China VS1 (VTD12-24kV Indoor High Voltage AC Vacuum Circuit Breaker Suppliers & Factory

The VS1 (VTDSeries Indoor High Voltage AC Vacuum Circuit Breaker is designed for switchgears with a rated voltage range of 12 to 24 kV. This advanced circuit breaker is ideal for protecting and controlling electrical equipment in various sectors, including industrial facilities, mining enterprises, power plants, and substations. With its unique advantages, our vacuum circuit breaker is particularly suited for applications that demand frequent operations at rated current or multiple short-circuit currents, Manufactured in China by leading suppliers, our circuit breaker features an integrated design that combines the operating mechanism and circuit breaker into a cohesive unit. This innovative design ensures reliable interlocking functions within a front and rear sub-assembly structure. The VS1 (VTDcan be utilized as either a fixed installation unit or a handcart unit equipped with a chassis, making it a versatile choice for any electrical infrastructure needs. Choose our factory for high-quality, dependable circuit breakers that meet your operational requirements

    General

    VS1 (VTD6) series Indoor high voltage AC vacuum circuit breaker is applicable to switchgears with rated voltage of 12~24kV. It's used for protecting and controlling the electrical equipment in the fields of industry & mining enterprise, power plants and substation. Due to the special advantages of vacuum circuit breakers, it is especially suitable for applications requiring frequent operations at rated current or multiple short-circuit currents.

    The circuit breaker adopts the integrated design of operating mechanism and circuit breaker. They form a front and rear sub assembly structure with reliable interlocking function. It can be used as a fixed installation unit or a handcart unit with a chassis.

    Standards

    Product quality assurance is based on the continuous improvement of product research, development, design and production processes that meet the requirements of all aspects of the quality system. The basic parameters and technical indicators of the product meet the following standards.

    • GB/T1984 - High voltage AC circuit breaker
    • DL/T403 - High voltage AC circuit breaker
    • IEC60694 - Common specifications for high-voltage switchgear and controlgear standards
    • IEC62271-100 - High-voltage switchgear and controlgear-Part 100: Alternating current circuit breakers

    Service Conditions

    • Ambient temperature: - 15 ℃ ~ + 40 ℃
    • Altitude: ≤ 1000M
    • Relative humidity:
      • Daily average relative humidity ≤ 95%
      • Daily average vapor pressure ≤ 2.2x10-3MPa
      • Monthly average relative humidity ≤ 90%
      • Monthly average vapor pressure ≤ 1.8x10-3MPa
    • Earthquake resistant level: < grade 8
    • Site condition: no dripping, no flammable and explosive hazards, no chemical corrosive gas and no violent vibration
    ※Note: If the service environment exceeds the above conditions, please consult with the manufacturer.

    Type and Designation

    Type and Designation Diagram

    Technical Data

    ◆Technical parameters of circuit breaker

    Item Unit Parameters
    Rated voltage kV 12 24
    Rated frequency Hz 50/60
    1min Rated power frequency short-time withstand voltage (phase to phase, to earth / isolation distance) kV 42 65
    Rated Lightning impulse withstand voltage (peak) (phase to phase, to earth / isolation distance) kV 75 125
    Rated operation sequence   O-t-CO-t'-CO
    Item Unit Parameters
    Rated current A 630 1250 1250 1600 2000 2500 1250 1600 2000 2500 3150 3150 4000
    Rated short-time breaking current kA 20/25 31.5 40 50
    Rated short-circuit making current (peak) kA 50/63 80 100 125
    Rated short-circuit duration S 4 4 4 4
    Mechanical life Times 20000 20000 20000 10000
    Note:
    20kA   25kA   31.5kA   t=0.3s   t’=180s
    40kA   50kA   t=180s   t’=180s
    4000A requires forced air cooling
    ※ If the mechanical life requirement is higher than the standard configuration, consult with the manufacturer.

    ◆Mechanical characteristic parameters of circuit breaker

    Item Unit Parameters
    12KV 24KV
    Distance of contact mm 9 ± 1 13 ± 1
    Over-travel mm 3.5 ± 0.5
    Three-phase C/O asynchrony ms ≤2
    Closing contact bounce time ms ≤2 / ≤3(50kA)
    Contact pressure of closing contact N 20kA 25kA 31.5kA 40kA 50kA
    2000 ± 200 2400 ± 200 3100 ± 200 4250 ± 200 5500 ± 200
    Average opening speed m/s 0.9~1.31 1.1~1.6
    Average closing speed m/s 0.4~0.8 0.6~1.0

    ◆Opening and closing time

    Closing time: 30~70ms Opening time: 15~45ms

    ◆Technical parameters of coil and locking electromagnet

    Name of equipment Power (W) Rated voltage (V)
    Opening coil 368 220/110
    Closing coil 368
    Locking electromagnet 4.8
    Overcurrent controller Y7 (Y8, Y9)

