0102030405
China Metal-Oxide Surge Arrester Supplier - High-Quality Protection from Over-Voltage | Factory Direct Supply
General
Polymer-housed metal-oxide surge arrester is the scientific achievement that combines the advantages of organic insulation material and traditional porcelain-clad MOA technique. It has excellent insulation performance, high dialectical strength, anti-leaking, anti-electric corrosion, heat-resisting, cold-resisting, anti-aging, explosion-proof, and good chemical stability, hydrophobic property, and nice sealing. It is designed and manufactured strictly following the standard of IEC and GB, and achieves advantage against the competitive international products.
Normal Service conditions
- For indoors and outdoors;
- Ambient air temperature within the range of -40℃~+40℃;
- Altitude not exceeding 2600m;
- Frequency for A.C. power supply not less than 48Hz and not exceeding 62Hz;
- Power Frequency voltage applied continuously between the terminals of the arrester not exceeding its continuous operating voltage;
- Earthquake intensity: 8 degree and below;
- Maximal wind velocity not exceeding 35m/s.
※ Please indicate in the contract, at exceptionally movement condition.
Description of type
According to the JB/T 8459-2011《Designation for surge arrester products》, the type of MOA shows as below:
Technical parameters
Gapless MOA for distribution
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WS-5/15 | 3 | 5 | 4.0 | 7.5 | 5 | 15.0 | 17.3 | 12.8 | 76 | 200 | 1 |
| YH5WS-10/30 | 6 | 10 | 8.0 | 15.0 | 5 | 30.0 | 34.6 | 25.6 | 76 | 200 | 1 |
| YH5WS-12/35.8 | 10 | 12 | 9.6 | 18.0 | 5 | 35.8 | 41.2 | 30.6 | 76 | 255 | 1 |
| YH5WS-15/45.6 | 10 | 15 | 12.0 | 23.0 | 5 | 45.6 | 52.5 | 39.0 | 76 | 255 | 1 |
| YH5WS-17/50 | 10 | 17 | 13.6 | 25.0 | 5 | 50.0 | 57.5 | 42.5 | 76 | 255 | 1 |
Gapless MOA for power station
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WZ-5/13.5 | 3 | 5 | 4.0 | 7.2 | 5 | 13.5 | 15.5 | 11.5 | 82 | 200 | 1 |
| YH5WZ-10/27 | 6 | 10 | 8.0 | 14.4 | 5 | 27.0 | 31.0 | 23.0 | 82 | 200 | 1 |
| YH5WZ-12/32.4 | 10 | 12 | 9.6 | 17.4 | 5 | 32.4 | 37.2 | 27.6 | 82 | 255 | 1 |
| YH5WZ-15/40.5 | 10 | 15 | 12.0 | 21.8 | 5 | 40.5 | 46.5 | 34.5 | 82 | 255 | 1 |
| YH5WZ-17/45 | 10 | 17 | 13.6 | 24.0 | 5 | 45.0 | 51.8 | 38.3 | 82 | 255 | 1 |
| Y5WZ-26/66 | 20 | 26 | 20.8 | 37.0 | 5 | 66.0 | 76.0 | 56.0 | 232 | 995 | 5 |
