220kV Oil Immersed Power Transformer - Reliable China Suppliers and Factory with Advanced Technology
General
Through continuous improvement and alteration, our products are with characteristics of low loss, low noise, low partial discharge, high short circuit withstand capacity, high impedance, and fully-enclosed structure. The series covers two-winding and three-Winding off-circuit tap changing power transformer, on-load tap changing transformer and tap-changing auto transformer.
Standard
- IEC60076 (1-5) Power transformers
- IEC60296 Specification for mineral insulating oil for transformers and switchgear
- IEC60354 Loading guide for oil immersed transformer
- IEC60317: Insulated Bushings
- ANSI, IEEE, AS, GB etc.
Technical parameter
The energy efficiency level of 220 kV oil-immersed three-phase double-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 15 | 115 | 18 | 115 | 22 | 122 | 12~14 |
| 40000 | 18 | 134 | 21 | 134 | 26 | 142 | |
| 50000 | 21 | 161 | 25 | 161 | 31 | 170 | |
| 63000 | 25 | 188 | 30 | 188 | 37 | 199 | |
| 75000 | 29 | 213 | 34 | 213 | 42 | 225 | |
| 90000 | 34 | 246 | 40 | 246 | 49 | 259 | |
| 120000 | 41 | 304 | 49 | 304 | 60 | 321 | |
| 150000 | 49 | 360 | 58 | 360 | 71 | 380 | |
| 160000 | 51 | 378 | 60 | 378 | 74 | 399 | |
| 180000 | 56 | 413 | 66 | 413 | 82 | 436 | |
| 240000 | 70 | 484 | 83 | 484 | 102 | 511 | |
| 300000 | 83 | 577 | 98 | 577 | 121 | 609 | |
| 360000 | 95 | 662 | 112 | 662 | 138 | 698 | |
| 370000 | 97 | 675 | 114 | 675 | 141 | 713 | |
| 400000 | 103 | 716 | 122 | 716 | 150 | 755 | |
| 420000 | 106 | 742 | 125 | 742 | 154 | 783 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
Set up voltage | Set down voltage | |
| 31500 | 18 | 138 | 21 | 138 | 26 | 145 | H-M:22~24 H-L:12~14 M-L:7~9 |
H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 21 | 165 | 25 | 165 | 30 | 174 | ||
| 50000 | 24 | 194 | 29 | 194 | 35 | 205 | ||
| 63000 | 29 | 231 | 34 | 231 | 42 | 244 | ||
| 90000 | 37 | 300 | 44 | 300 | 54 | 316 | ||
| 120000 | 46 | 369 | 55 | 369 | 67 | 390 | ||
| 150000 | 55 | 438 | 65 | 438 | 80 | 463 | ||
| 180000 | 62 | 500 | 73 | 500 | 90 | 527 | ||
| 240000 | 72 | 616 | 91 | 616 | 112 | 650 | ||
| 300000 | 91 | 726 | 108 | 726 | 133 | 767 | ||
The energy efficiency level of 220 kV oil-immersed three-phase double-winding LV-66kV no-load tap-changing power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 17 | 129 | 20 | 129 | 24 | 136 | 12~14 |
| 40000 | 20 | 150 | 23 | 150 | 29 | 159 | |
| 50000 | 23 | 180 | 27 | 180 | 34 | 190 | |
| 63000 | 28 | 211 | 33 | 211 | 40 | 222 | |
| 90000 | 36 | 275 | 43 | 275 | 53 | 291 | |
| 120000 | 45 | 330 | 53 | 330 | 65 | 349 | |
| 150000 | 53 | 387 | 63 | 387 | 78 | 409 | |
| 180000 | 61 | 438 | 72 | 438 | 88 | 463 | |
| 240000 | 75 | 543 | 88 | 543 | 109 | 573 | |
The energy efficiency level of 220 kV oil-immersed three-phase double-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
||||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
