0102030405
China Metal-Oxide Surge Arrester Suppliers | High-Quality Factory Products for Over-Voltage Protection
General
Polymer-housed metal-oxide surge arrester is the scientific achievement that combines the advantages of organic insulation material and traditional porcelain-clad MOA technique. It has excellent insulation performance, high dialectical strength, anti-leaking, anti-electric corrosion, heat-resisting, cold-resisting, anti-aging, explosion-proof, and good chemical stability, hydrophobic property, and nice sealing. It is designed and manufactured strictly following the standard of IEC and GB, and achieves advantage against the competitive international products.
Normal Service conditions
- a. For indoors and outdoors;
- b. Ambient air temperature within the range of -40℃~+40℃;
- c. Altitude not exceeding 2600m;
- d. Frequency for A.C. power supply not less than 48Hz and not exceeding 62Hz;
- e. Power Frequency voltage applied continuously between the terminals of the arrester not exceeding its continuous operating voltage;
- f. Earthquake intensity: 8 degree and below;
- g. Maximal wind velocity not exceeding 35m/s.
※ Please indicate in the contract, at exceptionally movement condition.
Description of type
According to the JB/T 8459-2011《Designation for surge arrester products》, the type of MOA shows as below:
Technical parameters
Gapless MOA for distribution
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WS-5/15 | 3 | 5 | 4.0 | 7.5 | 5 | 15.0 | 17.3 | 12.8 | 76 | 200 | 1 |
| YH5WS-10/30 | 6 | 10 | 8.0 | 15.0 | 5 | 30.0 | 34.6 | 25.6 | 76 | 200 | 1 |
| YH5WS-12/35.8 | 10 | 12 | 9.6 | 18.0 | 5 | 35.8 | 41.2 | 30.6 | 76 | 255 | 1 |
| YH5WS-15/45.6 | 10 | 15 | 12.0 | 23.0 | 5 | 45.6 | 52.5 | 39.0 | 76 | 255 | 1 |
| YH5WS-17/50 | 10 | 17 | 13.6 | 25.0 | 5 | 50.0 | 57.5 | 42.5 | 76 | 255 | 1 |
Gapless MOA for power station
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WZ-5/13.5 | 3 | 5 | 4.0 | 7.2 | 5 | 13.5 | 15.5 | 11.5 | 82 | 200 | 1 |
| YH5WZ-10/27 | 6 | 10 | 8.0 | 14.4 | 5 | 27.0 | 31.0 | 23.0 | 82 | 200 | 1 |
| YH5WZ-12/32.4 | 10 | 12 | 9.6 | 17.4 | 5 | 32.4 | 37.2 | 27.6 | 82 | 255 | 1 |
| YH5WZ-15/40.5 | 10 | 15 | 12.0 | 21.8 | 5 | 40.5 | 46.5 | 34.5 | 82 | 255 | 1 |
| YH5WZ-17/45 | 10 | 17 | 13.6 | 24.0 | 5 | 45.0 | 51.8 | 38.3 | 82 | 255 | 1 |
| Y5WZ-26/66 | 20 | 26 | 20.8 | 37.0 | 5 | 66.0 | 76.0 | 56.0 | 232 | 995 | 5 |
| YH5WZ-26/66 | 114 | 345 | 4 | ||||||||