| YH5WZ-26/66 | 114 | 345 | 4 | ||||||||
| Y5WZ-32/85 | 20 | 32 | 25.6 | 47.0 | 5 | 85.0 | 95.0 | 75.0 | 232 | 995 | 5 |
| YH5WZ-32/85 | 114 | 405 | 4 | ||||||||
| Y5WZ-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 154.0 | 114.0 | 232 | 995 | 5 |
| YH5WZ-51/134 | 114 | 525 | 4 | ||||||||
| Y5WZ-84/221 | 66 | 84 | 67.2 | 121 | 5 | 221 | 254 | 188 | 252 | 1200 | 6 |
| YH5WZ-84/221 | 195 | 1296 | 8 | ||||||||
| Y5WZ-90/235 | 66 | 90 | 72.5 | 130 | 5 | 235 | 270 | 201 | 252 | 1200 | 6 |
| YH5WZ-90/235 | 195 | 1296 | 8 | ||||||||
| Y10WZ-90/235 | 66 | 90 | 72.5 | 130 | 10 | 235 | 264 | 201 | 252 | 1200 | 6 |
| YH10WZ-90/235 | 195 | 1296 | 8 | ||||||||
| Y5WZ-96/250 | 110 | 96 | 75 | 140 | 5 | 250 | 288 | 213 | 270 | 1620 | 7 |
| YH5WZ-96/250 | 195 | 1296 | 8 | ||||||||
| Y10WZ-96/250 | 110 | 96 | 75 | 140 | 10 | 250 | 280 | 213 | 270 | 1620 | 7 |
| YH10WZ-96/250 | 195 | 1296 | 8 | ||||||||
Gapless MOA for power station (Continued)
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| Y5WZ-100/260 | 110 | 100 | 78 | 145 | 5 | 260 | 299 | 221 | 270 | 1620 | 7 |
| YH5WZ-100/260 | 195 | 1296 | 8 | ||||||||
| Y10WZ-100/260 | 110 | 100 | 78 | 145 | 10 | 260 | 291 | 221 | 270 | 1620 | 7 |
| YH10WZ-100/260 | 195 | 1296 | 8 | ||||||||
| Y5WZ-102/266 | 110 | 102 | 79.6 | 148 | 5 | 266 | 305 | 226 | 270 | 1620 | 7 |
| YH5WZ-102/266 | 195 | 1296 | 8 | ||||||||
| Y10WZ-102/266 | 110 | 102 | 79.6 | 148 | 10 | 266 | 297 | 226 | 270 | 1620 | 7 |
| YH10WZ-102/266 | 195 | 1296 | 8 | ||||||||
| Y5WZ-108/281 | 110 | 108 | 84 | 157 | 5 | 281 | 323 | 239 | 270 | 1620 | 7 |
| YH5WZ-108/281 | 195 | 1296 | 8 | ||||||||
| Y10WZ-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 315 | 239 | 270 | 1620 | 7 |
| YH10WZ-108/281 | 195 | 1296 | 8 | ||||||||
| Y10WZ-192/500 | 220 | 192 | 150 | 280 | 10 | 500 | 560 | 426 | 278 | 2880 | 9 |
| YH10WZ-192/500 | 216 | 2635 | 10 | ||||||||
| Y10WZ-200/520 | 220 | 200 | 156 | 290 | 10 | 520 | 582 | 442 | 278 | 2880 | 9 |
| YH10WZ-200/520 | 216 | 2635 | 10 | ||||||||
| Y10WZ-204/532 | 220 | 204 | 159 | 296 | 10 | 532 | 594 | 452 | 278 | 2880 | 9 |
| YH10WZ-204/532 | 216 | 2635 | 10 | ||||||||
| Y10WZ-216/562 | 220 | 216 | 168.5 | 314 | 10 | 562 | 630 | 478 | 278 | 2880 | 9 |
| YH10WZ-216/562 | 216 | 2635 | 10 | ||||||||
| Y10WZ-288/698 | 330 | 288 | 219 | 408 | 10 | 698 | 782 | 593 | 298 | 5100 | 11 |
| YH10WZ-288/698 | 377 | 3850 | 12 | ||||||||
