Leave Your Message

China ZBW -12(2HV/LV Prefabricated Substation: Reliable Power Solutions from Leading Suppliers and Factory

Overview 
The ZBW series HV/LV prefabricated (combined) substation, manufactured by leading China suppliers, is a highly efficient and compact power distribution solution. This prefabricated substation integrates high voltage (HV) electrical equipment, transformers, and low voltage (LV) electrical equipment into a single unit. It is specifically designed for a wide range of applications, including commercial buildings, residential communities, transportation hubs, public facilities, industrial campuses, mining enterprises, and temporary setups. As a reliable choice from a trusted factory, our prefabricated substations ensure effective power acceptance and distribution for various power supply needs.

    General

    The prefabricated substation has the characteristic of high integration, compact structure, small footprint safe and reliable operation, convenient maintenance and mobility. Compared with conventional (Civil substations, the area of prefabricated (box) substations with the same capacity is usually only 1/10-1/5 0that of conventional substations, which greatly reduces the design workload and construction quantities and saves the construction cost. in the distribution system, it can be used in ring network distribution system, dual power supply or radial terminal distribution system. lt is a new complete set of equipment for the construction and transformation of urban and rural substations.

    ZBW series prefabricated substation meets requirements of lEC62271-202: 2014.

    Service Conditions

    • a Ambient temperature: -25 ℃~+ 40 ℃; maximum daily temperature difference: < 25 ℃
    • b Altitude: ≤ 1000m
    • c Relative humidity: Daily average relative humidity ≤ 95%
    • Monthly average relative humidity ≤ 90%
    • d Sunlight intensity: 0.1W/cm² (wind speed 0.5m/s);
    • e Outdoor wind speed: ≤ 35m/s;
    • f Pollution grade: Grade III;
    • g Rain proof grade: Grade 3.
    • h The gradient at installation site: ≤ 3°:
    • i Earthquake withstand level: < Grade 8;
    • j Installation site: no fire, explosion danger, serious pollution, chemical corrosion and violent vibration.
    ※ Note: If the service environment exceeds the above conditions, please confirm with the manufacturer.

    Technical Data

    Item Unit HV Unit Transformer Unit LV Unit
    Rated voltage kV 12(24) 10(20) 0.4
    Rated current A 630, 1250 - 100–4000
    Rated frequency Hz 50/60 50/60 50/60
    Rated power frequency withstand voltage (1min, r.m.s) kV To earth, phase to phase 42(65) 35/28(50/40) 2.0/2.5
    Between isolation contacts 48(79)
    Rated lightning impulse withstand voltage (peak) kV To earth, phase to phase 75(125) 75(125) -
    Between isolation contacts 85(145)
    Rated power kVA - 300–2000 -
    Rated short time withstand current / short circuit duration kA/s 20/4 - 30/1
    Rated peak withstand current kA 50 - 63
    Rated short circuit making current (peak) kA 50 - 15–30
    Fuse breaking current kA 31.5 - -
    Switch breaking current A 630, 1250 - -
    Protection level of enclosure - IP33D/IP23D (Transformer enclosure)
    Noise level dB Oil transformer ≤ 55, dry transformer ≤ 65
    Number of circuit pcs 1–6 2 4–30
    Max. reactive compensation capacity kvar - - 300

    Structure

    ◆ This product is combined with HV unit, transformer unit and LV unit, with three function compartments, that is HV compartment, transformer compartment and LV compartment, The HV/LV compartment has complete functions, and the primary power supply system at HV side can be arranged in various power supply modes, such as ring network power supply, terminal power supply, dual power supply and so on. Also, it can be equipped with HV measuring components to meet requirements of HV measuring, and low loss oil immersed transformer or dry type transformer can be selected; according to the requirements of users, the LV compartment can adopt panel or cabinet type structure to consist power supply scheme required by users, including multiple functions, such as power distribution electric, lighting power distribution, reactive power compensation, energy measurement, electrical measurement, etc. to meet different requirements of users, convenient for power supply management and improve power supply quality.

    ◆ The HV compartment has compact and optimized structure with comprehensive anti-misoperation interlocking function. When required by users, the transformer can be equipped with rail to facilitate access from the doors on both sides of the transformer compartment. Each compartment has automatic lighting device. in addition, all components selected for HV/LV switchgear have reliable performance and convenient operation, so as that the product can operate safely and reliability and maintain conveniently.

    ◆ Natural ventilation and forced ventilation can be adopted. Ventilation facilities can be equipped in transformer compartment, HV/LV compartment. Generally, when the temperature reaches the setting value, the ventilation facilities will be opened automatically to ensure the equipment can be operated normally.

    ◆ The substation structure has reasonable design and elegant appearance, made with high-quality materials, with excellent surface treatment technology, good anti-corrosion, waterproof and dust-proof performance and long service life.

    Overall Dimension

    Typical layout of 12kV substation
    Typical layout of 12kV substation
    Construction design drawing for foundation and cable incoming & outgoing
    Construction design drawing for foundation and cable incoming & outgoing (for reference)

    Typical appearances of Substation

    Typical appearance 1
    Typical appearance 2
    Typical appearance 3
    Typical appearance 4
    Typical appearance 5
    Typical appearance 6

    Frequently Asked Questions

    Q: What are the main benefits of using a prefabricated substation over a conventional civil substation?
    Prefabricated substations offer high integration, a compact structure, a small footprint (usually only 1/10 to 1/5 of the area of conventional substations), safe and reliable operation, convenient maintenance, and mobility. This greatly reduces design workload, construction quantities, and overall construction costs.
    Q: Which standards does the ZBW series prefabricated substation comply with?
    The ZBW series prefabricated substation fully meets the requirements of the international standard IEC62271-202: 2014.
    Q: What are the standard ambient service conditions required for installation?
    The substation operates under ambient temperatures between -25 ℃ and +40 ℃ (daily temperature difference < 25 ℃), at altitudes ≤ 1000m, and with daily average relative humidity ≤ 95% (monthly average ≤ 90%). The installation site gradient should be ≤ 3°, and the earthquake withstand level must be less than Grade 8.
    Q: How is ventilation managed inside the substation compartments?
    The substation can utilize both natural and forced ventilation. Ventilation facilities are equipped in the transformer and HV/LV compartments. They open automatically when the internal temperature reaches the set value to ensure normal equipment operation.
    Q: What functions can be incorporated into the Low Voltage (LV) compartment?
    Depending on user requirements, the LV compartment can adopt panel or cabinet structures. It can support multiple functions including power distribution, lighting distribution, reactive power compensation, energy measurement, and electrical measurement.
    Q: What is the ingress protection (IP) level of the enclosure?
    The general protection level of the enclosure is IP33D, while the transformer enclosure specifically has a protection level of IP23D.

    Leave Your Message