| Y5WZ-32/85 | 20 | 32 | 25.6 | 47.0 | 5 | 85.0 | 95.0 | 75.0 | 232 | 995 | 5 |
| YH5WZ-32/85 | 114 | 405 | 4 | ||||||||
| Y5WZ-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 154.0 | 114.0 | 232 | 995 | 5 |
| YH5WZ-51/134 | 114 | 525 | 4 | ||||||||
| Y5WZ-84/221 | 66 | 84 | 67.2 | 121 | 5 | 221 | 254 | 188 | 252 | 1200 | 6 |
| YH5WZ-84/221 | 195 | 1296 | 8 | ||||||||
| Y5WZ-90/235 | 66 | 90 | 72.5 | 130 | 5 | 235 | 270 | 201 | 252 | 1200 | 6 |
| YH5WZ-90/235 | 195 | 1296 | 8 | ||||||||
| Y10WZ-90/235 | 66 | 90 | 72.5 | 130 | 10 | 235 | 264 | 201 | 252 | 1200 | 6 |
| YH10WZ-90/235 | 195 | 1296 | 8 | ||||||||
| Y5WZ-96/250 | 110 | 96 | 75 | 140 | 5 | 250 | 288 | 213 | 270 | 1620 | 7 |
| YH5WZ-96/250 | 195 | 1296 | 8 | ||||||||
| Y10WZ-96/250 | 110 | 96 | 75 | 140 | 10 | 250 | 280 | 213 | 270 | 1620 | 7 |
| YH10WZ-96/250 | 195 | 1296 | 8 | ||||||||
Gapless MOA for power station (Continued)
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| Y5WZ-100/260 | 110 | 100 | 78 | 145 | 5 | 260 | 299 | 221 | 270 | 1620 | 7 |
| YH5WZ-100/260 | 195 | 1296 | 8 | ||||||||
| Y10WZ-100/260 | 110 | 100 | 78 | 145 | 10 | 260 | 291 | 221 | 270 | 1620 | 7 |
| YH10WZ-100/260 | 195 | 1296 | 8 | ||||||||
| Y5WZ-102/266 | 110 | 102 | 79.6 | 148 | 5 | 266 | 305 | 226 | 270 | 1620 | 7 |
| YH5WZ-102/266 | 195 | 1296 | 8 | ||||||||
| Y10WZ-102/266 | 110 | 102 | 79.6 | 148 | 10 | 266 | 297 | 226 | 270 | 1620 | 7 |
| YH10WZ-102/266 | 195 | 1296 | 8 | ||||||||
| Y5WZ-108/281 | 110 | 108 | 84 | 157 | 5 | 281 | 323 | 239 | 270 | 1620 | 7 |
| YH5WZ-108/281 | 195 | 1296 | 8 | ||||||||
| Y10WZ-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 315 | 239 | 270 | 1620 | 7 |
| YH10WZ-108/281 | 195 | 1296 | 8 | ||||||||
| Y10WZ-192/500 | 220 | 192 | 150 | 280 | 10 | 500 | 560 | 426 | 278 | 2880 | 9 |
| YH10WZ-192/500 | 216 | 2635 | 10 | ||||||||
| Y10WZ-200/520 | 220 | 200 | 156 | 290 | 10 | 520 | 582 | 442 | 278 | 2880 | 9 |
| YH10WZ-200/520 | 216 | 2635 | 10 | ||||||||
| Y10WZ-204/532 | 220 | 204 | 159 | 296 | 10 | 532 | 594 | 452 | 278 | 2880 | 9 |
| YH10WZ-204/532 | 216 | 2635 | 10 | ||||||||
| Y10WZ-216/562 | 220 | 216 | 168.5 | 314 | 10 | 562 | 630 | 478 | 278 | 2880 | 9 |
| YH10WZ-216/562 | 216 | 2635 | 10 | ||||||||
| Y10WZ-288/698 | 330 | 288 | 219 | 408 | 10 | 698 | 782 | 593 | 298 | 5100 | 11 |
| YH10WZ-288/698 | 377 | 3850 | 12 | ||||||||
| Y10WZ-300/727 | 330 | 300 | 228 | 425 | 10 | 727 | 814 | 618 | 298 | 5100 | 11 |
