China LW39-126 Outdoor AC High Voltage SF6 Circuit Breaker Factory Suppliers for 110kV Power Systems

The LW39-126 outdoor AC high voltage porcelain SF6 circuit breaker is specifically designed for power systems operating at frequencies of 50/60Hz and a normal voltage of 110kV. As a crucial piece of equipment in power plants and substations, it plays a vital role in control and protection within the electrical grid, This circuit breaker features a thermal expansion self-arc-extinguishing mechanism and is filled with SF6 gas, renowned for its exceptional arc-extinguishing and electrical insulation properties. To ensure longevity and reliability, all seals are equipped with double-circle O-type seal rings that effectively prevent leakage. The LW39-126 is also integrated with the CT30 type spring operation mechanism, allowing for three-phase mechanical linkage operation, As a leading product manufactured by top suppliers in China, this circuit breaker exemplifies quality and innovation in high voltage electrical components, making it an essential choice for any factory or service provider in the energy sector

    General
    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is applied in power system with 50/60Hz frequency, 110kV system normal voltage. It is the main power equipment used in power plant and substation for control and protection.

    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker adopts thermal expansion self-arc-extinguish, filled with SF6 gas of well arc-extinguishing and electric insulation performance. All the seals adopt double-circle O type seal ring, which can effective prevent leakage; equipped with CT30 type spring operation mechanism, three phase mechanical linkage operation.
    Features
    LW39-126 type outdoor AC HV porcelain SF6 circuit breaker is a new type HV SF6 circuit breaker with high performance, which is designed according to national standards and domestic industry manufacture level. The main features are as follows:
    a. High breaking level, break reliably when outgoing terminal is in short circuit, out of phase and fault in near zone.
    b. Structure of arc-extinguishing chamber is simple, reliable and convenient to maintain.
    c. Long service life, have 20 times' breaking ability under full capacity and free of maintenance under normal operation in many years.
    d. Light operation force, adopts simple, reliable and compact spring operation mechanism.
    e. Rated charging pressure of gas is low and can be used in low temperature condition.
    f. Small occupied area.
    g. Low noise level and suitable to apply in residential area.
    h. Long overhaul period and less maintenance.
    i. Short installation time on the spot.
    Service condition

    Altitude

    ≤ 3000m

    Ambient temperature

    -35℃~+40℃

    Wind speed

    ≤ 35m/s

    Daily temperature difference

    ≤ 25℃

    Sunlight temperature

    0.1w/cm2

    Relative humidity

    Average (monthly): ≤ 90

    Average (daily): ≤ 95

    Ice thickness

    ≤ 10mm

    Earthquake

    ≤ 9°

    Pollution grade

    III or IV

    Main Technical Parameters
    1.1 Main technical parameters of circuit breaker

    No.

    Items

    Unit

    Parameters

    1

    System nominal voltage

    kV

    110

    2

    Rated voltage

    kV

    126

    3

    Rated frequency

    Hz

    50/60

    4

    Rated current

    A

    3150

    5

    Rated short-circuit breaking current

    kA

    31.5

    40

    6

    Rated short-circuit making current

    kA

    80

    100

    7

    Rated short time withstand current

    kA

    31.5

    40

    8

    Rated peak withstand current

    kA

    80

    100

    9

    Rated duration time of short-circuit

    S

    4

    3

    10

    First-pole-to-clear factor

     

    1.5

    11

    Lightning impulse withstand voltage

    kV

    650

    12

    1min power frequency withstand voltage

    kV

    275

    13

    Creepage distance fracture/to earth

    mm/kV

    25/31

    14

    Rated operation sequence

     

    O-0.3s-CO-180s-CO

    15

    Making time

    ms

    ≤ 110

    16

    Breaking time

    ms

    ≤ 65

    17

    Closing-opening time

    ms

    ≤ 85

    18

    Closing time

    ms

    80 ± 15

    19

    Opening time

    ms

    33 ± 7

    20

    Fracture quantity of per pole

    pc

    1

    21

    Main loop resistance

    μΩ

    ≤ 45

    22

    Mechanical life

    times

    10000

    23


    SF6 gas pressure(20℃)

