Leave Your Message

FTD9-12RD Indoor High Voltage AC Vacuum Load Switch-Fuse Combo Apparatus | China Suppliers & Factory

Product Overview
The FTD9-12RD indoor high-voltage AC vacuum load switch-fuse combination apparatus is designed for reliable performance in robust electrical systems. Manufactured in China, this innovative product features a set of three pole load switches and three fuses equipped with impactors, ensuring efficient operation. When any impactor is activated, all three poles of the load switch will automatically open, providing enhanced safety. This indoor switchgear integrates the vacuum (arc extinguishing chamber) load switch with fuses to create a series circuit. It effectively manages various load currents and overload conditions, as well as handles short-circuit situations. As a leading product from reputable Suppliers in China, the FTD9-12RD is essential for applications that require dependable short-circuit current interruption and load current management.

    Detail introduction
    This product is suitable for three-phase AC 50/60HZ, 12KV power systems, used in conjunction with complete distribution equipment, ring main unit, modular substations, etc. The layout, technical characteristics, appearance, and dimensions of this combination electrical appliance are basically the same as those of the FTD9-12D vacuum load switch, and it is particularly suitable for installation in small and limited spaces.
    Quality standard
    This product is complied with the following standards:
    GB/T16926 High voltage AC load switch- fuse combination device
    NB/T10283 Guidelines for Testing High Voltage AC Load Switch Fuse Combination Electrical Appliances
    IEC62271-105 High voltage switchgear and control equipment - Part 105: 1KV~52KV AC load switch fuse combination
    Service Conditions
    a.
    Environmental temperature: -25℃ ~ +40℃;
    b.
    Altitude: ≤ 1000m;
    c.
    Relative humidity:
    Daily average relative humidity ≤ 95%
    Monthly average relative humidity ≤ 90%
    Daily average vapor pressure ≤ 2.2x10-3 MPa
    Monthly average vapor pressure ≤ 1.8x10-3 MPa;
    d.
    Seismic grade: seismic intensity ≤ 8;
    e.
    The applicable location is free from dripping water, flammable and explosive hazards, chemical corrosive gases, and severe vibrations.
    ※ Note: When the usage environment deviates from normal usage conditions, please consult with our company to determine.
    Technical Date
    Item Unit Parameter
    Combination device
    Rated frequency Hz 50/60
    Rated voltage kV 12
    Rated power frequency withstand voltage (1 minute, r.m.s) Phase to phase and phase to ground KV 42
    Isolation fracture 48
    Control and auxiliary circuits 2
    Rated lightning impulse withstand voltage (peak) Phase to phase and phase to ground kV 75
    Isolation fracture 85
    Rated current A Depends on the fuse
    Rated short-circuit breaking current (r.m.s) kA Depends on the fuse
    Rated short-time withstand current and time kA/s /
    Rated peak withstand current kA /
    Rated short-circuit making current (peak) kA Depends on the fuse
    Rated breaking current of single/back-to-back capacitor group A /
    Rated capacitor bank making current kA /
    Rated handover (transfer) current A 3150
    Mechanical life Times 5000
    Main circuit resistance of each phase ≤250
    Clearance between open contacts mm 9±1
    Contacting travel mm 5.5±1
    Contact closing bounce time mm /
    Three-phase asynchronous closing and opening ms ≤2
    Average opening speed (contact just opened -6mm) m/s 0.9-1.3
    Average closing speed (contact just opened -6mm) m/s /
    Rated contact pressure N 1000±100
    Opening time (at rated voltage) ms /
    Closing time (at rated voltage) ms /
    Rated operating sequence /
    Typical outline dimensions (fit) and structural diagram
    product description01
    FTD9-12R (inter-phase distance P=210) outline dimension diagram of vacuum load switch-fuse combination apparatus (this diagram shows the product in the upright position, and the product can also be installed in an inverted position.)
    product description02
    FTD9-12RD (inter-phase distance P=210) outline dimension diagram of vacuum load switch-fuse combination apparatus (this diagram shows the product in the upright position, and the product can also be installed in an inverted position.)
    Frequently Asked Questions (FAQ)
    Q1: What are the primary applications of this vacuum load switch-fuse combination apparatus?
    This product is designed for three-phase AC 50/60Hz, 12KV power systems. It is commonly used in conjunction with complete distribution equipment, ring main units, and modular substations.
    Q2: Is this combination device suitable for limited installation spaces?
    Yes. The layout, technical characteristics, and dimensions are basically identical to the FTD9-12D vacuum load switch, making it highly suitable for installation in small and restricted spaces.
    Q3: What standards does this combination device comply with?
    The product complies with GB/T16926 (High voltage AC load switch-fuse combination device), NB/T10283 (testing guidelines), and IEC62271-105 standards.
    Q4: What are the environmental temperature limits for normal service conditions?
    The normal environmental operating temperature ranges from -25℃ to +40℃. For ambient conditions outside this range, please consult the manufacturer directly.
    Q5: Can this equipment be installed in an inverted position?
    Yes, according to the outline dimension diagrams (for both FTD9-12R and FTD9-12RD configurations), the product can be installed in both upright and inverted positions.
    Q6: What is the mechanical life of this combination device?
    The device is rated for a mechanical life of up to 5,000 operation cycles under standard operating conditions.

    Leave Your Message