| Y10WZ-300/727 | 330 | 300 | 228 | 425 | 10 | 727 | 814 | 618 | 298 | 5100 | 11 |
| YH10WZ-300/727 | 377 | 3850 | 12 | ||||||||
| Y10WZ-306/742 | 330 | 306 | 233 | 433 | 10 | 742 | 831 | 630 | 298 | 5100 | 11 |
| YH10WZ-306/742 | 377 | 3850 | 12 | ||||||||
| Y10WZ-312/760 | 330 | 312 | 237 | 442 | 10 | 760 | 847 | 643 | 298 | 5100 | 11 |
| YH10WZ-312/760 | 377 | 3850 | 12 | ||||||||
| Y10WZ-324/789 | 330 | 324 | 246 | 459 | 10 | 789 | 880 | 668 | 298 | 5100 | 11 |
| YH10WZ-324/789 | 377 | 3850 | 12 | ||||||||
| Y20WZ-420/1046 | 500 | 420 | 318 | 565 | 20 | 1046 | 1170 | 858 | 418 | 6240 | 11 |
| YH20WZ-420/1046 | 377 | 5850 | 12 | ||||||||
| Y20WZ-444/1106 | 500 | 444 | 324 | 597 | 20 | 1106 | 1238 | 957 | 418 | 6240 | 11 |
| YH20WZ-444/1106 | 377 | 5850 | 12 | ||||||||
| Y20WZ-468/1166 | 500 | 468 | 330 | 630 | 20 | 1166 | 1306 | 630 | 418 | 6240 | 11 |
| YH20WZ-468/1166 | 377 | 5850 | 12 | ||||||||
Gapless MOA for shunt compensating capacitor
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| YH5WR-5/13.5 | 3 | 5 | 4.0 | 7.2 | 5 | 13.5 | 10.5 | 88 | 200 | 1 |
| YH5WR-10/27 | 6 | 10 | 8.0 | 14.4 | 5 | 27.0 | 21.0 | 88 | 200 | 1 |
| YH5WR-12/32.4 | 10 | 12 | 9.6 | 17.4 | 5 | 32.4 | 25.2 | 88 | 255 | 1 |
| YH5WR-15/40.5 | 10 | 15 | 12.0 | 21.8 | 5 | 40.5 | 31.5 | 88 | 255 | 1 |
| YH5WR-17/46 | 10 | 17 | 13.6 | 24.0 | 5 | 46.0 | 35.0 | 88 | 255 | 1 |
| Y5WR-26/66 | 20 | 26 | 20.8 | 37.0 | 5 | 66.0 | 53.0 | 232 | 995 | 5 |
| YH5WR-26/66 | 120 | 345 | 4 | |||||||
| Y5WR-32/85 | 20 | 32 | 25.6 | 47.0 | 5 | 85.0 | 68.0 | 232 | 995 | 5 |
| YH5WR-32/85 | 120 | 405 | 4 | |||||||
| Y5WR-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 105.0 | 232 | 995 | 5 |
| YH5WR-51/134 | 120 | 525 | 4 | |||||||
| Y5WR-84/221 | 66 | 84 | 67.2 | 121 | 5 | 221 | 176 | 252 | 1200 | 6 |
| YH5WR-84/221 | 195 | 1296 | 8 | |||||||
| Y5WR-90/236 | 66 | 90 | 72.5 | 130 | 5 | 236 | 190 | 252 | 1200 | 6 |
| YH5WR-90/236 | 195 | 1296 | 8 | |||||||
| Y10WR-105/265 | 66 | 105 | 84 | 152 | 10 | 265 | 225 | 252 | 1200 | 6 |
| YH10WR-105/265 | 195 | 1296 | 8 | |||||||
| Y10WR-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 239 | 270 | 1620 | 7 |
| YH10WR-108/28 | 195 | 1296 | 8 | |||||||
| Y10WR-174/372 | 110 | 174 | 139 | 240 | 10 | 372 | 336 | 351 | 2135 | 25 |
| YH10WR-174/372 | 377 | 2200 | 26 | |||||||
Arrester for low voltage system
