | 390 | ||
| 150000 | 55 | 438 | 65 | 438 | 80 | 463 | ||
| 180000 | 62 | 500 | 73 | 500 | 90 | 527 | ||
| 240000 | 72 | 616 | 91 | 616 | 112 | 650 | ||
| 300000 | 91 | 726 | 108 | 726 | 133 | 767 | ||
The energy efficiency level of 220 kV oil-immersed three-phase double-winding LV-66kV no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 17 | 129 | 20 | 129 | 24 | 136 | 12~14 |
| 40000 | 20 | 150 | 23 | 150 | 29 | 159 | |
| 50000 | 23 | 180 | 27 | 180 | 34 | 190 | |
| 63000 | 28 | 211 | 33 | 211 | 40 | 222 | |
| 90000 | 36 | 275 | 43 | 275 | 53 | 291 | |
| 120000 | 45 | 330 | 53 | 330 | 65 | 349 | |
| 150000 | 53 | 387 | 63 | 387 | 78 | 409 | |
| 180000 | 61 | 438 | 72 | 438 | 88 | 463 | |
| 240000 | 75 | 543 | 88 | 543 | 109 | 573 | |
The energy efficiency level of 220 kV oil-immersed three-phase double-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
|---|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
|||
| 31500 | 17 | 115 | 20 | 115 | 24 | 122 | 12~14 | |
| 40000 | 20 | 134 | 23 | 134 | 29 | 142 | ||
| 50000 | 24 | 161 | 28 | 161 | 34 | 170 | ||
| 63000 | 28 | 188 | 33 | 188 | 40 | 199 | ||
| 90000 | 35 | 246 | 42 | 246 | 51 | 259 | ||
| 120000 | 43 | 304 | 51 | 304 | 63 | 321 | ||
| 150000 | 51 | 360 | 60 | 360 | 74 | 380 | ||
| 180000 | 59 | 413 | 70 | 413 | 86 | 436 | ||
| 120000 |
LV 66kV 69kV |
45 | 303 | 53 | 303 | 65 | 320 | |
| 150000 | 53 | 355 | 62 | 355 | 77 | 374 | ||
| 180000 | 62 | 406 | 73 | 406 | 90 | 428 | ||
| 240000 | 77 | 504 | 91 | 504 | 112 | 532 | ||
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 19 | 138 | 23 | 138 | 28 | 145 |
H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 23 | 165 | 27 | 165 | 33 | 174 | |
| 50000 | 26 | 194 | 31 | 194 | 38 | 205 | |
| 63000 | 31 | 231 | 36 | 231 | 45 | 244 | |
| 90000 | 40 | 300 | 47 | 300 | 58 | 316 | |
| 120000 | 51 | 369 | 60 | 369 | 74 | 390 | |
| 150000 | 59 | 438 | 70 | 438 | 86 | 463 | |
| 180000 | 68 | 538 | 81 | 538 | 99 | 568 | |
| 240000 | 85 | 667 | 100 | 667 | 123 | 704 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC autotransformer power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
|---|---|---|---|---|---|---|---|
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 11 | 92 | 13 | 92 | 16 | 97 |
H-M:8~11 H-L:28~34 M-L:18~24 |
| 40000 | 13 | 113 | 16 | 113 | 19 | 119 | |
| 50000 | 15 | 134 | 18 | 134 | 22 | 142 | |
| 63000 | 18 | 161 | 21 | 161 | 26 | 170 | |
| 90000 | 22 | 211 | 26 | 211 | 32 | 222 | |
| 120000 | 28 | 263 | 33 | 263 | 41 | 277 | |
| 150000 | 33 | 311 | 39 | 311 | 48 | 329 | |
| 180000 | 37 | 358 | 44 | 358 | 54 | 378 | |
| 240000 | 46 | 462 | 54 | 462 | 66 | 487 | |
Frequently Asked Questions (FAQ)
Q: Which international standards do these 220 kV transformers comply with?
Our transformers fully comply with major international standards including IEC60076 (1-5) for power transformers, IEC60296 for mineral insulating oil, IEC60354 for loading guides, IEC60317 for insulated bushings, as well as ANSI, IEEE, AS, and GB standards.
Q: What are the main design features and characteristics of these transformers?
They are engineered with a fully-enclosed structure that offers low loss, low noise, low partial discharge, high short-circuit withstand capacity, and high impedance characteristics.
Q: What winding and tap-changing configurations are available in this series?
The series covers two-winding and three-winding configurations, including both off-circuit tap-changing power transformers, on-load tap-changing (OLTC) transformers, and tap-changing autotransformers.
Q: How is the energy efficiency of these transformers classified?
Energy efficiency is categorized into three levels: Level I (highest efficiency, lowest losses), Level II, and Level III. Each level defines specific maximum limits for No-Load Loss and Load Loss (measured at 75℃) based on the rated capacity.
Q: What is the typical short-circuit impedance for these 220 kV transformers?
For double-winding no-load, LV-66kV, and OLTC power transformers, the short-circuit impedance typically ranges from 12% to 14%. For three-winding OLTC autotransformers, it varies by voltage coupling (H-M: 8~11%, H-L: 28~34%, M-L: 18~24%).