| YH10WZ-300/727 | 377 | 3850 | 12 | ||||||||
| Y10WZ-306/742 | 330 | 306 | 233 | 433 | 10 | 742 | 831 | 630 | 298 | 5100 | 11 |
| YH10WZ-306/742 | 377 | 3850 | 12 | ||||||||
| Y10WZ-312/760 | 330 | 312 | 237 | 442 | 10 | 760 | 847 | 643 | 298 | 5100 | 11 |
| YH10WZ-312/760 | 377 | 3850 | 12 | ||||||||
| Y10WZ-324/789 | 330 | 324 | 246 | 459 | 10 | 789 | 880 | 668 | 298 | 5100 | 11 |
| YH10WZ-324/789 | 377 | 3850 | 12 | ||||||||
| Y20WZ-420/1046 | 500 | 420 | 318 | 565 | 20 | 1046 | 1170 | 858 | 418 | 6240 | 11 |
| YH20WZ-420/1046 | 377 | 5850 | 12 | ||||||||
| Y20WZ-444/1106 | 500 | 444 | 324 | 597 | 20 | 1106 | 1238 | 957 | 418 | 6240 | 11 |
| YH20WZ-444/1106 | 377 | 5850 | 12 | ||||||||
| Y20WZ-468/1166 | 500 | 468 | 330 | 630 | 20 | 1166 | 1306 | 630 | 418 | 6240 | 11 |
| YH20WZ-468/1166 | 377 | 5850 | 12 | ||||||||
Gapless MOA for shunt compensating capacitor
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| YH5WR-5/13.5 | 3 | 5 | 4.0 | 7.2 | 5 | 13.5 | 10.5 | 88 | 200 | 1 |
| YH5WR-10/27 | 6 | 10 | 8.0 | 14.4 | 5 | 27.0 | 21.0 | 88 | 200 | 1 |
| YH5WR-12/32.4 | 10 | 12 | 9.6 | 17.4 | 5 | 32.4 | 25.2 | 88 | 255 | 1 |
| YH5WR-15/40.5 | 10 | 15 | 12.0 | 21.8 | 5 | 40.5 | 31.5 | 88 | 255 | 1 |
| YH5WR-17/46 | 10 | 17 | 13.6 | 24.0 | 5 | 46.0 | 35.0 | 88 | 255 | 1 |
| Y5WR-26/66 | 20 | 26 | 20.8 | 37.0 | 5 | 66.0 | 53.0 | 232 | 995 | 5 |
| YH5WR-26/66 | 120 | 345 | 4 | |||||||
| Y5WR-32/85 | 20 | 32 | 25.6 | 47.0 | 5 | 85.0 | 68.0 | 232 | 995 | 5 |
| YH5WR-32/85 | 120 | 405 | 4 | |||||||
| Y5WR-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 105.0 | 232 | 995 | 5 |
| YH5WR-51/134 | 120 | 525 | 4 | |||||||
| Y5WR-84/221 | 66 | 84 | 67.2 | 121 | 5 | 221 | 176 | 252 | 1200 | 6 |
| YH5WR-84/221 | 195 | 1296 | 8 | |||||||
| Y5WR-90/236 | 66 | 90 | 72.5 | 130 | 5 | 236 | 190 | 252 | 1200 | 6 |
| YH5WR-90/236 | 195 | 1296 | 8 | |||||||
| Y10WR-105/265 | 66 | 105 | 84 | 152 | 10 | 265 | 225 | 252 | 1200 | 6 |
| YH10WR-105/265 | 195 | 1296 | 8 | |||||||
| Y10WR-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 239 | 270 | 1620 | 7 |
| YH10WR-108/28 | 195 | 1296 | 8 | |||||||
| Y10WR-174/372 | 110 | 174 | 139 | 240 | 10 | 372 | 336 | 351 | 2135 | 25 |
| YH10WR-174/372 | 377 | 2200 | 26 | |||||||
Arrester for low voltage system
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Residual voltage at Lightning current impulse kV.peak | Parachute diameter Φ mm | Height H mm | Fig. No |