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Residual voltage at Lightning current impulse kV.peak | Parachute diameter Φ mm | Height H mm | Fig. No |
| kV.rms | |||||||||
| YH1.5W-0.28/1.3 | 0.22 | 0.28 | 0.24 | 0.6 | 1.5 | 1.3 | 35 | 85 | 2 |
| YH1.5W-0.5/2.6 | 0.38 | 0.5 | 0.42 | 1.2 | 1.5 | 2.6 | 35 | 85 | 2 |
Gapless MOA for motor and generators
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH2.5WD-4/9.5 | 3.15 | 4 | 3.2 | 5.7 | 2.5 | 9.5 | 10.7 | 7.6 | 88 | 200 | 1 |
| YH2.5WD-8/18.7 | 6.3 | 8 | 6.3 | 11.2 | 2.5 | 18.7 | 21.0 | 15.0 | 88 | 200 | 1 |
| YH2.5WD-13.5/31 | 10.5 | 13.5 | 10.5 | 18.6 | 2.5 | 31.0 | 34.7 | 25.0 | 88 | 255 | 1 |
| YH5WD-4/9.5 | 3.15 | 4 | 3.2 | 5.7 | 5 | 9.5 | 10.7 | 7.6 | 88 | 200 | 1 |
| YH5WD-8/18.7 | 6.3 | 8 | 6.3 | 11.2 | 5 | 18.7 | 21.0 | 15.0 | 88 | 200 | 1 |
| YH5WD-13.5/31 | 10.5 | 13.5 | 10.5 | 18.6 | 5 | 31.0 | 34.7 | 25.0 | 88 | 255 | 1 |
| YH5WD-17.5/40 | 13.8 | 17.5 | 13.8 | 24.4 | 5 | 40.0 | 44.8 | 32.0 | 88 | 255 | 1 |
| YH5WD-20/45 | 15.75 | 20 | 15.8 | 28.0 | 5 | 45.0 | 50.4 | 36.0 | 88 | 255 | 1 |
| YH5WD-23/51 | 18.0 | 23 | 18.0 | 31.9 | 5 | 51.0 | 57.2 | 40.8 | 88 | 310 | 1 |
| YH5WD-25/56.2 | 20.0 | 25 | 20.0 | 35.4 | 5 | 56.2 | 62.9 | 45.0 | 88 | 310 | 1 |
※Note:The arrester which nominal discharge current is 2.5kA used for protection of Motor.
The arrester which nominal discharge current is 5kA used for protection of Generators.
The arrester which nominal discharge current is 5kA used for protection of Generators.
Gapless MOA with Polymer-housed for transmission lines
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WX-34/90 | 20 | 34 | 27.2 | 50.0 | 5 | 90.0 | 104.0 | 80.0 | 114 | 475 | 13 |
| YH5WX-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 154.0 | 114.0 | 114 | 595 | 13 |
| YH⁵WX-54/L49 | 35 | 54.0 | 43.2 | 77.0 | 5 | 142.0 | 163.0 | 121.0 | 114 | 595 | 13 |
| YH5WX-54/150 | 35 | 54.0 | 43.2 | 80.0 | 5 | 150.0 | 169.0 | 128.0 | 114 | 595 | 13 |
| YH5WX-96/250 | 66 | 96 | 75 | 140 | 5 | 250 | 288 | 213 | 195 | 1355 | 14 |
| YH5WX-96/275 | 66 | 96 | 75 | 154 | 5 | 275 | 316 | 234 | 195 | 1355 | 14 |
| YH5WX-108/281 | 110 | 108 | 84 | 157 | 5 | 281 | 323 | 239 | 195 | 1355 | 14 |
| YH5WX-108/300 | 110 | 108 | 84 | 173 | 5 | 309 | 348 | 263 | 195 | 1355 | 14 |
| YH1OWX-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 315 | 239 | 195 | 1355 | 14 |
