Indoor Gas Insulated Metal-Clad Switchgear XGN (XGTD5)-(12, 24)40.5 - China Suppliers and Factory

General
Introducing the XGN (XGTD5)-(12,24)40.5 series indoor gas-insulated metal-clad switchgear, also known as the C-GIS panel. This innovative switchgear represents the forefront of technology in China, utilizing a spring-operated vacuum circuit breaker, an electrically operated three-station isolation/grounding switch, and high-quality transformers and lightning arresters as its core components. All high-voltage conductors are securely enclosed within a metal-clad structure, and the use of SF6 gas ensures exceptional insulation performance. As a leading supplier and factory in this domain, we are committed to providing reliable and efficient solutions for your electrical distribution needs.

    General
    The product has features of flexible combinations, great safety, complete interlocking logic as well as extendibility, miniaturization and free for maintenance. So that it was commonly used in infrastructure construction for power station, power substation, movable transformer pack, rail traffic, buildings that have the 35kV or below nominal voltage. Especially for some sever environment like high altitude, heavy pollution and high humidity. The product quality assurance is based on researching, developing designing and producing required by quality system and continues to improve. So it is completely complying with the newest version or revised version of following standard, but not limited to them.
    Service conditions
    Ambient temperature: -45 ℃~+40 ℃ the daily average value shall not exceed 35 ℃;
    Altitude: < 5000m above the sea level;
    Relative humidity: Daily average< 95%, Monthly average is < 90%;
    Seismic grade: the seismic intensity shall not exceed grade 8;
    Inductive electromagnetic interference value of secondary system: not more than 1.6 KV.
    Note: If the service environment exceeds the above conditions, please consult with our company.
    Technical Parameter
    Main technical parameters of switchgear
    Item Unit Parameters
    Rated voltage kV 12 24 40.5
    Rated current A 630/1250/1600/2000/2500/3150
    Rated frequency Hz 50/60
    1 min Rated power frequency withstand voltage (RMS) Phase to Phase
    Phase to earth
    kV 42 65 95
    Insulation Distance 48 79 118
    Rated Lightning impulse withstand voltage (peak) Phase to Phase
    Phase to earth
    kV 75 125 185
    Insulation Distance 85 145 215
    Rated power frequency withstand voltage of auxiliary circuit kV 2
    Rated short-circuit breaking current(RMS) kA 20/25/31.5/40
    Rated short-circuit making current (peak) kA 50/63/80/100
    Rated short-time withstand current (4s) kA 20/25/31.5/40
    Rated peak withstand current kA 50/63/80/100
    Main circuit resistance of each phase μ Ω Rated current≤1600A,Rc≤220
    Rated current≥2000A, Rc≤105
    Rated voltage of auxiliary and control circuit V DC110/220AC220
    Rated SF6 gas pressure (20℃) MPa 0.04/0.05
    Min SF6 gas pressure (20℃) MPa 0.03
    Annual SF6 gas loss rate ≤5
    Degree of Protection / HV compartment IP67; LV compartment IP4X
    Weight Kg 1000~1600
    Main technical parameters of vacuum circuit breaker
    Item Unit Parameters
    Rated voltage kV 12 24 40.5
    Rated current A 630/1250/1600/2000/2500/3150
    Rated frequency Hz 50/60
    1 min Rated power frequency withstand voltage (RMS) Phase to Phase/Phase to earth kV 42 65 95
    Insulation Distance 48 79 118
    Rated Lightning impulse withstand voltage(peak) Phase to Phase/Phase to earth kV 75 125 185
    Insulation Distance 85 145 215
    Rated short-circuit breaking current(RMS) kA 20/25/31.5/40
    Rated short-circuit making current(peak) kA 50/63/80/100
    Rated short-time withstand current (4S) kA 20/25/31.5/40
    Rated peak withstand current kA 50/63/80/100
    Mechanical life Times 10000
    Rated operating sequence / 0-0.3s-CO-3min-CO
    Clearance between open contacts mm 9±1 13±1 18±1
    Contact touching range mm 3±0.5 3±0.5 3±0.5
    Contact closing bounce time ms ≤2
    Three-phase closing &opening asynchrony ms ≤2
    Average opening speed (at the initial 75%opening distance) m/s 0.8~1.4 1.2~1.6 1.2~1.8
    Average closing speed (at the initial 75%opening distance) m/s 0.4~0.8 0.5~0.9 0.8~1.2
    Opening time ms 35±10
    Closing time ms 50±10
    Rebound amplitude of opening contact mm ≤2
    Main circuit resistance of each phase μΩ ≤25
    Energy storage time of closing spring S ≤15
    Note: The above insulation levels are reference values at the rated working pressure of the insulating gas.
    Structure
    product-description1
    Figure 1 Typical structure of circuit breaker cabinet
    (Bus top connection - cables input & output and outer cone bushing)
    A. Bus panel  |  B. Meter panel  |  C. Circuit breaker panel  |  D. Cable panel  |  E. Mechanism panel
    1Front panel
    2Framework
    3Back panel
    4HV cable (user prepare)
    5Back plug type lightning arrester
    6CT (ring core type)
    7Extended outer cone bushing
    8Vacuum circuit breaker
    9Outer cone bushing
    10Gas tank
    11Branch bus
    12Pressure release device for circuit breaker panel
    13Three position switch operating mechanism
    14Gas density relay
    15Three position DS/ES
    16Secondary unit panel
    17Top connection outer cone bushing
    18Pressure release device for bus panel
    19Top connection main bus
    product-description2
    Figure 2 Typical structure of circuit breaker cabinet
    (Bus side connection - cable input & output and inner cone bushing)
    A. Bus panel  |  B. Meter panel  |  C. Circuit breaker panel  |  D. Cable panel  |  E. Mechanism panel
    1Front panel
    2Framework
    3HV cable (user prepare)
    4Lightning arrester
    5CT
    6HV charged display
    72# Inner cone outlet
    83# inner cone outlet
    9CT (built-in type)
    10Vacuum circuit breaker
    11Gas tank
    12Branch bus
    13Three position switch operating mechanism
    14Gas density relay
    15Pressure release device for vacuum circuit breaker panel
    16Three position DS/ES
    17Secondary components front-panel
    18Main bus and side connection inner cone bushing
    19Pressure relief device for bus panel
    Frequently Asked Questions (FAQ)
    What are the primary applications for this switchgear?
    This product is designed for infrastructure construction in power stations, power substations, movable transformer packs, rail traffic, and buildings with a nominal voltage of 35kV or below. It is especially suitable for severe environments such as high altitudes, heavy pollution, and high humidity areas.
    Can this equipment operate reliably at high altitudes?
    Yes, it is designed to operate under standard service conditions at altitudes up to 5000m above sea level. If your installation environment exceeds this limit, please contact our technical team for custom solutions.
    What is the IP protection rating of the switchgear compartments?
    The switchgear features superior environmental protection, with the High-Voltage (HV) compartment rated at IP67 and the Low-Voltage (LV) compartment rated at IP4X.
    What is the mechanical lifespan of the integrated vacuum circuit breaker?
    The vacuum circuit breaker is engineered for high durability with a rated mechanical life of up to 10,000 operations.
    What are the acceptable temperature limits for operation?
    The standard ambient temperature range for reliable operation is from -45 ℃ to +40 ℃, with the daily average value not exceeding 35 ℃.