China VT19-12/24 Indoor High Voltage Vacuum Circuit Breaker Suppliers & Factory for 12kV and 24kV Systems

The VT19-12/24 indoor AC high voltage vacuum circuit breaker is an essential switching device designed for 12kV and 24kV power systems. It plays a critical role in controlling and protecting electrical equipment across various industries, including mining enterprises, power plants, and substations. Manufactured in China, this reliable circuit breaker is favored by numerous suppliers for its unique benefits, making it especially suitable for applications that demand frequent operation at rated working current or multiple interruptions of short circuit currents. Partner with our factory to experience top-notch quality and performance in vacuum circuit breakers.

    General

    VT19-12/24 indoor AC high voltage vacuum circuit breaker is a switching device unsed for 12kV and 24kV power system, serving as the control and protection unit of electrical equipment in industrial & mining enterprises, power plants and substation. Due to the special advantages of vacuum circuit breaker, it is particularly suitable for applications that require frequent operation of the rated working current or multiple interruptions of short circuit currents.
    The circuit breaker features an integrated design of the operating mechanism and the breaker body, with a front-and-back split structure. It has reliable interlocking functions and can be used as a fixed installation unit or in combination with a trolley to form a withdrawable unit.

    Standards

    The circuit breaker complies with the following standards:
    IEC62271-100:2008 High-voltage switchgear and controlgear
    GB/T1984-2014 AC High-Voltage Circuit Breakers
    JB/T3855-2008 3.6~40.5KV Indoor AC High-Voltage Vacuum Circuit Breakers
    DLT403-2000 Technical Specifications for Ordering 10-40.5KV High-Voltage Vacuum Circuit Breakers

    Type designation

    Type designation description diagram
    Type Designation Diagram

    Service Conditions

    Normal condition
    Ambient temperature: +40℃~-15℃
    Relative humidity: Daily average relative humidity ≤ 95%
    Daily average vapor pressure ≤ 2.2x10-3MPa
    Monthly average relative humidity ≤ 90%
    Monthly average vapor pressure ≤ 1.8x10-3MPa
    Altitude ≤ 1000m (Suitable for VT19-14/24kV)
    Altitude ≤ 2000m (Suitable for VT19-40.5EP)
    Earthquake intensity: < grade 8
    Installation place: The site should have no water, explosion danger, serious pollution, chemical corrosion and exquisite shake.
    Special service condition
    If the customer deviates from the normal conditions, it can be consulted with the manufacturer.
    ※Note: If the service environment exceeds the above conditions, please consult with the manufacturer.

    Technical Parameters

    Technical parameters of circuit breaker
    Item Unit Parameters
    Rated voltage kV 12 24
    Rated frequency Hz 50/60
    1min Rated power frequency short-time withstand voltage (phase to phase, to earth / isolation distance) kV 75 125
    Rated Lightning impulse withstand voltage (peak) (phase to phase, to earth / isolation distance) kV 42 65
    Rated operation sequence   O-0.3s-CO-180s-CO
    Type Rated current (A) Rated short circuit breaking current (kA) Rated short circuit making current (peak kA) Rated duration of short circuit (s) Rated breaking times of short circuit (times) Mechanical life (times)
    VT19-12
    VT19-24
    630 20/25 50/63 4 50 30000
    1250
    1250 31.5 80 4 50 30000
    1600
    2000
    2500
    1250 40 100 4 30 30000
    1600
    2000
    2500
    3150
    VT19-12 3150 50 125 4 20 20000
    4000
    Note: 4000A need forced cold wind
    Mechanical characteristic parameters of circuit breaker
    S/N Parameter name Unit Data
    12kV 24kV
    1 Clearance between open contacts mm 9 ± 1 (11 ± 1 According to interrupter parameters) 13 ± 1
    2 Over-travel 3.5 ± 0.5
    3 Three phase opening and closing asynchronous ms ≤ 2
    4 Bounce time of closing contact ms ≤ 2 / ≤ 3(50kA)
    5 Contact pressure of closing contact N 20kA, 25kA, 31.5kA, 40kA, 50kA
    2000±200, 2400±200, 3100±200, 4250±200, 5500±200
    6 Average opening speed ms 0.9~1.3 1.1~1.6
    7 Average closing speed 0.4~0.8 0.6~1.0
    8 Each phase circuit resistance (Except contact arm) μΩ / /
    Opening and closing time
    Type Closing time (ms) Opening time (ms)
    12&24kV 30-70 15-45