| kV.rms | |||||||||
| YH1.5W-0.28/1.3 | 0.22 | 0.28 | 0.24 | 0.6 | 1.5 | 1.3 | 35 | 85 | 2 |
| YH1.5W-0.5/2.6 | 0.38 | 0.5 | 0.42 | 1.2 | 1.5 | 2.6 | 35 | 85 | 2 |
Gapless MOA for motor and generators
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH2.5WD-4/9.5 | 3.15 | 4 | 3.2 | 5.7 | 2.5 | 9.5 | 10.7 | 7.6 | 88 | 200 | 1 |
| YH2.5WD-8/18.7 | 6.3 | 8 | 6.3 | 11.2 | 2.5 | 18.7 | 21.0 | 15.0 | 88 | 200 | 1 |
| YH2.5WD-13.5/31 | 10.5 | 13.5 | 10.5 | 18.6 | 2.5 | 31.0 | 34.7 | 25.0 | 88 | 255 | 1 |
| YH5WD-4/9.5 | 3.15 | 4 | 3.2 | 5.7 | 5 | 9.5 | 10.7 | 7.6 | 88 | 200 | 1 |
| YH5WD-8/18.7 | 6.3 | 8 | 6.3 | 11.2 | 5 | 18.7 | 21.0 | 15.0 | 88 | 200 | 1 |
| YH5WD-13.5/31 | 10.5 | 13.5 | 10.5 | 18.6 | 5 | 31.0 | 34.7 | 25.0 | 88 | 255 | 1 |
| YH5WD-17.5/40 | 13.8 | 17.5 | 13.8 | 24.4 | 5 | 40.0 | 44.8 | 32.0 | 88 | 255 | 1 |
| YH5WD-20/45 | 15.75 | 20 | 15.8 | 28.0 | 5 | 45.0 | 50.4 | 36.0 | 88 | 255 | 1 |
| YH5WD-23/51 | 18.0 | 23 | 18.0 | 31.9 | 5 | 51.0 | 57.2 | 40.8 | 88 | 310 | 1 |
| YH5WD-25/56.2 | 20.0 | 25 | 20.0 | 35.4 | 5 | 56.2 | 62.9 | 45.0 | 88 | 310 | 1 |
※Note:The arrester which nominal discharge current is 2.5kA used for protection of Motor.
The arrester which nominal discharge current is 5kA used for protection of Generators.
The arrester which nominal discharge current is 5kA used for protection of Generators.
Gapless MOA with Polymer-housed for transmission lines
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5WX-34/90 | 20 | 34 | 27.2 | 50.0 | 5 | 90.0 | 104.0 | 80.0 | 114 | 475 | 13 |
| YH5WX-51/134 | 35 | 51 | 40.8 | 73.0 | 5 | 134.0 | 154.0 | 114.0 | 114 | 595 | 13 |
| YH⁵WX-54/L49 | 35 | 54.0 | 43.2 | 77.0 | 5 | 142.0 | 163.0 | 121.0 | 114 | 595 | 13 |
| YH5WX-54/150 | 35 | 54.0 | 43.2 | 80.0 | 5 | 150.0 | 169.0 | 128.0 | 114 | 595 | 13 |
| YH5WX-96/250 | 66 | 96 | 75 | 140 | 5 | 250 | 288 | 213 | 195 | 1355 | 14 |
| YH5WX-96/275 | 66 | 96 | 75 | 154 | 5 | 275 | 316 | 234 | 195 | 1355 | 14 |
| YH5WX-108/281 | 110 | 108 | 84 | 157 | 5 | 281 | 323 | 239 | 195 | 1355 | 14 |
| YH5WX-108/300 | 110 | 108 | 84 | 173 | 5 | 309 | 348 | 263 | 195 | 1355 | 14 |
| YH1OWX-108/281 | 110 | 108 | 84 | 157 | 10 | 281 | 315 | 239 | 195 | 1355 | 14 |
| YH10WX-108/309 | 110 | 108 | 84 | 173 | 10 | 309 | 348 | 263 | 195 | 1355 | 14 |
| YH10WX-216/562 | 220 | 216 | 168 | 314 | 10 | 562 | 630 | 478 | 195 | 2685 | 15 |
| YH10WX-216/618 | 220 | 216 | 168.5 | 346 | 10 | 618 | 693 | 526 | 195 | 2685 | 15 |