    ◆Technical parameters of energy charging motor

    Rated voltage (V) Power (W) Charging time (s) Applicable current class
    220/110 70 ≤15 20kA、25kA、31.5kA、40kA
    220/110 90 ≤15 50kA

    Outline Dimension Drawing

    A) Fixed type - 12kV

    Outline dimension drawing 1
    Outline dimension drawing of VS1 (VTD6)-12 fixed type circuit breaker
    (Distance between phases is 150mm)
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5 31.5, 40
    Distance between phases (mm) 150 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing 2
    Outline dimension drawing of VS1 (VTD6)-12 fixed type circuit breaker
    (Distance between phases is 210mm)

    Note: The dimension in brackets refers to the dimension from the outgoing terminal of the composite insulated pole to the center of the pole.

    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5 31.5, 40
    Distance between phases (mm) 210 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing 3
    Outline dimension drawing of VS1 (VTD6)-12 fixed type circuit breaker
    (Distance between phases is 275mm)
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5 31.5, 40
    Distance between phases (mm) 210 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)

    B) Withdrawable type - 12kV (trolley travel distance is 200m)

    Withdrawable Outline 1
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker
    (For cabinet width 550mm)
    Rated current (A) 630 1250
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5
    Dimension of static contact (mm) Φ35 Φ49
    Distance between phases (mm) 150 ± 1.5
    Withdrawable Outline 2
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker
    (For cabinet width 650mm)
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 150 ± 1.5
    Withdrawable Outline 3
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker
    (For cabinet width 880mm)
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 210 ± 1.5
    Withdrawable Outline 4
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker
    (For cabinet width 1000mm)
    Rated current (A) 1600 2000 2500 3150 4000
    Rated short circuit breaking current (A) 31.5, 40 31.5, 40 40, 50
    Dimension of static contact (mm) Φ79 Φ109
    Distance between phases (mm) 275 ± 1.5

    C) Fixed type - 24kV

    Fixed 24kV Outline 1
    Outline dimension drawing of VS1 (VTD6)-24 fixed type circuit breaker
    (Distance between phases is 275mm)
    Note:
    1. The outgoing conductive surface of 1600A fixed & sealed pole and transition conductive block of the connecting busbar shall be provided by customer.
    2. The dimension in brackets refers to the dimension from the outgoing terminal of the composite insulated pole to the center of the pole.
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40
    Distance between phases (mm) 275 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Fixed 24kV Outline 2
    Outline dimension drawing of VS1 (VTD6)-24 fixed type circuit breaker
    (Distance between phases is 275mm)
    Rated current (A) 1600 2000 2500 3150
    Rated short circuit breaking current (A) 31.5, 40
    Distance between phases (mm) 275 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)

    D) Withdrawable type - 12kV (trolley travel distance is 300m)

    Withdrawable 24kV Outline 1
    Outline dimension drawing of VS1 (VTD6)-24 withdrawable type circuit breaker
    (For cabinet width 1000mm)
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 275 ± 1.5
    Withdrawable 24kV Outline 2
    Outline dimension drawing of VS1 (VTD6)-24 withdrawable type circuit breaker
    (For cabinet width 1000mm)
    Rated current (A) 1600 1600 2000 2500 3150
    Rated short circuit breaking current (A) 31.5, 40 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ55 Φ79 Φ109
    Distance between phases (mm) 275 ± 1.5

    Frequently Asked Questions (FAQ)

    What applications is the VS1 (VTD6) series vacuum circuit breaker suitable for?
    It is designed for protecting and controlling electrical equipment in industries, mining enterprises, power plants, and substations with rated voltages of 12~24kV. It is especially suitable for environments requiring frequent operations at rated current or multiple short-circuit currents.
    Which standards do the VS1 (VTD6) series comply with?
    The technical indicators of the product meet GB/T1984, DL/T403, IEC60694, and IEC62271-100 standards.
    What are the environmental limits for normal service conditions?
    The standard service conditions require an ambient temperature of -15℃ to +40℃, altitude ≤ 1000m, daily average relative humidity ≤ 95%, monthly average relative humidity ≤ 90%, earthquake-resistant level under grade 8, and a site free from dripping, flammable/explosive hazards, chemical corrosive gases, and violent vibration.
    What is the mechanical life of this vacuum circuit breaker?
    The mechanical life is 20,000 operations for standard current classes (up to 40kA) and 10,000 operations for the 50kA current class. If you require a higher mechanical life, please consult with the manufacturer.
    Does the 4000A current rated circuit breaker require extra cooling?
    Yes, the 4000A rated current configuration requires forced air cooling as specified in the technical parameters.
    What are the typical opening and closing times?
    The closing time is between 30ms and 70ms, and the opening time ranges from 15ms to 45ms.