China LZZBJ9-35D Indoor Epoxy Resin Casting Current Transformer - Lightweight, Pollution-Resistant Suppliers & Factory

General
The LZZB9-35D1 indoor single-phase epoxy resin casting current transformer is a compact and lightweight device designed for optimal performance. Manufactured in China, this fully enclosed current transformer is made using high-quality epoxy resin, ensuring excellent resistance to pollution and moisture. Its small size allows for versatile installation in any orientation, making it a preferred choice among suppliers and factories looking for reliable and efficient solutions. With the LZZB9-35D1, you can trust in a product that combines durability and functionality for various industrial applications.

    General
    It is designed for use in power systems with a rated frequency of 50 or 60 Hz and a rated voltage of 35 kV and below, installed indoors. It is mainly used for electric energy metering, current measurement, and relay protection. This type of current transformer is generally used in air insulated switchgear rated at 6 to 35 kV.
    Standards
    • IEC61869.1-2007 Instrument transformers Part 1: General technical requirements
    • IEC61869.2-2012 Instrument Transformers Part2: Complementary technical requirements for current transformers
    • GB311.1-1997 Insulation and coordination of high-voltage transmission and transformation equipment
    • GB 5583-1985 Partial discharge measurement of instrument transformers
    • GB/T 22071.1-2008 Instrument Transformer Test Guidelines Part I: Current Transformers
    • JJG 1021-2007 Electrical Transformer Verification Regulations
    Service Conditions
    Ambient Temperature
    • Maximum temperature: + 40℃
    • Minimum temperature: - 5℃
    • Average daily temperature: Not exceed 30℃
    Altitude & Environment
    • Altitude: Not exceed 1000m
    • Insolation radiation: Effects can be ignored
    • Air Quality: Free of obvious dust, smoke, corrosive gases, steam or salt
    Humidity Conditions
    • 24h Average Relative Humidity: ≤ 95%
    • 24h Average Water Vapor Pressure: ≤ 2.2kPa
    • Monthly Average Relative Humidity: ≤ 90%
    • Monthly Average Water Vapor Pressure: ≤ 1.8kPa
    Technical Data
    • Rated insulation level: 40.5/95/185kV
    • Rated frequency: 50Hz or 60Hz
    • Rated secondary current: 5A or 1A
    Rated primary current (A) Accuracy class combination Accuracy class and rated output Short time thermal current (kA/s) Rated dynamic current (kA) Weight (kg)
    0.2(S) / 0.5(S) 0.5 5P20 5P25 5P30 kA S
    20-100 0.2(S)/5P

    0.5(S)/5P

    0.2(S)/0.5(S)/5P

    0.2(S)/0.5(S)/5P/5P
    30 30 30 25 20 150│1n 2 375│1n 140
    150 25 1 63
    200-250 31.5 1 80
    300-500 31.5 2
    600-800 31.5 4
    1000-3150 31.5 4
    ※Note: If the parameters are beyond the above range, it can be discussed and confirmed with us.
    Appearance and installation size
    Product appearance and installation dimensions
    Frequently Asked Questions (FAQ)
    What are the primary applications of this current transformer?
    This current transformer is designed for indoor power systems with a rated voltage of 35 kV and below. It is mainly used for electric energy metering, current measurement, and relay protection within air-insulated switchgear.
    What standards does this current transformer comply with?
    It complies with key international and national standards including IEC61869.1-2007, IEC61869.2-2012, GB311.1-1997, GB 5583-1985, GB/T 22071.1-2008, and JJG 1021-2007.
    What are the environmental limits for installing this transformer?
    It is suitable for indoor installation at altitudes not exceeding 1000m. The ambient temperature should remain between -5℃ and +40℃ (with a daily average not exceeding 30℃), and the air should be free of dust, corrosive gases, steam, or salt.
    What are the humidity limits for safe operation?
    The daily average relative humidity must not exceed 95% (water vapor pressure ≤ 2.2kPa), and the monthly average relative humidity must not exceed 90% (water vapor pressure ≤ 1.8kPa).
    Can I customize the technical parameters if my requirements are outside the standard range?
    Yes. If your required parameters (such as rated primary current, accuracy class, or outputs) fall outside the standard ranges listed in our technical data table, please contact us directly to discuss and confirm custom specifications.