KYN28A-12(2Air-Insulated Metal-Clad Switchgear - Reliable Power Distribution from China Suppliers & Factory

General 
The KYN28A Air-Insulated Withdrawable Metal-Clad Switchgear, commonly known as KYN28A switchgear, offers a comprehensive solution for 15~24kV three-phase AC distribution systems featuring a single busbar and segmented configurations. This advanced switchgear is designed and manufactured by top suppliers in China, ensuring high quality and reliability.

,

 

,

This equipment is primarily utilized in power plants, substations, industrial and mining enterprises, as well as high-rise buildings for efficient power transformation and distribution. It plays a crucial role in receiving and redistributing electrical energy, while also providing control, protection, and monitoring for electrical lines. Choose our KYN28A switchgear from a trusted factory in China to enhance your electrical distribution systems.

    Detail introduction

    The KYN28A switchgear meets the requirements of IEC298, GB3906 and other standards, and has interlocking functions to prevent pushing-pulling circuit breaker handcart with load, prevent accidental opening and closing of the circuit breaker, prevent closing of the circuit breaker when the earthing switch is in the closed position, prevent accidental entry into the live compartment, and prevent accidental closing of the earthing switch when charged.
    KYN28A switchgear is a mid-mounted, miniaturized, metal-clad, and air insulated switchgear. According to the different purposes of the mid-mounted handcart, it can be divided into: circuit breaker handcart, contactor handcart, load switch handcart, isolation handcart, PT handcart, metering handcart, fuse handcart, lower PT handcart, lower lightning arrester handcart, etc. The main switch can be equipped with vacuum circuit breakers from domestic or foreign manufacturers such as VS1 (VTD6), VT19, VD4, etc., which is actually a high performance distribution device.
    The design and manufacturing of KYN28 switchgear comply with the following standards:
    IEC62271-200 AC metal-clad switchgear and control equipment with rated voltage of 1kV and above & 52kV and below
    IEC62271-100 High voltage switchgear and control device - Part 100: AC current circuit breakers
    GB/T3906 3.6kV - 40.5kV AC metal-clad switchgear and control equipment
    GB/T11022 Common technical requirements for high-voltage switchgear and control equipment standards
    GB/T1984 High voltage AC circuit breaker
    DL/T404 3.6kV - 40.5kV AC metal-clad switchgear and control equipment

    Service Conditions

    • Altitude: ≤1000m;
    • Ambient temperature: -15℃~ +45℃(-25℃ is allowed to transport and storage );
    • Relavent humidity: daily average humidity ≤ 95%,monthly average humidity ≤ 90%;
    • Suitable for condensation and Class II polluted environments;
    • The seismic intensity shall not exceed Grade 8;
    NOTE: If the clients deviate normal operating,please communicate with manufacturer.

    Technical Data

    Technical Parameter of KYN28A-12 Switchgear
    Item Unit Parameter
    Rated voltage kV 12
    Rated frequency Hz 50/60
    Rated insulation level 1min Power frequency withstand voltage (isolating fracture) kV 42/48
    Lightening impulse withstand voltage (isolating fracture) kV 75/85
    1min Power frequency withstand voltage of auxiliary circuit V 2000
    Rated current A 630, 1250, 1600, 2000, 2500, 3150, 4000, 5000
    Rated short circuit breaking current (r.m.s) kA 20, 25, 31.5, 40, 50
    Rated short circuit making current (peak value) kA 50, 63, 80, 100, 125
    Rated short time withstand current (4S, r.m.s) kA 20, 25, 31.5, 40, 50
    Rated peak withstand current kA 50, 63, 80, 100, 125
    Rated voltage of auxiliary control circuit V DC110/220 AC220
    Degree of protection - Enclosure: IP4X
    Overall dimension (W×D×H) mm 650×1500/1660×2300  800×1500/1660×2300  1000×1500/1660×2300
    Note: For rated currents of 4000A and above, forced air cooling is required.
    Technical Parameter of KYN28A-24 Switchgear
    Item Unit Parameter
    Rated voltage kV 24
    Rated frequency Hz 50/60
    Rated insulation level 1min Power frequency withstand voltage (isolating fracture) kV 65/79
    Lightening impulse withstand voltage (isolating fracture) kV 125/145
    1min Power frequency withstand voltage of auxiliary circuit V 2000
    Rated current A 630, 1250, 1600, 2000, 2500, 3150
    Rated short circuit breaking current (r.m.s) kA 20, 25, 31.5
    Rated short circuit making current (peak value) kA 50, 63, 80
    Rated short time withstand current (4S, r.m.s) kA 20, 25, 31.5
    Rated peak withstand current kA 50, 63, 80
    Rated voltage of auxiliary control circuit V DC110/220 AC220
    Degree of protection - Enclosure: IP4X
    Overall dimension (W×D×H) mm 800×1860/2260×23801)   1000×1860/2260×2380
    Note: 1) Rated current ≤ 1250A

