China FTD9-12D Indoor High Voltage AC Vacuum Load Switch - Reliable Supplier & Factory for 12kV Power Systems

Product Overview
The FTD9-12D indoor high-voltage AC vacuum load switch, manufactured in China, is an essential component for modern electrical distribution systems. This advanced indoor switchgear effectively manages the closing, opening, and carrying of normal operating currents, including specified overload and short-circuit currents. Designed for three-phase AC 50/60HZ, 12KV power systems, it is compatible with a variety of distribution equipment, including ring network switchgear and modular substations. The FTD9-12D shares a similar layout, technical characteristics, appearance, and dimensions with the VTD9-12D vacuum circuit breaker, making it a versatile choice for installation in compact and constrained spaces. Trustworthy suppliers and reputable factories in China can provide this high-quality load switch to meet your electrical infrastructure needs.

    Quality standard
    Product quality assurance is based on continuous improvement of research, development, design, and production processes that meet all aspects of the quality system requirements. It fully complies with the latest versions or modified versions of the following standards, specifications, and guidelines, and is not limited to them.
    • IEC62271-103   High voltage switchgear and control equipment - Part 103: 1KV~52KV AC load switches
    • IEC62271-105   High voltage switchgear and control equipment - Part 105: 1KV~52KV AC load switch fuse combination
    • GB/T3804   3.6kV~40.5kV High Voltage AC Load Switch
    • GB/T16926   High voltage AC load switch- fuse combination device
    Service Conditions
    • a Environmental temperature: -25℃ ~ +40℃;
    • b Altitude: ≤ 1000m;
    • c Relative humidity:
      • Daily average relative humidity ≤ 95%
      • Monthly average relative humidity ≤ 90%
      • Daily average vapor pressure ≤ 2.2x10-3 MPa
      • Monthly average vapor pressure ≤ 1.8x10-3 MPa;
    • d Seismic grade: seismic intensity ≤ 8;
    • e The applicable location is free from dripping water, flammable and explosive hazards, chemical corrosive gases, and severe vibrations.
    ※Note: When the usage environment deviates from normal usage conditions, please consult with our company to determine.
    Technical Data
    Item

    Unit

    Parameter

    Rated frequency

    Hz

    50/60

    Rated voltage

    kV

    12

    Rated power frequency withstand voltage (1 minute, r.m.s) Phase to phase and phase to ground

    KV

    42

    Isolation fracture

    48

    Control and auxiliary circuits

    2

    Rated lightning impulse withstand voltage (peak) Phase to phase and phase to ground

    kV

    75

    Isolation fracture

    85

    Rated current

    A

    630

    Rated short-circuit breaking current (r.m.s)

    kA

    /

    Rated short-time withstand current and time

    kA/s

    20/4

    Rated peak withstand current

    kA

    50

    Rated short-circuit making current (peak)

    kA

    /

    Rated breaking current of single/back-to-back capacitor group

    A

    /

    Rated capacitor bank making current

    kA

    /

    Rated handover (transfer) current

    A

    1

    Mechanical life

    Times

    5000

    Main circuit resistance of each phase

    ≤ 100

    Clearance between open contacts

    mm

    9 ± 1

    Contacting travel

    mm

    5.5 ± 1

    Contact closing bounce time

    mm

    ≤ 2

    Three-phase asynchronous closing and opening

    ms

    ≤ 2

    Average opening speed (contact just opened - 6mm)

    m/s

    0.9 -1.3

    Average closing speed (6mm - contact just opened)

    m/s

    0.4 ~ 0.8

    Rated contact pressure

    N

    1000 ± 100

    Opening time (at rated voltage)

    ms

    /

    Closing time (at rated voltage)

    ms

    /

    Rated operating sequence  

    /

    Technical characteristics
    ● Reasonable design and novel structure

    The operating mechanism is integrated with the "five-prevention" interlocking mechanism, and modular design is adopted for components such as the (load switch) solid-sealed pole and the earthing switch. These components are combined into a single unit through a common mounting frame. The operating panel indicators are integrated with the primary circuit indicators, providing clear, simple, and easy-to-understand indications. The interlocking design is rationally integrated to form a "foolproof" operating procedure, making incorrect operations "impossible".

    ● Miniaturization

    Compared with air-insulated switches of the same model and specification, the device has a smaller volume, with a cabinet width of only 500 mm. It is a paragon of the new generation of miniaturized air-insulated switchgear.

    ● Less maintenance

    The device uses maintenance-free vacuum (arc extinguishing chamber) switch (poles), which are virtually maintenance-free, have a long service life, and offer low operating costs.

    ● Visual Consistency

    VTD9 circuit breaker, FTD9 load switch, and GTD isolating switch have identical external dimensions, facilitating the expansion and combination of switchgear cabinets.

    Typical outline dimensions (fit) and structural diagram
    FTD9 - 12/630 vacuum load switch outline dimension drawing
    FTD9 - 12/630 (inter-phase distance P=210) Outline dimension drawing of vacuum load switch
    (this drawing is for normal installation, but it can also be reversed)
    FTD9 - 12D/630 vacuum load switch outline dimension drawing
    FTD9 - 12D/630 (inter-phase distance P=210) outline dimension drawing of vacuum load switch
    (this drawing is for normal installation, but it can also be reversed)
    Frequently Asked Questions (FAQ)
    Q1: Which international and national standards do these switchgears comply with?
    The products fully comply with IEC62271-103 (AC load switches), IEC62271-105 (AC load switch fuse combination), GB/T3804 (High Voltage AC Load Switch), and GB/T16926 (High voltage AC load switch-fuse combination device).
    Q2: What are the standard service conditions for installing this equipment?
    Normal operations require an environmental temperature of -25℃ to +40℃, altitude ≤ 1000m, daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%, and a seismic intensity grade ≤ 8. The installation location must be free from dripping water, flammable/explosive hazards, chemical corrosive gases, and severe vibrations.
    Q3: What are the key rated electrical specifications of the switch?
    The switch features a rated voltage of 12 kV, a rated current of 630 A, operates at a rated frequency of 50/60 Hz, and has a mechanical life of 5000 operations.
    Q4: How does the miniaturized design benefit installation?
    Compared to standard air-insulated switches, this device is highly compact with a cabinet width of only 500 mm, making it ideal for space-constrained installations.
    Q5: What makes this switch low maintenance?
    The device utilizes maintenance-free vacuum poles (arc extinguishing chambers), which drastically reduce upkeep, extend service life, and lower overall operating costs.
    Q6: Can the installation orientation of the vacuum load switches be modified?
    Yes, although the provided outline dimension drawings display normal installation setups, the installation direction can also be reversed depending on requirements.