    Rated value

    Mpa

    0.55

    0.60

    Alarm value

    Mpa

    0.50

    0.55

    Interlock value

    Mpa

    0.45

    0.50

    24

    SF6 moisture content

    ppm(V/V)

    ≤ 150

    25

    Yearly leak rate of SF6

     

    ≤ 1%

    26

    Charging SF6 gas weight of each circuit breaker

    kg

    7

    9

    27

    Total weight of each circuit breaker

    kg

    2000

    28

    Static tension of circuit breaker connecting terminal

    longitudinal

    N

    1250

    horizontal

    N

    750

    vertical

    N

    1000

    29

    Voltage of auxiliary circuit

    V

    AC220

    30

    Closing coil

    rated voltage

    V

    DC220

    DC110

    rated current

    A

    2

    3.3

    Coil resistance under 20℃

    Ω

    110 ± 5

    33 ± 1.6

    31

    Opening coil

    rated voltage

    V

    DC220

    DC110

    rated current

    A

    2

    5.8

    Coil resistance under 20℃

    Ω

    110±5

    19±1

    32

    Energy Storage motor

    Voltage

    V

    AC220/DC220

    Power

    W

    600

    33

    Energy storage time

    S

    ≤ 15

    34

    Heater

    Voltage

    V

    AC220

    Power

    W

    100

    35

    Standards

    GB1984

    1.2 Mechanical parameters of circuit breaker

    No.

    Items

    Unit

    Parameters

    1

    Closing asynchronous between phases

    ms

    ≤ 5

    2

    Opening asynchronous between phases

    ms

    ≤ 3

    3

    Contact travel of moving-contact

    mm

    38 ~ 42

    4

    Main drive lever travel of mechanism

    mm

    98 ~ 100

    5

    Travel of moving-contact

    mm

    118 ~ 122

    Drawing
    01
    Drawing 1 LW39-126 External drawing of circuit breaker
    Instruction:
    1. Arc extinguish chamber
    2. Support porcelain bushing
    3. Beam
    4. Post
    5. Mechanism box
    6. Charging & discharge self-sealing valve
    7. Density controller
    8. Nameplate
    9. Closing & opening indication
    1
    Drawing 2
    1.Upper wiring plate
    2.Absorbing-type filler
    3.Porcelain bushing of arc-extinguishing chamber
    4.Compression cylinder
    5.Piston
    6.Lower collector
    7.Lower wiring plate
    8.Support porcelain bushing
    9.Insulation pulling rod
    10.Movable main contact
    11.Movable arc contact
    12.Arc-extinguishing spout
    13.Static arc contact
    14.Static main contact
    2
    Drawing 3
    10.Movable main contact
    11.Movable arc contact
    12.Arc-extinguishing spout
    13.Static arc contact
    14.Static main contact
    15.Thermal expansion chamber
    16.Valve plate of thermal
    17.Compression chamber
    18.Valve plate of compressionChamber
    3
    Drawing 4
    Frequently Asked Questions (FAQ)
    What is the primary application of the LW39-126 circuit breaker?
    It is designed for outdoor AC high voltage systems with a 50/60Hz frequency and a 110kV normal system voltage, mainly serving control and protection functions in power plants and substations.
    What operating mechanism does this circuit breaker use?
    The LW39-126 circuit breaker is equipped with a CT30 type spring operating mechanism, which supports three-phase mechanical linkage operation.
    How does the arc-extinguishing system work?
    It utilizes thermal expansion self-arc-extinguishment and is filled with high-performance SF6 gas for superior arc-extinguishing and electrical insulation. Double-circle O-ring seals prevent gas leakage.
    What are the environmental limits for installing the LW39-126?
    It operates in altitudes up to 3000 meters, ambient temperatures from -35℃ to +40℃, wind speeds up to 35m/s, and relative humidity averages up to 95% daily.
    What is the mechanical lifespan of this circuit breaker?
    The LW39-126 circuit breaker has a mechanical life rating of 10,000 operations and features a long overhaul period with minimal maintenance requirements.
    Which quality standard does the circuit breaker conform to?
    The circuit breaker is designed and tested in compliance with the GB1984 standards.