| YH10WX-312/760 | 330 | 312 | 237 | 442 | 10 | 760 | 847 | 643 | 216 | 3530 | 16 |
| YH10WX-324/789 | 330 | 324 | 246 | 459 | 10 | 789 | 880 | 668 | 216 | 3530 | 16 |
| YH20WX-468/1166 | 500 | 468 | 330 | 630 | 20 | 1166 | 1306 | 630 | 377 | 5850 | 12 |
Gapless MOA for electrical railway
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| Y5WT-42/105 | 27.5 | 42 | 31.5 | 58.0 | 5 | 105.0 | 118.0 | 89.0 | 232 | 995 | 5 |
| YH5WT-42/105 | 128 | 525 | 4 | ||||||||
| Y5WT-42/110 | 27.5 | 42 | 31.5 | 60.0 | 5 | 110.0 | 127.0 | 94.0 | 232 | 995 | 5 |
| YH5WT-42/110 | 128 | 525 | 4 | ||||||||
| Y5WT-42/120 | 27.5 | 42 | 34.0 | 65.0 | 5 | 120.0 | 138.0 | 98.0 | 232 | 995 | 5 |
| YH5WT-42/120 | 128 | 525 | 4 | ||||||||
| Y5WT-84/240 | 55 | 84 | 68 | 130 | 5 | 240 | 276 | 196 | 252 | 1200 | 6 |
| YH5WT-84/240 | 195 | 1296 | 8 | ||||||||
| Y5WT-100/260 | 110 | 100 | 73 | 145 | 5 | 260 | 291 | 221 | 270 | 1620 | 7 |
| YH5WT-100/260 | 195 | 1296 | 8 | ||||||||
| Y5WT-100/275 | 110 | 100 | 73 | 150 | 5 | 275 | 316 | 234 | 270 | 1620 | 7 |
| YH5WT-100/275 | 195 | 1296 | 8 | ||||||||
| Y10WT-100/290 | 110 | 100 | 73 | 158 | 10 | 290 | 325 | 247 | 270 | 1620 | 7 |
| YH10WT-100/290 | 195 | 1296 | 8 | ||||||||
| Y10WT-100/295 | 110 | 100 | 73 | 160 | 10 | 295 | 330 | 251 | 270 | 1620 | 7 |
| YH10WT-100/295 | 195 | 1296 | 8 | ||||||||
Gapless MOA for electrical machinery neutral point
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| YH1.5W-2.4/6 | 3.15 | 2.4 | 1.9 | 3.4 | 1.5 | 6.0 | 5.0 | 88 | 200 | 1 |
| YH1.5W-4.8/12 | 6.3 | 4.8 | 3.8 | 6.8 | 1.5 | 12.0 | 10.0 | 88 | 200 | 1 |
| YH1.5W-8/19 | 10.5 | 8 | 6.4 | 11.4 | 1.5 | 19.0 | 15.9 | 88 | 200 | 1 |
| YH1.5W-10.5/23 | 13.8 | 10.5 | 8.4 | 14.9 | 1.5 | 23.0 | 19.2 | 88 | 200 | 1 |
| YH1.5W-12/26 | 15.75 | 12 | 9.6 | 17.0 | 1.5 | 26.0 | 21.6 | 88 | 200 | 1 |
| YH1.5W-13.7/29.2 | 18.0 | 13.7 | 11.0 | 19.5 | 1.5 | 29.2 | 24.3 | 88 | 255 | 1 |
| YH1.5W-15.2/31.7 | 20.0 | 15.2 | 12.2 | 21.6 | 1.5 | 31.7 | 26.4 | 88 | 255 | 1 |
MOA with parallel gaps for electrical machinery
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Residual voltage at Nominal discharge current kV.peak ≯ | Parachute diameter Φ mm | Height H mm | Fig. No |
| kV.rms | |||||||||
| YH0.5B-8/11 | 6.3 | 8 | 6.3 | 11.5 | 0.5 | 11.0 | 88 | 255 | 1 |
| YH0.5B-13.5/20 | 10.5 | 13.5 | 10.5 | 21.0 | 0.5 | 20.0 | 88 | 255 | 1 |
Gapless MOA for transformer neutral point