| YH10WX-108/309 | 110 | 108 | 84 | 173 | 10 | 309 | 348 | 263 | 195 | 1355 | 14 |
| YH10WX-216/562 | 220 | 216 | 168 | 314 | 10 | 562 | 630 | 478 | 195 | 2685 | 15 |
| YH10WX-216/618 | 220 | 216 | 168.5 | 346 | 10 | 618 | 693 | 526 | 195 | 2685 | 15 |
| YH10WX-312/760 | 330 | 312 | 237 | 442 | 10 | 760 | 847 | 643 | 216 | 3530 | 16 |
| YH10WX-324/789 | 330 | 324 | 246 | 459 | 10 | 789 | 880 | 668 | 216 | 3530 | 16 |
| YH20WX-468/1166 | 500 | 468 | 330 | 630 | 20 | 1166 | 1306 | 630 | 377 | 5850 | 12 |
Gapless MOA for electrical railway
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| Y5WT-42/105 | 27.5 | 42 | 31.5 | 58.0 | 5 | 105.0 | 118.0 | 89.0 | 232 | 995 | 5 |
| YH5WT-42/105 | 128 | 525 | 4 | ||||||||
| Y5WT-42/110 | 27.5 | 42 | 31.5 | 60.0 | 5 | 110.0 | 127.0 | 94.0 | 232 | 995 | 5 |
| YH5WT-42/110 | 128 | 525 | 4 | ||||||||
| Y5WT-42/120 | 27.5 | 42 | 34.0 | 65.0 | 5 | 120.0 | 138.0 | 98.0 | 232 | 995 | 5 |
| YH5WT-42/120 | 128 | 525 | 4 | ||||||||
| Y5WT-84/240 | 55 | 84 | 68 | 130 | 5 | 240 | 276 | 196 | 252 | 1200 | 6 |
| YH5WT-84/240 | 195 | 1296 | 8 | ||||||||
| Y5WT-100/260 | 110 | 100 | 73 | 145 | 5 | 260 | 291 | 221 | 270 | 1620 | 7 |
| YH5WT-100/260 | 195 | 1296 | 8 | ||||||||
| Y5WT-100/275 | 110 | 100 | 73 | 150 | 5 | 275 | 316 | 234 | 270 | 1620 | 7 |
| YH5WT-100/275 | 195 | 1296 | 8 | ||||||||
| Y10WT-100/290 | 110 | 100 | 73 | 158 | 10 | 290 | 325 | 247 | 270 | 1620 | 7 |
| YH10WT-100/290 | 195 | 1296 | 8 | ||||||||
| Y10WT-100/295 | 110 | 100 | 73 | 160 | 10 | 295 | 330 | 251 | 270 | 1620 | 7 |
| YH10WT-100/295 | 195 | 1296 | 8 | ||||||||
Gapless MOA for electrical machinery neutral point
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| YH1.5W-2.4/6 | 3.15 | 2.4 | 1.9 | 3.4 | 1.5 | 6.0 | 5.0 | 88 | 200 | 1 |
| YH1.5W-4.8/12 | 6.3 | 4.8 | 3.8 | 6.8 | 1.5 | 12.0 | 10.0 | 88 | 200 | 1 |
| YH1.5W-8/19 | 10.5 | 8 | 6.4 | 11.4 | 1.5 | 19.0 | 15.9 | 88 | 200 | 1 |
| YH1.5W-10.5/23 | 13.8 | 10.5 | 8.4 | 14.9 | 1.5 | 23.0 | 19.2 | 88 | 200 | 1 |
| YH1.5W-12/26 | 15.75 | 12 | 9.6 | 17.0 | 1.5 | 26.0 | 21.6 | 88 | 200 | 1 |
| YH1.5W-13.7/29.2 | 18.0 | 13.7 | 11.0 | 19.5 | 1.5 | 29.2 | 24.3 | 88 | 255 | 1 |
| YH1.5W-15.2/31.7 | 20.0 | 15.2 | 12.2 | 21.6 | 1.5 | 31.7 | 26.4 | 88 | 255 | 1 |
MOA with parallel gaps for electrical machinery
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Residual voltage at Nominal discharge current kV.peak ≯ | Parachute diameter Φ mm | Height H mm | Fig. No |
