China VTD5-(12/24)40.5 Vacuum Circuit Breaker Suppliers - Reliable Factory Solutions for GIS Applications

General
Our vacuum circuit breaker, designed with a horizontal layout, serves as an ideal solution for reliable power management. Featuring a sealing flange plate that functions as the benchmark installation and sealing interface, this product ensures optimal performance. The innovative electric spring operating mechanism allows for three-pole linkage and can be operated both electrically and manually, providing versatility and ease of use. As a leading supplier in China, our factory is committed to delivering high-quality vacuum circuit breakers that meet international standards.

    General

    For vacuum circuit breakers with a rated current of 2000 A and above, a high-strength insulating plate holding the vacuum interrupter will be used, which is mounted on the flange plate. In contrast, for those with a rated current below 1600 A, an APG enclosed-type structure is adopted. This structure fixes the vacuum interrupter (VXG) onto the flange plate using a fixed plate.
    The opening and closing operation is achieved through the connection of the vacuum interrupter's dynamic side to the insulating rod, and the stainless steel sealing bellows connecting the crank arm, rod, down crank arm, and mechanism. All secondary cables are connected to an aerial socket, which facilitates convenient secondary wiring.

    Function: Vacuum circuit breaker has the function that open, rated current and open circuit and close short circuit current.

    Main Technical Parameters

    Item Unit Parameter
    Rated voltage kV 12 24 40.5
    Rated current A 630, 1250, 1600, 2000, 2500, 3150
    Rated short-circuit breaking current kA 20, 25, 31.5
    Rated insulation level 1 min rated power frequency withstand voltage (r.m.s) kV 42 65 95
    Rated lighting impulse withstand voltage (peak) kV 75 125 85
    Rated short-time withstand current (4s) kA 20, 25, 31.5
    Rated peak short-time current kA 50, 63, 80
    Rated short-circuit making current kA 50, 63, 80
    Rated operating sequence / O - 0.3s - CO - 180s - CO
    Mechanical life Times 10000

    Outline Dimension and Structure Diagram (mm)

    Maintenance

    The vacuum circuit breaker should be subject to an annual power-off inspection and maintenance to ensure normal operation. The inspection should cover the following aspects:
    • a
      Perform a power frequency withstand voltage test on the tube, measure the vacuum level, and record the results.
    • b
      Conduct a power frequency withstand voltage test on the insulating components.
    • c
      Test the breaker's contact gap, contact travel, and mechanical characteristics, and record the results.
    • d
      Inspect the connecting bolts, nuts, and other adjustable parts of the connections for any signs of loosening, especially the small screws at the auxiliary switch lever and the locking nuts connected to the vacuum tube's moving conductor rod.
    • e
      Check the retaining rings, pins, and other components at the rotating joints for any signs of loosening or disengagement; apply lubricating grease to the rotating and sliding parts.
    • f
      For vacuum circuit breakers used with currents exceeding 1,600 A, perform a direct current (DC) resistance test on each pole and record the results.
    • g
      If tube replacement is required, follow the instructions in the product manual. After replacement, conduct mechanical characteristic tests and withstand voltage tests.
    • h
      After the annual inspection and before commissioning, perform 8 to 10 no-load operations to ensure everything is functioning normally before commissioning.

    Frequently Asked Questions (FAQ)

    What is the difference in structure for vacuum circuit breakers based on rated current?
    For vacuum circuit breakers with a rated current of 2000 A and above, a high-strength insulating plate is used to hold the vacuum interrupter. For those below 1600 A, an APG enclosed-type structure is adopted to fix the interrupter onto the flange plate.
    How is the opening and closing operation achieved in these circuit breakers?
    The operation is achieved by connecting the vacuum interrupter's dynamic side to the insulating rod, along with stainless steel sealing bellows connecting the crank arm, rod, down crank arm, and mechanism.
    What are the primary functions of this vacuum circuit breaker?
    The vacuum circuit breaker is designed to open and close the rated current, open the circuit, and close the short-circuit current safely.
    How often should maintenance be performed on the vacuum circuit breaker?
    It is highly recommended to perform a power-off inspection and maintenance annually to ensure the safe and normal operation of the circuit breaker.
    What tests should be conducted during annual maintenance?
    Annual maintenance should include power frequency withstand voltage tests on the tube and insulating components, vacuum level measurements, contact gap and travel checks, and a DC resistance test for breakers rated above 1600 A.