China FTD9-12D Indoor High Voltage AC Vacuum Load Switch - Reliable Suppliers and Quality Factory Production
Quality Standard
Product quality assurance is based on continuous improvement of research, development, design, and production processes that meet all aspects of the quality system requirements. It fully complies with the latest versions or modified versions of the following standards, specifications, and guidelines, and is not limited to them.
- IEC62271-103 High voltage switchgear and control equipment - Part 103: 1KV~52KV AC load switches
- IEC62271-105 High voltage switchgear and control equipment - Part 105: 1KV~52KV AC load switch fuse combination
- GB/T3804 3.6kV~40.5kV High Voltage AC Load Switch
- GB/T16926 High voltage AC load switch- fuse combination device
Service Conditions
a. Environmental temperature: - 25℃ ~ +40℃;
b. Altitude: ≤ 1000m;
c. Relative humidity:
Daily average relative humidity ≤ 95%
Monthly average relative humidity ≤ 90%
Daily average vapor pressure ≤ 2.2x10-3 MPa
Monthly average vapor pressure ≤ 1.8x10-3 MPa;
Daily average relative humidity ≤ 95%
Monthly average relative humidity ≤ 90%
Daily average vapor pressure ≤ 2.2x10-3 MPa
Monthly average vapor pressure ≤ 1.8x10-3 MPa;
d. Seismic grade: seismic intensity ≤ 8;
e. Applicable location: Free from dripping water, flammable and explosive hazards, chemical corrosive gases, and severe vibrations.
※ Note:
When the usage environment deviates from normal usage conditions, please consult with our company to determine.
Technical Data
| Item | Unit |
Parameter |
|
|---|---|---|---|
| Rated frequency | Hz |
50/60 |
|
| Rated voltage | kV |
12 |
|
| Rated power frequency withstand voltage (1 minute, r.m.s) | Phase to phase and phase to ground | KV |
42 |
| Isolation fracture | 48 |
||
| Control and auxiliary circuits | 2 |
||
| Rated lightning impulse withstand voltage (peak) | Phase to phase and phase to ground | kV |
75 |
| Isolation fracture | 85 |
||
| Rated current | A |
630 |
|
| Rated short-circuit breaking current (r.m.s) | kA |
/ |
|
| Rated short-time withstand current and time | kA/s |
20/4 |
|
| Rated peak withstand current | kA |
50 |
|
| Rated short-circuit making current (peak) | kA |
/ |
|
| Rated breaking current of single/back-to-back capacitor group | A |
/ |
|
| Rated capacitor bank making current | kA |
/ |
|
| Rated handover (transfer) current | A |
1 |
|
| Mechanical life | Times |
5000 |
|
| Main circuit resistance of each phase | mΩ |
≤ 100 |
|
| Clearance between open contacts | mm |
9 ± 1 |
|
| Contacting travel | mm |
5.5 ± 1 |
|
| Contact closing bounce time | mm |
≤ 2 |
|
| Three-phase asynchronous closing and opening | ms |
≤ 2 |
|
| Average opening speed (contact just opened - 6mm) | m/s |
0.9 -1.3 |
|
| Average closing speed (6mm - contact just opened) | m/s |
0.4 ~ 0.8 |
|
| Rated contact pressure | N |
1000 ± 100 |
|
| Opening time (at rated voltage) | ms |
/ |
|
| Closing time (at rated voltage) | ms |
/ |
|
| Rated operating sequence | / |
||
Technical Characteristics
● Reasonable design and novel structure
The operating mechanism is integrated with the "five-prevention" interlocking mechanism, and modular design is adopted for components such as the (load switch) solid-sealed pole and the earthing switch. These components are combined into a single unit through a common mounting frame.
The operating panel indicators are integrated with the primary circuit indicators, providing clear, simple, and easy-to-understand indications. The interlocking design is rationally integrated to form a "foolproof" operating procedure, making incorrect operations "impossible".
● Miniaturization
Compared with air-insulated switches of the same model and specification, the device has a smaller volume, with a cabinet width of only 500 mm. It is a paragon of the new generation of miniaturized air-insulated switchgear.
● Less maintenance
The device uses maintenance-free vacuum (arc extinguishing chamber) switch (poles), which are virtually maintenance-free, have a long service life, and offer low operating costs.
● Visual Consistency
VTD9 circuit breaker, FTD9 load switch, and GTD isolating switch have identical external dimensions, facilitating the expansion and combination of switchgear cabinets.
Typical Outline Dimensions & Structural Diagram

FTD9 - 12/630 (inter-phase distance P=210) Outline dimension drawing of vacuum load switch
(this drawing is for normal installation, but it can also be reversed)

FTD9 - 12D/630 (inter-phase distance P=210) outline dimension drawing of vacuum load switch
(this drawing is for normal installation, but it can also be reversed)
Frequently Asked Questions (FAQ)
Which international and national standards do these vacuum load switches comply with?
The products comply with IEC62271-103 (1KV~52KV AC load switches), IEC62271-105 (AC load switch fuse combination), GB/T3804 (3.6kV~40.5kV High Voltage AC Load Switch), and GB/T16926 (High voltage AC load switch-fuse combination device) standards.
What are the standard ambient service conditions for installation?
The standard service conditions include an environmental temperature range of -25℃ to +40℃, an altitude of ≤ 1000m, daily average relative humidity ≤ 95% (monthly ≤ 90%), and a seismic grade of intensity ≤ 8. The installation location must be free from dripping water, flammable/explosive hazards, corrosive gases, and severe vibrations.
What is the rated voltage and mechanical life of the FTD9 vacuum load switch?
The FTD9 vacuum load switch features a rated voltage of 12 kV and has a mechanical life of up to 5000 operations.
How does the design support space-saving switchgear configurations?
The device is designed for miniaturization. It has a significantly smaller volume compared to standard air-insulated switches, allowing for a cabinet width of only 500 mm.
Can the VTD9, FTD9, and GTD switches be combined in the same switch cabinet layout?
Yes. The VTD9 circuit breaker, FTD9 load switch, and GTD isolating switch share identical external dimensions, which ensures visual consistency and makes the expansion and combination of switchgear cabinets very convenient.
What should I do if my operating environment deviates from the standard service conditions?
If your installation environment deviates from the specified normal usage conditions (such as higher altitude or extreme temperatures), please consult directly with our technical support team to determine the compatibility and customized adjustments.