    Outline dimension drawing

    VT19-12kV
    A) Fixed type
    Outline dimension drawing A
    Outline dimension drawing reference
    Note: The dimension indicated in the parentheses is the fitting dimension of the composite insulated pole.
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5 31.5, 40
    Distance between phases (mm) 150 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing of VS1 (VTD6)-12 fixed type circuit breaker (Distance between phases is 150mm)
    Outline Drawing Phase spacing 150mm - Front
    Outline Drawing (150mm phase spacing) - Front View
    Outline Drawing Phase spacing 150mm - Side
    Outline Drawing (150mm phase spacing) - Side View
    Note: The dimension in brackets refers to the dimension from the outgoing terminal of the composite insulated pole to the center of the pole.
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5 31.5, 40
    Distance between phases (mm) 210 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing of VS1 (VTD6)-12 fixed type circuit breaker (Distance between phases is 210mm)
    Outline Drawing Phase spacing 210mm - Front
    Outline Drawing (210mm phase spacing) - Front View
    Outline Drawing Phase spacing 210mm - Side
    Outline Drawing (210mm phase spacing) - Side View
    Rated current (A) 1600 2000 2500 3150 4000
    Rated short-circuit breaking current (kA) 31.5, 40 40, 50
    Distance between phases (mm) 275 ± 1.5
    Mechanism top interlock L1 (mm) 30, 50 (Interlock can be extended from left side or right side, length can be customized according to customer requirements)
    Mechanism main shaft interlock L2 (mm) 30, 50 (Main shaft has left output or right output, length can be customized according to customer requirements)
    Figure 3 Fixed Type VT19-12 (Phase spacing of 275mm) Circuit Breaker Outline Dimension Diagram
    B) Handcart type (Travel distance 200mm)
    Handcart Type VT19-12 - 1
    Handcart Type VT19-12 Dimension Drawing 1
    Handcart Type VT19-12 - 2
    Handcart Type VT19-12 Dimension Drawing 2
    Handcart Type VT19-12 - 3
    Handcart Type VT19-12 Dimension Drawing 3
    Rated current (A) 630 1250
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5
    Dimension of static contact (mm) Φ35 Φ49
    Distance between phases (mm) 150 ± 1.5
    Figure 4 Handcart Type VT19-12 Circuit Breaker Outline Dimension Diagram (configured in medium-mounted cabinet with a width of 550mm)
    Handcart Type VT19-12 650mm - 1
    Withdrawable Type Outline Drawing 1
    Handcart Type VT19-12 650mm - 2
    Withdrawable Type Outline Drawing 2
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 150 ± 1.5
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker (For cabinet width 650mm)
    Handcart Type VT19-12 880mm - 1
    Withdrawable Type Outline Drawing 1
    Handcart Type VT19-12 880mm - 2
    Withdrawable Type Outline Drawing 2
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 210 ± 1.5
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker (For cabinet width 880mm)
    Handcart Type VT19-12 1000mm - 1
    Withdrawable Type Outline Drawing 1
    Handcart Type VT19-12 1000mm - 2
    Withdrawable Type Outline Drawing 2
    Rated current (A) 1600 2000 2500 3150 4000
    Rated short circuit breaking current (A) 31.5, 40 31.5, 40 40, 50
    Dimension of static contact (mm) Φ79 Φ109
    Distance between phases (mm) 275 ± 1.5
    Outline dimension drawing of VS1 (VTD6)-12 withdrawable type circuit breaker (For cabinet width 1000mm)
    C) Fixed type - 24kV
    Fixed Type 24kV - 1
    Fixed Type 24kV Dimension Drawing 1
    Fixed Type 24kV - 2
    Fixed Type 24kV Dimension Drawing 2
    Note:
    1. The outgoing conductive surface of 1600A fixed & sealed pole and transition conductive block of the connecting busbar shall be provided by customer.
    2. The dimension in brackets refers to the dimension from the outgoing terminal of the composite insulated pole to the center of the pole.
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40
    Distance between phases (mm) 275 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing of VS1 (VTD6)-24 fixed type circuit breaker (Distance between phases is 275mm)
    Fixed Type 24kV 275mm spacing - 1
    Fixed Type 24kV (275mm spacing) Drawing 1
    Fixed Type 24kV 275mm spacing - 2
    Fixed Type 24kV (275mm spacing) Drawing 2
    Rated current (A) 1600 2000 2500 3150
    Rated short circuit breaking current (A) 31.5, 40
    Distance between phases (mm) 275 ± 1.5
    Top interlock L1 of mechanism 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Spindle interlock L2 (mm) 30, 50 (Interlock extended from left or right, and the length can be made as per the requirements of clients)
    Outline dimension drawing of VS1 (VTD6)-24 fixed type circuit breaker (Distance between phases is 275mm)
    D) Withdrawable type - 12kV (trolley travel distance is 300m)
    Withdrawable Type 12kV - 1
    Withdrawable Type Outline Drawing 1
    Withdrawable Type 12kV - 2
    Withdrawable Type Outline Drawing 2
    Rated current (A) 630 1250 1600
    Rated short circuit breaking current (A) 20, 25, 31.5 25, 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ35 Φ49 Φ55
    Distance between phases (mm) 275 ± 1.5
    Outline dimension drawing of VS1 (VTD6)-24 withdrawable type circuit breaker (For cabinet width 1000mm)
    Withdrawable Type 24kV - 1
    Withdrawable Type 24kV Outline Drawing 1
    Withdrawable Type 24kV - 2
    Withdrawable Type 24kV Outline Drawing 2
    Rated current (A) 1600 1600 2000 2500 3150
    Rated short circuit breaking current (A) 31.5, 40 31.5, 40 31.5, 40
    Dimension of static contact (mm) Φ55 Φ79 Φ109
    Distance between phases (mm) 275 ± 1.5
    Outline dimension drawing of VS1 (VTD6)-24 withdrawable type circuit breaker (For cabinet width 1000mm)

