China LW39-126 Outdoor High Voltage SF6 Circuit Breaker Suppliers - Reliable Factory for Power System Solutions

The LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is designed for power systems operating at a frequency of 50/60Hz and a normal voltage of 110kV. This essential equipment is widely utilized in power plants and substations for effective control and protection. As a reliable choice among China suppliers, our circuit breakers ensure optimal performance and safety.

Featuring advanced thermal expansion self-arc-extinguishing technology, the LW39-126 circuit breaker is filled with SF6 gas, known for its excellent arc-extinguishing and electrical insulation properties. The design includes double-circle O-type seal rings, which effectively prevent leakage, enhancing durability and reliability. Additionally, the circuit breaker is equipped with the CT30 type spring operation mechanism, allowing for synchronized three-phase mechanical linkage operations, making it an ideal product from a trusted factory in China.

    General
    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is applied in power system with 50/60Hz frequency, 110kV system normal voltage. It is the main power equipment used in power plant and substation for control and protection.
    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker adopts thermal expansion self-arc-extinguish, filled with SF6 gas of well arc-extinguishing and electric insulation performance. All the seals adopt double-circle O type seal ring, which can effective prevent leakage; equipped with CT30 type spring operation mechanism, three phase mechanical linkage operation.
    Features
    LW39-126 type outdoor AC HV porcelain SF6 circuit breaker is a new type HV SF6 circuit breaker with high performance, which is designed according to national standards and domestic industry manufacture level. The main features are as follows:
    a. High breaking level, break reliably when outgoing terminal is in short circuit, out of phase and fault in near zone.
    b. Structure of arc-extinguishing chamber is simple,reliable and convenient to maintain.
    c. Long service life, have 20 times' breaking ability under full capacity and free of maintenance under normal operation in many years.
    d. Light operation force, adopts simple, reliable and compact spring operation mechanism.
    e. Rated charging pressure of gas is low and can be used in low temperature condition.
    f. Small occupied area.
    g. Low noise level and suitable to apply in residential area.
    h. Long overhaul period and less maintenance.
    i. Short installation time on the spot.
    Service condition
    Items Requirements / Limits
    Altitude ≤ 3000m
    Ambient temperature -35℃~+40℃
    Wind speed ≤ 35m/s
    Daily temperature difference ≤ 25℃
    Sunlight temperature 0.1w/cm2
    Relative humidity Average (monthly): ≤ 90
    Average (daily): ≤ 95
    Ice thickness ≤ 10mm
    Earthquake ≤ 9°
    Pollution grade III or IV
    Main Technical Parameters
    1.1 Main technical parameters of circuit breaker
    No. Items Unit Parameters
    1 System nominal voltage kV 110
    2 Rated voltage kV 126
    3 Rated frequency Hz 50/60
    4 Rated current A 3150
    5 Rated short-circuit breaking current kA 31.5 40
    6 Rated short-circuit making current kA 80 100
    7 Rated short time withstand current kA 31.5 40
    8 Rated peak withstand current kA 80 100
    9 Rated duration time of short-circuit S 4 3
    10 First-pole-to-clear factor 1.5
    11 Lightning impulse withstand voltage kV 650
    12 1min power frequency withstand voltage kV 275
    13 Creepage distance fracture/to earth mm/kV 25/31
    14 Rated operation sequence O-0.3s-CO-180s-CO
    15 Making time ms ≤ 110
    16 Breaking time ms ≤ 65
    17 Closing-opening time ms ≤ 85
    18 Closing time ms 80 ± 15
    19 Opening time ms 33 ± 7
    20 Fracture quantity of per pole pc 1
    21 Main loop resistance μΩ ≤ 45
    22 Mechanical life times 10000
    23 SF6 gas pressure (20℃) Rated value Mpa 0.55 0.60
    Alarm value Mpa 0.50 0.55
    Interlock value Mpa 0.45 0.50
    24 SF6 moisture content ppm(V/V) ≤ 150
    25 Yearly leak rate of SF6 ≤ 1%
    26 Charging SF6 gas weight of each circuit breaker kg 7 9
    27 Total weight of each circuit breaker kg 2000
    28 Static tension of circuit breaker connecting terminal longitudinal N 1250
    horizontal N 750
    vertical N 1000
    29 Voltage of auxiliary circuit V AC220
    30 Closing coil rated voltage V DC220 DC110
    rated current A 2 3.3
    Coil resistance under 20℃ Ω 110 ± 5 33 ± 1.6
    31 Opening coil rated voltage V DC220 DC110
    rated current A 2 5.8
    Coil resistance under 20℃ Ω 110 ± 5 19 ± 1
    32 Energy Storage motor Voltage V AC220/DC220
    Power W 600
    33 Energy storage time S ≤ 15
    34 Heater Voltage V AC220
    Power W 100
    35 Standards GB1984
    1.2 Mechanical parameters of circuit breaker
    No. Items Unit Parameters
    1 Closing asynchronous between phases ms ≤ 5
    2 Opening asynchronous between phases ms ≤ 3
    3 Contact travel of moving-contact mm 38 ~ 42
    4 Main drive lever travel of mechanism mm 98 ~ 100
    5 Travel of moving-contact mm 118 ~ 122
    Drawing
    01
    Drawing 1 LW39-126 External drawing of circuit breaker
    Instruction:
    • 1. Arc extinguish chamber
    • 2. Support porcelain bushing
    • 3. Beam
    • 4. Post
    • 5. Mechanism box
    • 6. Charging & discharge self-sealing valve
    • 7. Density controller
    • 8. Nameplate
    • 9. Closing & opening indication
    1
    Drawing 2
    • 1. Upper wiring plate
    • 2. Absorbing-type filler
    • 3. Porcelain bushing of arc-extinguishing chamber
    • 4. Compression cylinder
    • 5. Piston
    • 6. Lower collector
    • 7. Lower wiring plate
    • 8. Support porcelain bushing
    • 9. Insulation pulling rod
    • 10. Movable main contact
    • 11. Movable arc contact
    • 12. Arc-extinguishing spout
    • 13. Static arc contact
    • 14. Static main contact
    2
    Drawing 3
    • 10. Movable main contact
    • 11. Movable arc contact
    • 12. Arc-extinguishing spout
    • 13. Static arc contact
    • 14. Static main contact
    • 15. Thermal expansion chamber
    • 16. Valve plate of thermal
    • 17. Compression chamber
    • 18. Valve plate of compression Chamber
    3
    Drawing 4
    Frequently Asked Questions (FAQ)
    What is the primary application of the LW39-126 circuit breaker?
    The LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is designed for electrical power systems with a 50/60Hz frequency and 110kV normal system voltage, serving as the main control and protection equipment in power plants and substations.
    How does the arc-extinguishing system work?
    It utilizes a thermal expansion self-arc-extinguish structure filled with SF6 gas, which provides superior arc-extinguishing and electrical insulation performance.
    What type of operating mechanism is integrated?
    The circuit breaker is equipped with a CT30 type spring operating mechanism, which supports three-phase mechanical linkage operation.
    What are the environmental limits for service conditions?
    It operates reliably at altitudes up to 3000m, ambient temperatures ranging from -35℃ to +40℃, wind speeds ≤ 35m/s, and in pollution grades of III or IV.
    How does the design prevent SF6 gas leakage?
    All seals utilize double-circle O-type seal rings to effectively prevent leaks, maintaining a very low yearly leakage rate of ≤ 1%.
    What is the mechanical life span of the LW39-126?
    The circuit breaker has a mechanical design life of 10,000 operations, offering a long service life with low maintenance requirements.