The VT19-40.5 type indoor high voltage vacuum circuit breaker is an essential component in indoor switchgear, specifically designed for three-phase 50Hz/60Hz, 35kV electric power systems. Manufactured in China, this circuit breaker serves as both a control and protective unit, making it ideal for use in the electric facilities of industrial and mining enterprises, power plants, and substations. Its unique advantages allow it to handle frequent operations requiring a rated working current, as well as effectively interrupting short-circuit currents multiple times. As a reliable product from leading suppliers and factories in China, the VT19-40.5 circuit breaker ensures optimal performance and safety in high voltage applications

    General

    VT19-40.5 type indoor high voltage vacuum circuit breaker is indoor switchgear, used in three phase 50Hz/60Hz, 35kV electric power system. It is a control and protective unit, applied in electric facilities of industrial and mining enterprises, power plants and substation. Because of its special superiority, it is particularly suitable for frequent operations that require a rated working current , or for place where short-circuit current are broken multiple times.

    Standards

    The break circuit meets the requirements of GB1984 "HV AC circuit breaker", JB3855"HV AC vacuum circuit breaker" and relevant IEC standards. It has reliable interlocking function, and can be used as both handcart unit and fixed unit.

    Type designation

    Type designation of VT19-40.5 Vacuum Circuit Breaker

    Service Conditions

    Normal condition
    • Ambient temperature: +40℃~-15℃
    • Relative humidity: Daily average relative humidity≤95%, Daily average vapour pressure ≤2.2x10-3 Mpa; Monthly average relative humidity≤90%, Monthly average vapour pressure ≤1.8x10-3 Mpa.
    • Altitude ≤ 2000m (Suitable for VT19-40.5EP)
    • Earthquake intensity: < grade 8
    • Installation: The using place should be no water drop, no inflammable and explosion hazard, no chemical enchant gas, and no strenuous vibration.
    Special service condition
    If the customer deviates from the normal conditions, it can be consulted with the manufacturer.

    Technical Parameters

    Technical parameters of circuit breaker
    S/N Parameter name Unit Data
    1 Rated voltage kV 40.5
    2 Rated frequency Hz 50/60
    3 Rated lighting impulse withstand voltage kV 185
    4 Rated 1 min power frequency withstand voltage kV 95
    5 Rated operation sequence - O-0.3s-CO-180s-CO
    Type Rated current (A) Rated short circuit breaking current (kA) Rated short circuit making current (peak kA) Rated duration of short circuit (s) Rated breaking times of short circuit (times) Mechanical life (times)
    VT19-40.5 630 20/25 50/63 4 30 10000
    1250
    1250 31.5 80 4 20 10000
    1600
    2000
    2500
    4000
    Mechanical characteristic parameters of circuit breaker
    S/N Parameter name Unit Data
    40.5kV
    1 Clearance between open contacts mm 18 ± 1
    2 Over-travel 4 ± 0.5
    3 Three phase opening and closing asynchronous ms ≤ 2
    4 Bounce time of closing contact ms ≤ 3
    5 Contact pressure of closing contact N 20kA, 25kA, 31.5kA
    2000±200, 2700±200, 3100±200
    6 Average opening speed m/s 1.8 ± 0.2
    7 Average closing speed 0.8 ± 0.2
    Opening and closing time
    Type Closing time (ms) Opening time (ms)
    40.5kV 30-70 15-50

    Outline dimension drawing

    A) Handcart type (The travel distance is about 615±2mm)
    VT19-40.5 handcart type circuit breaker outline dimension diagram
    Figure 1 VT19-40.5 handcart type circuit breaker outline dimension diagram (configured in medium-mounted cabinet with a width of 1400mm)
    Rated current (A) 630 1250 1600 2000 2500 3150
    Rated short circuit breaking current (kA) 20/25/31.5 31.5 31.5 31.5
    Distance between phase (mm) Φ35 Φ49 Φ55 Φ79 Φ109
    B) Fixed type
    VT19-40.5 fixed front mounted type circuit breaker outline dimension diagram
    Figure 2 VT19-40.5 fixed front mounted type circuit breaker outline dimension diagram
    Rated current (A) 630 1250 1600 2000 2500 3150
    Rated short circuit breaking current (kA) 20/25 31.5
    VT19-40.5 fixed side mounted type circuit breaker outline dimension diagram
    Figure 3 VT19-40.5 fixed side mounted type circuit breaker outline dimension diagram
    Rated current (A) 630 1250 1600 2000 2500 3150
    Rated short circuit breaking current (kA) 20/25 31.5

    Structure

    Main structure
    The circuit breaker adopts integrated structure. The design of operating mechanism and main conductive circuit are front and rear layout respectively. Operating mechanism has modular design, compact structure and stable performance. Main conductive circuit part has three choices of different types of poles: environment-friendly high strength nylon embedded pole, APG process epoxy resin sealed pole and composite insulated ordinary pole. Solid insulated and composite insulated pole both greatly reduce the accumulation of dust on the outer surface of the arc-extinguishing chamber. In particular, solid insulated pole plays a role in protecting the vacuum interrupter and anti-external arc.
    The structure of the operating mechanism
    The operating mechanism is spring energy storage operating mechanism, installed under circuit breaker. The device is the inherent component of circuit breaker, provided with stored energy part, transmission part, closing and opening units of tripping part is composed with one or several tripping electromagnet auxiliary switch, indicators, etc. There are closing-opening button, manual energy-stored handle hole, closing-opening indicators of spring energy-stored condition on the front of device. This monolithic construction reduces unnecessary intermediate link, lowers energy consumption and noise, and realizes reasonable mechanical efficiency, and stability and superior strength and stiffness, so that ensure excellent, stable and reliable mechanical characteristics of circuit breaker.

    Frequently Asked Questions (FAQ)

    What are the primary applications of the VT19-40.5 vacuum circuit breaker?
    It is designed for indoor switchgear use in three-phase 50Hz/60Hz, 35kV electric power systems. It serves as a control and protective unit for electrical facilities in industrial and mining enterprises, power plants, and substations.
    Which standards does this circuit breaker comply with?
    The VT19-40.5 circuit breaker meets the requirements of GB1984 "HV AC circuit breaker", JB3855 "HV AC vacuum circuit breaker", and relevant IEC standards.
    What are the normal ambient temperature limits for installation?
    The normal ambient operating temperature range for the circuit breaker is from -15℃ up to +40℃.
    What types of poles are available for the main conductive circuit?
    There are three choices: environment-friendly high-strength nylon embedded poles, APG process epoxy resin sealed poles, and composite insulated ordinary poles.
    What is the mechanical life expectancy of the VT19-40.5 circuit breaker?
    The circuit breaker features a robust mechanical design with a rated mechanical life of 10,000 operations.
    What kind of operating mechanism is integrated into the unit?
    It features an integrated spring energy storage operating mechanism installed directly beneath the circuit breaker, which helps reduce energy consumption, lowers noise, and ensures stable mechanical characteristics.