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Continuous operation voltage | Reference voltage at D.C.1mA k V . D C ≮ | Nominal discharge current kA .peak | Lightning impulse | Switching impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | ||||||||||
| kV.rms | ||||||||||
| Y1.5W-30/98 | 35 | 30 | 24.0 | 61.0 | 1.5 | 98.0 | 88.0 | 232 | 995 | 5 |
| YH1.5W-30/98 | 120 | 525 | 4 | |||||||
| Y1.5W-60/144 | 110 | 60 | 48 | 85 | 1.5 | 144 | 135 | 232 | 1145 | 5 |
| YH1.5W-60/144 | 142 | 585 | 4 | |||||||
| Y1.5W-72/186 | 110 | 72 | 58 | 103 | 1.5 | 186 | 174 | 110 | 215 | 5 |
| YH1.5W-72/186 | 142 | 585 | 4 | |||||||
| Y1.5W-96/260 | 500 | 96 | 77 | 137 | 1.5 | 260 | 243 | 270 | 1620 | 7 |
| YH1.5W-96/260 | 195 | 1296 | 8 | |||||||
| Y1.5W-144/320 | 220 | 144 | 116 | 205 | 1.5 | 320 | 299 | 270 | 1620 | 7 |
| YH1.5W-144/320 | 195 | 1296 | 8 | |||||||
| Y1.5W-210/440 | 330 | 210 | 168 | 285 | 1.5 | 440 | 410 | 278 | 2880 | 9 |
| YH1.5W-210/440 | 216 | 2635 | 10 | |||||||
MOA with series gap
| Technical parameters Product type |
Rated voltage of electrical machinery | Rated voltage | Continuous operation voltage | Power frequency discharge voltage kV.rms ≮ | Discharge voltage at impulse 1.2/50μS kV.peak ≯ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5CS-3.8/15 | 3 | 3.8 | 3.0 | 9.0 | 21.0 | 5 | 15.0 | 17.2 | 82 | 200 | 1 |
| YH5CS-7.6/27 | 6 | 7.6 | 6.1 | 16.0 | 35.0 | 5 | 27.0 | 31.0 | 82 | 200 | 1 |
| YH5CS-12.7/45 | 10 | 12.7 | 10.2 | 26.0 | 50.0 | 5 | 45.0 | 51.8 | 82 | 255 | 1 |
| YH5CZ-3.8/12 | 3 | 3.8 | 3.0 | 9.0 | 20.0 | 5 | 12.0 | 13.8 | 82 | 200 | 1 |
| YH5CZ-7.6/24 | 6 | 7.6 | 6.1 | 16.0 | 30.0 | 5 | 24.0 | 27.6 | 82 | 200 | 1 |
| YH5CZ-12.7/41 | 10 | 12.7 | 12.7 | 26.0 | 45.0 | 5 | 41.0 | 47.2 | 82 | 255 | 1 |
| YH5CZ-42/124 | 35 | 42 | 33.6 | 80.0 | 134.0 | 5 | 124.0 | 142.6 | 114 | 585 | 4 |
| YH2.5CD-3.8/9.5 | 3.15 | 3.8 | 3.0 | 7.5 | 9.5 | 2.5 | 9.5 | 10.7 | 88 | 200 | 1 |
| YH2.5CD-7.6/18.7 | 6.3 | 7.6 | 6.1 | 15.0 | 18.7 | 2.5 | 18.7 | 21.0 | 88 | 200 | 1 |
| YH2.5CD-12.7/3 | 10.5 | 12.7 | 10.2 | 25.0 | 31.0 | 2.5 | 31.0 | 34.7 | 88 | 255 | 1 |
| YH5CD-3.8/9.5 | 3.15 | 3.8 | 3.0 | 7.5 | 9.5 | 5 | 9.5 | 10.7 | 88 | 200 | 1 |
| YH5CD-7.6/18.7 | 6.3 | 7.6 | 6.1 | 15.0 | 18.7 | 5 | 18.7 | 21.0 | 88 | 200 | 1 |
| YH5CD-12.7/31 | 10.5 | 12.7 | 10.2 | 25.0 | 31.0 | 5 | 31.0 | 34.7 | 88 | 255 | 1 |
※Note:The arrester which nominal discharge current is 2.5kA used for protection of Motor.
