China MNS Low Voltage Switchgear Suppliers - Reliable Factory Solutions for Power Distribution Systems
Advantages
Standardized and modular design for the entire series.
The switchgear can be designed with different protection levels according to the working and environmental requirements.
Different types of functional components can be freely installed in the same switchgear, such as fixed components and withdrawable components.
Compact structure that saves space inside the switchgear.
The distribution circuit layout is economical and the installation density is high.
The switchgear can be arranged back-to-back.
Equipment updates and improvements are convenient.
The equipment has high reliability and continuity in operation.
Fully guarantee the personal safety of operators.
Standards
- doc IEC61439-2 "Low voltage switchgear and control equipment"
- doc GBIT7251.12 "Low Voltage Switchgear and Control Equipment"
- doc GBIT24274 "Low voltage withdrawable switchgear and control equipment"
Type and meaning
Service conditions
MNS switchgear is a complete electrical equipment installed indoors. When the protection level reaches IP54, it can operate under other working conditions.
The upper limit of ambient temperature is 40 ℃, and the average temperature within 24 hours shall not higher than 35 ℃; The lower limit of ambient temperature is -5 ℃. When the equipment is used under conditions higher than the above ambient temperature, it should be operated at reduced capacity.
The air is clean, and the relative humidity should not exceed 50% at 40 ℃. Higher relative humidity is allowed at lower temperatures (e.g. 90% at 20 ℃). In cases where condensation may occur, ventilation or heating measures can be used in the switchgear to prevent condensation.
The altitude of the location where the switchgear is used shall not exceed 2000m. If the switchgear is installed in an area above an altitude of 2000m, the equipment should be correspondingly reduced in capacity for operation.
Main technical parameters
| Electrical parameters | Rated voltage | Rated insulation voltage Ui | AC 690V / 1000V | |
| Rated working voltage Ue | AC 400V / 690V | |||
| Rated impulse withstand voltage Uimp | 8kV / 12kV | |||
| 1-minute power frequency withstand voltage | 2.5kV / 3.5kV | |||
| Rated current | Main busbar | Rated current le | To 6300A | |
| Rated peak withstand current lpk | To 220kA | |||
| Rated short-time withstand current lcw | To 100kA | |||
| Vertical busbar1 | Rated current le | To 1250A | ||
| Rated peak withstand current lpk | To 143kA | |||
| Rated short-time withstand current lcw | To 65kA | |||
| Rated frequency | 50Hz / 60Hz | |||
| Structural features | Dimensions | Height (mm) | 2200 | |
| Width (mm) | 400, 600, 800, 1000, 1200 | |||
| Depth(mm) | 600, 800, 1000, 1200 | |||
| Modulus | E=25mm | |||
| Internal separation form | To 4b | |||
| Protection level | IP30, IP40, IP42, IP54 | |||