Leave Your Message

China VTD5-(12/24)40.5 Vacuum Circuit Breaker Suppliers | Factory Direct High-Quality GIS Solutions

General Overview
This vacuum circuit breaker, manufactured by leading China suppliers, features a horizontal layout that establishes the sealing flange plate as the benchmark installation and sealing interface. Designed for reliability, it is equipped with an advanced electric spring operating mechanism, enabling a three-pole linkage operation. This versatile device can be operated either electrically or manually, making it an essential product from our factory for various industrial applications.

    General

    For vacuum circuit breakers with a rated current of 2000 A and above, a high-strength insulating plate holding the vacuum interrupter will be used, which is mounted on the flange plate. In contrast, for those with a rated current below 1600 A, an APG enclosed-type structure is adopted. This structure fixes the vacuum interrupter (VXG) onto the flange plate using a fixed plate.

    The opening and closing operation is achieved through the connection of the vacuum interrupter's dynamic side to the insulating rod, and the stainless steel sealing bellows connecting the crank arm, rod, down crank arm, and mechanism. All secondary cables are connected to an aerial socket, which facilitates convenient secondary wiring.

    Vacuum circuit breaker has the function that open, rated current and open circuit and close short circuit current.

    Main Technical Parameters

    Item Unit Parameter
    Rated voltage kV 12 24 40.5
    Rated current A 630, 1250, 1600, 2000, 2500, 3150
    Rated short-circuit breaking current kA 20, 25, 31.5
    Rated insulation level 1 min rated power frequency withstand voltage (r.m.s) kV 42 65 95
    Rated lighting impulse withstand voltage (peak) kV 75 125 85
    Rated short-time withstand current (4s) kA 20, 25, 31.5
    Rated peak short-time current kA 50, 63, 80
    Rated short-circuit making current kA 50, 63, 80
    Rated operating sequence / O - 0.3s - CO - 180s - CO
    Mechanical life Times 10000

    Outline Dimension and Structure Diagram (mm)

    product-description1
    product-description2

    Maintenance

    The vacuum circuit breaker should be subject to an annual power-off inspection and maintenance to ensure normal operation. The inspection should cover the following aspects:

    • a Perform a power frequency withstand voltage test on the tube, measure the vacuum level, and record the results.
    • b Conduct a power frequency withstand voltage test on the insulating components.
    • c Test the breaker's contact gap, contact travel, and mechanical characteristics, and record the results.
    • d Inspect the connecting bolts, nuts, and other adjustable parts of the connections for any signs of loosening, especially the small screws at the auxiliary switch lever and the locking nuts connected to the vacuum tube's moving conductor rod.
    • e Check the retaining rings, pins, and other components at the rotating joints for any signs of loosening or disengagement; apply lubricating grease to the rotating and sliding parts.
    • f For vacuum circuit breakers used with currents exceeding 1,600 A, perform a direct current (DC) resistance test on each pole and record the results.
    • g If tube replacement is required, follow the instructions in the product manual. After replacement, conduct mechanical characteristic tests and withstand voltage tests.
    • h After the annual inspection and before commissioning, perform 8 to 10 no-load operations to ensure everything is functioning normally before commissioning.

    Frequently Asked Questions (FAQ)

    What is the structural difference between vacuum circuit breakers of different rated currents?
    For rated currents of 2000 A and above, a high-strength insulating plate is used to hold the vacuum interrupter mounted on the flange plate. For rated currents below 1600 A, an APG enclosed-type structure is adopted, which fixes the vacuum interrupter (VXG) onto the flange plate using a fixed plate.
    How is the opening and closing operation of the vacuum circuit breaker achieved?
    It is achieved by connecting the vacuum interrupter's dynamic side to the insulating rod, and using stainless steel sealing bellows to connect the crank arm, rod, down crank arm, and mechanism.
    What are the core functions of this vacuum circuit breaker?
    The vacuum circuit breaker functions to open and close rated current, open circuit current, and close short circuit current.
    How often should inspection and maintenance be conducted?
    The vacuum circuit breaker should undergo a power-off inspection and maintenance annually to ensure safe and normal operation.
    What is the mechanical life expectancy of the breaker?
    The mechanical life of the vacuum circuit breaker is rated at 10,000 operations.
    What steps should be taken after replacing the vacuum tube?
    After replacing the tube according to the product manual, you must conduct mechanical characteristic tests and withstand voltage tests, followed by 8 to 10 no-load operations before commissioning.

    Leave Your Message