    Structure

    KYN28A switchgear is designed as per the standards of insulation matel-clad switchgear , conforms to IEC62271 and GB/T3906. The whole structure has two main parts, such as cabinet body and mid-mounted withdrawable unit (or handcart), as shown in diagram 1. It has bottom cable incoming & outgoing scheme、overhead incoming & outgoing scheme and other function scheme which can constitute many schemes about power distribution devices. The switchgear could install, adjust and maintain at the front., so it can be installed in double row back to back or face to face and also can installed by way.
    Outline Dimensions and Internal Structure Diagram of Typical Scheme KYN28A-12/1250-31.5
    product description01
    Compartments & Components:
    A. Instrument Compartment
    B. Circuit breaker compartment
    C. Busbar Compartment
    D. Cable Compartment

    1. Pressure relief device
    2. Cabinet frame
    3. Branch busbar
    4. Busbar bushing
    5. Main busbar
    6. Contact device
    7. Static contact box
    8. Current transformer
    9. Earthing switch
    10. Cable
    11. Lightning arrester
    12. Heater
    13. Cable cover plate
    14. Earthing busbar
    15. Earthing switch operating mechanism
    16. Withdrawable horizontal clapboard
    17. Circuit breaker handcart
    18. Secondary plug device
    19. Valve
    20. Detachable clapboard
    21. Small control busbar
    Item Unit Parameter
    Height (H) mm 2320
    Width (W) Rated Current of Branch Busbar ≤ 1250A
    Rated short time withstand current ≤ 31.5kA
    mm 630(optional)  800
    Rated Current of Branch Busbar ≤ 1250A-1600A
    Rated short time withstand current ≤ 31.5kA
    mm 800
    Rated Current of Branch Busbar ≥ 2000A
    Rated short time withstand current ≤ 31.5kA
    mm 1000
    Depth (D) Cable incoming & outgoing mm 1450
    Overhead incoming & outgoing mm 1610
    Weight kg 700~1200
    Outline Dimensions and Internal Structure Diagram of Typical Scheme KYN28A-24/1250-31.5
    product description02
    Compartments & Components:
    A. Instrument Compartment
    B. Circuit breaker compartment
    C. Busbar Compartment
    D. Cable Compartment

    1. Main busbar
    2. Branch busbar
    3. Contact box device
    4. Current transformer
    5. Earthing switch
    6. Primary cable
    7. Circuit breaker
    8. LV connector plug
    9. Valve device
    Item Unit Parameter
    Height (H) mm 2380
    Width (W) Rated Current of Branch Busbar ≤ 1250A
    Rated short time withstand current ≤ 31.5kA
    mm 800(optional)  1000
    Rated Current of Branch Busbar ≤ 1250A-3150A
    Rated short time withstand current ≤ 31.5kA
    mm 1000
    Depth (D) Cable incoming & outgoing mm 1810
    Overhead incoming & outgoing mm 2200
    Weight kg 850~1400

    Frequently Asked Questions (FAQ)

    What standards does the KYN28A switchgear comply with?
    The KYN28A switchgear is designed and manufactured in compliance with major international and national standards, including IEC62271-200, IEC62271-100, GB/T3906, GB/T11022, GB/T1984, and DL/T404.
    What interlocking safety functions are built into the KYN28A switchgear?
    It features interlocking functions to prevent pushing-pulling the circuit breaker handcart with load, prevent accidental opening and closing of the circuit breaker, prevent closing of the circuit breaker when the earthing switch is closed, prevent accidental entry into live compartments, and prevent closing of the earthing switch when charged.
    What types of handcarts can be used in KYN28A switchgear?
    Depending on the application, it can accommodate circuit breaker handcarts, contactor handcarts, load switch handcarts, isolation handcarts, PT handcarts, metering handcarts, fuse handcarts, lower PT handcarts, and lower lightning arrester handcarts.
    What are the normal environmental service conditions for KYN28A switchgear?
    Standard operating conditions require an altitude of ≤1000m, ambient temperature between -15℃ and +45℃, daily average relative humidity ≤95% (monthly ≤90%), and suitability for condensation, Class II polluted environments, and seismic intensity up to Grade 8.
    When is forced air cooling required for the KYN28A switchgear?
    For KYN28A-12 switchgear configurations, forced air cooling is specifically required for rated currents of 4000A and above.
    What is the enclosure protection degree of the KYN28A switchgear?
    Both the KYN28A-12 and KYN28A-24 models feature an enclosure with a protection degree of IP4X to ensure safety and prevent accidental contact with internal parts.