The arrester which nominal discharge current is 5kA used for protection of Generators.
The arrester which nominal discharge current is 5kA used for protection of Generators.
Polymer-housed MOA with gaps for transmission lines
| Technical parameters Product type |
Nominal voltage of system | Rated voltage | Reference voltage at D.C.1mA of units k V . D C ≮ | Power frequency withstand voltage kV.rms ≯ | 50% Lightning impulse sparkover voltage kV.peak ≯ | Nominal discharge current kA .peak | Lightning impulse | Steeping impulse | Parachute diameter Φ mm | Height H mm | Fig. No |
| Residual voltage kV.peak ≯ | |||||||||||
| kV.rms | |||||||||||
| YH5CX-13/40 | 10 | 13 | 20.0 | 26 | 100 | 5 | 40.0 | 46.0 | 76 | 185 | 17 |
| YH5CX-42/120 | 35 | 42 | 60.0 | 70 | 240 | 5 | 120.0 | 138.0 | 120 | 545 | 18 |
| 120 | 960 | 19 | |||||||||
| YH5CX-75/218 | 66 | 75 | 108 | 117 | 400 | 5 | 218 | 246 | 195 | 910 | 20 |
| 195 | 1600 | 21 | |||||||||
| YH5CX-90/260 | 110 | 90 | 130 | 170 | 525 | 5 | 260 | 292 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-90/260 | 110 | 90 | 130 | 170 | 525 | 10 | 260 | 292 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-96/280 | 110 | 96 | 140 | 170 | 525 | 10 | 280 | 314 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-102/296 | 110 | 102 | 148 | 170 | 525 | 10 | 296 | 332 | 195 | 975 | 20 |
| 195 | 2035 | 21 | |||||||||
| YH10CX-180/520 | 220 | 180 | 260 | 340 | 900 | 10 | 520 | 584 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-192/560 | 220 | 192 | 280 | 340 | 900 | 10 | 560 | 628 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-204/592 | 220 | 204 | 296 | 340 | 900 | 10 | 592 | 664 | 195 | 1655 | 20 |
| 195 | 3450 | 21 | |||||||||
| YH10CX-288/775 | 330 | 288 | 408a | 460 | 1300 | 10 | 775 | 868 | 195 | 2450 | 22 |
| YH20CX-396/1050 | 500 | 396 | 561 | 510 | 1760 | 20 | 1050 | 1171 | 216 | 3600 | 23 |
※Note: Reference voltage at D.C. 2mA.
The structure and installation dimensional drawing
Frequently Asked Questions
What are the main advantages of a polymer-housed metal-oxide surge arrester (MOA)?
It combines the benefits of organic insulation materials and traditional porcelain-clad MOA techniques. Key advantages include excellent insulation, high dielectric strength, anti-leaking, anti-electric corrosion, heat/cold resistance, anti-aging, explosion-proof properties, hydrophobic performance, and superior sealing.
What ambient temperature range is suitable for normal operation?
The normal service conditions require the ambient air temperature to remain within the range of -40℃ to +40℃.
What is the maximum altitude limit for these surge arresters under normal conditions?
Under normal service conditions, the altitude should not exceed 2600 meters. For exceptionally higher altitudes or special movement conditions, requirements must be indicated in the contract.
How do I choose between a 2.5kA and a 5kA nominal discharge current arrester?
According to the technical standards, arresters with a nominal discharge current of 2.5kA are specifically designed for the protection of motors, while arresters with a nominal discharge current of 5kA are used for the protection of generators.
Which design standards are followed during manufacturing?
The polymer-housed metal-oxide surge arresters are designed and manufactured in strict compliance with international IEC and national GB standards, ensuring competitive performance in the global market.
What is the maximum wind velocity and earthquake intensity these arresters can withstand?
They are designed to withstand a maximal wind velocity of up to 35 m/s and are suitable for installation in regions with an earthquake intensity of 8 degrees and below.