    Frequently Asked Questions (FAQ)

    Q1: What are the main applications for the VT19-12/24 indoor vacuum circuit breaker?
    A1: It is designed for 12kV and 24kV power systems, serving as control and protection units in industrial & mining enterprises, power plants, and substations. It is highly suitable for operations requiring frequent current switching or multiple short-circuit current interruptions.
    Q2: Which international standards does this vacuum circuit breaker comply with?
    A2: The VT19 circuit breaker complies with IEC62271-100:2008, GB/T1984-2014, JB/T3855-2008, and DLT403-2000 standards.
    Q3: What are the normal ambient temperature and humidity limits for operation?
    A3: The normal ambient temperature range is +40℃ to -15℃. The daily average relative humidity should be ≤ 95%, and the monthly average relative humidity should be ≤ 90%.
    Q4: Does the circuit breaker support both fixed and withdrawable installations?
    A4: Yes, it features an integrated design of the operating mechanism and the body. It can be used as a fixed installation unit or combined with a trolley/handcart to form a withdrawable unit.
    Q5: Is forced air cooling required for the high-current VT19-12 models?
    A5: Yes, the 4000A rated current configuration of the VT19-12 circuit breaker requires forced cold wind cooling.
    Q6: What is the mechanical life expectancy of the VT19-12/24 circuit breaker?
    A6: Most specifications have a mechanical life of 30,000 operations, while the VT19-12 model rated at 50kA breaking current has a mechanical life of 20,000 operations.