China VTD9-12D Indoor High Voltage AC Vacuum Circuit Breaker - Reliable Suppliers and Quality Factory Products
| Standard Code | Standard Description |
|---|---|
| IEC62271-1 | High voltage switchgear and control gear - Part 1: Common technical requirements for AC switchgear and control gear |
| IEC62271-100 | High voltage switchgear and control equipment - Part 100: High voltage AC circuit breakers |
| GB1984 | AC High Voltage Circuit Breaker |
| GB/T11022 | Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards |
| DL/T402 | High Voltage AC Circuit Breaker |
| JB/T3855 | High voltage AC vacuum circuit breaker |
• Daily average: ≤ 95%
• Monthly average: ≤ 90%
• Daily average vapor pressure: ≤ 2.2x10-3 MPa
• Monthly average vapor pressure: ≤ 1.8x10-3 MPa
| Item | Unit | Parameter | |
|---|---|---|---|
| Rated frequency | Hz | 50/60 | |
| Rated voltage | kV | 12 | |
| Rated power frequency withstand voltage (1 minute, r.m.s) | Phase to phase and phase to earth | kV | 42 |
| Isolation fracture | 48 | ||
| Control and auxiliary circuits | 2 | ||
| Rated lightning impulse withstand voltage (peak) | Phase to phase and phase to earth | kV | 75 |
| Isolation fracture | 85 | ||
| Rated current | A | 630, 1250 | |
| Rated short-circuit breaking current (r.m.s) | kA | 20, 25, 31.5 | |
| Rated short-time withstand current and time | kA/s | 20/4, 25/4, 31.5/4 | |
| Rated peak withstand current | kA | 50, 63, 80 | |
| Rated short-circuit making current (peak) | kA | 50, 63, 80 | |
| Rated breaking current of single/back-to-back capacitor group | A | 400(630)/400 | |
| Rated capacitor bank making current | kA | 2.5 ( fre.≤1000Hz) | |
| Rated handover (transfer) current | A | / | |
| Mechanical life | Times | 10000 | |
| Main circuit resistance of each phase | mΩ | ≤ 80, ≤ 70 | |
| Clearance between open contacts | mm | 9 ± 1 | |
| Contacting travel | mm | 5.5 ± 1 | |
| Contact closing bounce time | ms | ≤ 2 | |
| Three-phase asynchronous closing and opening | ms | ≤ 2 | |
| Average opening speed (contact just opened - 6mm) | m/s | 0.9 ~ 1.3 | |
| Average closing speed (6mm - contact just opened) | m/s | 0.4 ~ 0.8 | |
| Rated contact pressure | N | 2400±200 (20 - 25kA) | |
| 3100±200 (31.5kA) | |||
| Opening time (at rated voltage) | ms | ≤ 45 | |
| Closing time (at rated voltage) | ms | ≤ 70 | |
| Rated operating sequence | O-0.3s-CO-180s-CO | ||
The operating mechanism is integrated with the "five-prevention" interlocking mechanism, and modular design is adopted for components such as the (circuit breaker) solid-sealed pole and the earthing switch. These components are combined into a single unit through a common mounting frame.
The operating panel indicators are integrated with the primary circuit indicators, providing clear, simple, and easy-to-understand indications. The interlocking design is rationally integrated to form a "foolproof" operating procedure, making incorrect operations "impossible".
Compared with air-insulated switches of the same model and specification, the device has a smaller volume, with a cabinet width of only 500 mm. It is a paragon of the new generation of miniaturized air-insulated switchgear.
The device uses maintenance-free vacuum (arc extinguishing chamber) switch (poles), which are virtually maintenance-free, have a long service life, and offer low operating costs.
VTD9 circuit breaker, FTD9 load switch, and GTD isolating switch have identical external dimensions, facilitating the expansion and combination of switchgear cabinets.


| Rated current (A) | 630 | 1250 |
| Rated short-circuit breaking current (kA) | 20, 25, 31.5 | |
| Inter-phase distance (mm) | 210 | |

| Rated current (A) | 630 | 1250 |
| Rated short-circuit breaking current (kA) | 20, 25, 31.5 | |
| Inter-phase distance (mm) | 210 | |