| kV.rms | |||||||||
| YH0.5B-8/11 | 6.3 | 8 | 6.3 | 11.5 | 0.5 | 11.0 | 88 | 255 | 1 |
| YH0.5B-13.5/20 | 10.5 | 13.5 | 10.5 | 21.0 | 0.5 | 20.0 | 88 | 255 | 1 |
Gapless MOA for transformer neutral point
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| Y1.5W-30/98 | 35 | 30 | 24.0 | 61.0 | 1.5 | 98.0 | 88.0 | 232 | 995 | 5 |
| YH1.5W-30/98 | 120 | 525 | 4 | |||||||
| Y1.5W-60/144 | 110 | 60 | 48 | 85 | 1.5 | 144 | 135 | 232 | 1145 | 5 |
| YH1.5W-60/144 | 142 | 585 | 4 | |||||||
| Y1.5W-72/186 | 110 | 72 | 58 | 103 | 1.5 | 186 | 174 | 110 | 215 | 5 |
| YH1.5W-72/186 | 142 | 585 | 4 | |||||||
| Y1.5W-96/260 | 500 | 96 | 77 | 137 | 1.5 | 260 | 243 | 270 | 1620 | 7 |
| YH1.5W-96/260 | 195 | 1296 | 8 | |||||||
| Y1.5W-144/320 | 220 | 144 | 116 | 205 | 1.5 | 320 | 299 | 270 | 1620 | 7 |
| YH1.5W-144/320 | 195 | 1296 | 8 | |||||||
| Y1.5W-210/440 | 330 | 210 | 168 | 285 | 1.5 | 440 | 410 | 278 | 2880 | 9 |
| YH1.5W-210/440 | 216 | 2635 | 10 | |||||||
MOA with series gap
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Power frequency discharge voltage kV.rms ≮ | Discharge voltage at impulse 1.2/50μS kV.peak ≯ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5CS-3.8/15 | 3 | 3.8 | 3.0 | 9.0 | 21.0 | 5 | 15.0 | 17.2 | 82 | 200 | 1 |
| YH5CS-7.6/27 | 6 | 7.6 | 6.1 | 16.0 | 35.0 | 5 | 27.0 | 31.0 | 82 | 200 | 1 |
| YH5CS-12.7/45 | 10 | 12.7 | 10.2 | 26.0 | 50.0 | 5 | 45.0 | 51.8 | 82 | 255 | 1 |
| YH5CZ-3.8/12 | 3 | 3.8 | 3.0 | 9.0 | 20.0 | 5 | 12.0 | 13.8 | 82 | 200 | 1 |
| YH5CZ-7.6/24 | 6 | 7.6 | 6.1 | 16.0 | 30.0 | 5 | 24.0 | 27.6 | 82 | 200 | 1 |
| YH5CZ-12.7/41 | 10 | 12.7 | 12.7 | 26.0 | 45.0 | 5 | 41.0 | 47.2 | 82 | 255 | 1 |
| YH5CZ-42/124 | 35 | 42 | 33.6 | 80.0 | 134.0 | 5 | 124.0 | 142.6 | 114 | 585 | 4 |
| YH2.5CD-3.8/9.5 | 3.15 | 3.8 | 3.0 | 7.5 | 9.5 | 2.5 | 9.5 | 10.7 | 88 | 200 | 1 |
| YH2.5CD-7.6/18.7 | 6.3 | 7.6 | 6.1 | 15.0 | 18.7 | 2.5 | 18.7 | 21.0 | 88 | 200 | 1 |
| YH2.5CD-12.7/3 | 10.5 | 12.7 | 10.2 | 25.0 | 31.0 | 2.5 | 31.0 | 34.7 | 88 | 255 | 1 |
| YH5CD-3.8/9.5 | 3.15 | 3.8 | 3.0 | 7.5 | 9.5 | 5 | 9.5 | 10.7 | 88 | 200 | 1 |
| YH5CD-7.6/18.7 | 6.3 | 7.6 | 6.1 | 15.0 | 18.7 | 5 | 18.7 | 21.0 | 88 | 200 | 1 |
| YH5CD-12.7/31 | 10.5 | 12.7 | 10.2 | 25.0 | 31.0 | 5 | 31.0 | 34.7 | 88 | 255 | 1 |
※Note:The arrester which nominal discharge current is 2.5kA used for protection of Motor.