|||
| 31500 | 17 | 115 | 20 | 115 | 24 | 122 | 12~14 | |
| 40000 | 20 | 134 | 23 | 134 | 29 | 142 | ||
| 50000 | 24 | 161 | 28 | 161 | 34 | 170 | ||
| 63000 | 28 | 188 | 33 | 188 | 40 | 199 | ||
| 90000 | 35 | 246 | 42 | 246 | 51 | 259 | ||
| 120000 | 43 | 304 | 51 | 304 | 63 | 321 | ||
| 150000 | 51 | 360 | 60 | 360 | 74 | 380 | ||
| 180000 | 59 | 413 | 70 | 413 | 86 | 436 | ||
| 120000 | LV 66kV 69kV |
45 | 303 | 53 | 303 | 65 | 320 | |
| 150000 | 53 | 355 | 62 | 355 | 77 | 374 | ||
| 180000 | 62 | 406 | 73 | 406 | 90 | 428 | ||
| 240000 | 77 | 504 | 91 | 504 | 112 | 532 | ||
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 19 | 138 | 23 | 138 | 28 | 145 | H-M:12~14 H-L:22~24 M-L:7~9 |
| 40000 | 23 | 165 | 27 | 165 | 33 | 174 | |
| 50000 | 26 | 194 | 31 | 194 | 38 | 205 | |
| 63000 | 31 | 231 | 36 | 231 | 45 | 244 | |
| 90000 | 40 | 300 | 47 | 300 | 58 | 316 | |
| 120000 | 51 | 369 | 60 | 369 | 74 | 390 | |
| 150000 | 59 | 438 | 70 | 438 | 86 | 463 | |
| 180000 | 68 | 538 | 81 | 538 | 99 | 568 | |
| 240000 | 85 | 667 | 100 | 667 | 123 | 704 | |
The energy efficiency level of 220 kV oil-immersed three-phase three-winding OLTC autotransformer power transformer
| Rated capacity kVA |
Level Ⅰ | Level Ⅱ | Level Ⅲ | short circuit impedance % |
|||
| No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
No-Load Loss kW |
Load Loss (75℃) kW |
||
| 31500 | 11 | 92 | 13 | 92 | 16 | 97 | H-M:8~11 H-L:28~34 M-L:18~24 |
| 40000 | 13 | 113 | 16 | 113 | 19 | 119 | |
| 50000 | 15 | 134 | 18 | 134 | 22 | 142 | |
| 63000 | 18 | 161 | 21 | 161 | 26 | 170 | |
| 90000 | 22 | 211 | 26 | 211 | 32 | 222 | |
| 120000 | 28 | 263 | 33 | 263 | 41 | 277 | |
| 150000 | 33 | 311 | 39 | 311 | 48 | 329 | |
| 180000 | 37 | 358 | 44 | 358 | 54 | 378 | |
| 240000 | 46 | 462 | 54 | 462 | 66 | 487 | |
Frequently Asked Questions
What are the main characteristics of these 220 kV power transformers?
Our 220 kV oil-immersed power transformers feature low loss, low noise, low partial discharge, high short-circuit withstand capacity, high impedance, and a fully-enclosed structure.
Which international standards do these transformers comply with?
They are designed and manufactured in compliance with international standards including IEC60076 (1-5), IEC60296, IEC60354, IEC60317, as well as ANSI, IEEE, AS, and GB standards.
What types of tap-changing configurations are available?
The series covers two-winding and three-winding off-circuit tap changing power transformers, on-load tap changing (OLTC) transformers, and tap-changing autotransformers.
How are the energy efficiency levels classified for these transformers?
The energy efficiency is classified into three levels (Level I, Level II, and Level III) based on no-load loss and load loss parameters measured at 75℃.
What is the typical short circuit impedance range for a 220 kV double-winding transformer?
For most 220 kV double-winding power transformers, the typical short circuit impedance ranges from 12% to 14%.