The LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is designed for use in power systems with a frequency of 50/60Hz and a normal voltage of 110kV. This essential power equipment is widely utilized in power plants and substations for effective control and protection, Manufactured in China, this circuit breaker features advanced thermal expansion self-arc-extinguishing technology and is filled with SF6 gas, renowned for its outstanding arc-extinguishing and electrical insulation properties. Our factory ensures that all seals utilize double-circle O-type seal rings, significantly reducing the risk of leakage. The circuit breaker is also equipped with a CT30 type spring operating mechanism and operates through a three-phase mechanical linkage, making it a reliable choice for various electrical applications. As a leading supplier, we are committed to providing high-quality solutions to meet the needs of the power industry

    General

    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker is applied in power system with 50/60Hz frequency, 110kV system normal voltage. It is the main power equipment used in power plant and substation for control and protection.
    LW39-126 type outdoor AC high voltage porcelain SF6 circuit breaker adopts thermal expansion self-arc-extinguish, filled with SF6 gas of well arc-extinguishing and electric insulation performance. All the seals adopt double-circle O type seal ring, which can effective prevent leakage; equipped with CT30 type spring operation mechanism, three phase mechanical linkage operation.

    Features

    LW39-126 type outdoor AC HV porcelain SF6 circuit breaker is a new type HV SF6 circuit breaker with high performance, which is designed according to national standards and domestic industry manufacture level. The main features are as follows:
    a. High breaking level, break reliably when outgoing terminal is in short circuit, out of phase and fault in near zone.
    b. Structure of arc-extinguishing chamber is simple,reliable and convenient to maintain.
    c. Long service life, have 20 times' breaking ability under full capacity and free of maintenance under normal operation in many years.
    d. Light operation force, adopts simple, reliable and compact spring operation mechanism.
    e. Rated charging pressure of gas is low and can be used in low temperature condition.
    f. Small occupied area.
    g. Low noise level and suitable to apply in residential area.
    h. Long overhaul period and less maintenance.
    i. Short installation time on the spot.

    Service condition

    Altitude ≤ 3000m
    Ambient temperature -35℃~+40℃
    Wind speed ≤ 35m/s
    Daily temperature difference ≤ 25℃
    Sunlight temperature 0.1w/cm2
    Relative humidity Average (monthly): ≤ 90
    Average(daily): ≤ 95
    Ice thickness ≤ 10mm
    Earthquake ≤ 9°
    Pollution grade III or IV

    Main Technical Parameters

    1.1 Main technical parameters of circuit breaker

    No. Items Unit Parameters
    1 System nominal voltage kV 110
    2 Rated voltage kV 126
    3 Rated frequency Hz 50/60
    4 Rated current A 3150
    5 Rated short-circuit breaking current kA 31.5 40
    6 Rated short-circuit making current kA 80 100
    7 Rated short time withstand current kA 31.5 40
    8 Rated peak withstand current kA 80 100
    9 Rated duration time of short-circuit S 4 3
    10 First-pole-to-clear factor 1.5
    11 Lightning impulse withstand voltage kV 650
    12 1min power frequency withstand voltage kV 275
    13 Creepage distance fracture/to earth mm/kV 25/31
    14 Rated operation sequence O-0.3s-CO-180s-CO
    15 Making time ms ≤ 110
    16 Breaking time ms ≤ 65
    17 Closing-opening time ms ≤ 85
    18 Closing time ms 80 ± 15
    19 Opening time ms 33 ± 7
    20 Fracture quantity of per pole pc 1
    21 Main loop resistance μΩ ≤ 45
    22 Mechanical life times 10000
    23 SF6gas pressure(20℃) Rated value Mpa 0.55 0.60
    Alarm value Mpa 0.50 0.55
    Interlock value Mpa 0.45 0.50
    24 SF6 moisture content ppm(V/V) ≤ 150
    25 Yearly leak rate of SF6 ≤ 1%
    26 Charging SF6 gas weight of each circuit breaker kg 7 9
    27 Total weight of each circuit breaker kg 2000
    28 Static tension of circuit breaker connecting terminal longitudinal N 1250
    horizontal N 750
    vertical N 1000
    29 Voltage of auxiliary circuit V AC220
    30 Closing coil rated voltage V DC220 DC110
    rated current A 2 3.3
    Coil resistance under 20℃ Ω 110 ± 5 33 ± 1.6
    31 Opening coil rated voltage V DC220 DC110
    rated current A 2 5.8
    Coil resistance under 20℃ Ω 110±5 19±1
    32 Energy Storage motor Voltage V AC220/DC220
    Power W 600
    33 Energy storage time S ≤ 15
    34 Heater Voltage V AC220
    Power W 100
    35 Standards GB1984

    1.2 Mechanical parameters of circuit breaker

    No. Items Unit Parameters
    1 Closing asynchronous between phases ms ≤ 5
    2 Opening asynchronous between phases ms ≤ 3
    3 Contact travel of moving-contact mm 38 ~ 42
    4 Main drive lever travel of mechanism mm 98 ~ 100
    5 Travel of moving-contact mm 118 ~ 122

    Drawing

    Frequently Asked Questions (FAQ)

    Q1: What is the application of the LW39-126 circuit breaker?
    A1: The LW39-126 outdoor AC high voltage porcelain SF6 circuit breaker is designed for power systems operating at 50/60Hz frequency with a 110kV system normal voltage. It serves as the primary control and protection equipment in power plants and substations.
    Q2: What operating mechanism does this circuit breaker use?
    A2: It is equipped with a CT30 type spring operating mechanism, which supports three-phase mechanical linkage operation for reliable switching performance.
    Q3: How does the arc-extinguishing system work in the LW39-126?
    A3: The circuit breaker utilizes thermal expansion self-arc-extinguishing technology. It is filled with SF6 gas, which provides outstanding arc-extinguishing capabilities and electrical insulation.
    Q4: What are the key environmental service conditions for installation?
    A4: The standard operating conditions include an altitude of ≤ 3000m, ambient temperatures from -35℃ to +40℃, wind speeds ≤ 35m/s, and a maximum daily temperature difference of ≤ 25℃.
    Q5: What is the mechanical service life of this circuit breaker?
    A5: The LW39-126 circuit breaker is highly durable, with a rated mechanical life of 10,000 operations, offering a long overhaul period and minimal maintenance requirements.
    Q6: What standards does the LW39-126 circuit breaker comply with?
    A6: The circuit breaker is designed, manufactured, and tested in compliance with the GB1984 national standard.