The arrester which nominal discharge current is 5kA used for protection of Generators.
The arrester which nominal discharge current is 5kA used for protection of Generators.
Polymer-housed MOA with gaps for transmission lines
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Reference voltage at D.C.1mA of units k V . D C ≮ | Power frequency withstand voltage kV.rms ≯ | 50% Lightning impulse sparkover voltage kV.peak ≯ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5CX-13/40 | 10 | 13 | 20.0 | 26 | 100 | 5 | 40.0 | 46.0 | 76 | 185 | 17 |
| YH5CX-42/120 | 35 | 42 | 60.0 | 70 | 240 | 5 | 120.0 | 138.0 | 120 | 545 | 18 |
| 120 | 960 | 19 | |||||||||
| YH5CX-75/218 | 66 | 75 | 108 | 117 | 400 | 5 | 218 | 246 | 195 | 910 | 20 |
| 195 | 1600 | 21 | |||||||||
| YH5CX-90/260 | 110 | 90 | 130 | 170 | 525 | 5 | 260 | 292 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-90/260 | 110 | 90 | 130 | 170 | 525 | 10 | 260 | 292 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-96/280 | 110 | 96 | 140 | 170 | 525 | 10 | 280 | 314 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-102/296 | 110 | 102 | 148 | 170 | 525 | 10 | 296 | 332 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-180/520 | 220 | 180 | 260 | 340 | 900 | 10 | 520 | 584 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-192/560 | 220 | 192 | 280 | 340 | 900 | 10 | 560 | 628 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-204/592 | 220 | 204 | 296 | 340 | 900 | 10 | 592 | 664 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-288/775 | 330 | 288 | 408a | 460 | 1300 | 10 | 775 | 868 | 195 | 2450 | 22 |
| YH20CX-396/1050 | 500 | 396 | 561 | 510 | 1760 | 20 | 1050 | 1171 | 216 | 3600 | 23 |
※Note: Reference voltage at D.C. 2mA.
The structure and installation dimensional drawing
Frequently Asked Questions (FAQ)
What are the primary advantages of polymer-housed metal-oxide surge arresters?
They combine the benefits of organic insulation materials and traditional porcelain-clad MOA techniques. They offer excellent insulation performance, high dialectical strength, anti-leaking, anti-electric corrosion, heat and cold resistance, anti-aging, explosion-proof properties, good chemical stability, hydrophobic properties, and superior sealing.
What are the normal service conditions for these surge arresters?
Normal service conditions include indoor/outdoor installation, ambient temperatures from -40℃ to +40℃, altitude not exceeding 2600m, A.C. power frequency between 48Hz and 62Hz, wind velocity up to 35m/s, and earthquake intensity of 8 degrees or below.
What is the difference between arresters used for motor protection and generator protection?
According to the technical parameters, arresters with a nominal discharge current of 2.5kA are used for the protection of motors, while arresters with a nominal discharge current of 5kA are used to protect generators.
What standard is followed for the classification and designation of these surge arresters?
The designation and product type classification strictly follow the JB/T 8459-2011 standard (Designation for surge arrester products) and align with international IEC and GB standards.
What should be specified if the installation environment has exceptional movement conditions?
If the surge arrester is to be used under exceptionally high movement or special environmental conditions, this requirement must be explicitly indicated in the purchase contract.