0102030405
MNS Low Voltage Switchgear from China Suppliers - Reliable Factory for Power Distribution Solutions
Advantages
The electrical structure of the MNS switchgear is designed with a modular concept, and the switchgear frame structure offers high flexibility. Various electrical components can be installed inside the switchgear to meet different application requirements and to achieve the corresponding protection levels for different working environments. It can be selected as a new type of low-voltage switchgear by users.
Compared with traditional products, the MNS cabinet has the following advantages:
Compared with traditional products, the MNS cabinet has the following advantages:
Standardized and modular design for the entire series.
The switchgear can be designed with different protection levels according to the working and environmental requirements.
Different types of functional components can be freely installed in the same switchgear, such as fixed components and withdrawable components.
Compact structure that saves space inside the switchgear.
The distribution circuit layout is economical and the installation density is high.
The switchgear can be arranged back-to-back.
Equipment updates and improvements are convenient.
The equipment has high reliability and continuity in operation.
Fully guarantee the personal safety of operators.
Standards
IEC61439-2 "Low voltage switchgear and control equipment"
GBIT7251.12 "Low Voltage Switchgear and Control Equipment"
GBIT24274 "Low voltage withdrawable switchgear and control equipment"
Type and meaning
Service conditions
a. Installation position:
MNS switchgear is a complete electrical equipment installed indoors. When the protection level reaches IP54, it can operate under other working conditions.
b. Ambient temperature and relative humidity:
The upper limit of ambient temperature is 40 ℃, and the average temperature within 24 hours shall not higher than 35 ℃; The lower limit of ambient temperature is -5 ℃. When the equipment is used under conditions higher than the above ambient temperature, it should be operated at reduced capacity.
The air is clean, and the relative humidity should not exceed 50% at 40 ℃. Higher relative humidity is allowed at lower temperatures (e.g. 90% at 20 ℃). In cases where condensation may occur, ventilation or heating measures can be used in the switchgear to prevent condensation.
The air is clean, and the relative humidity should not exceed 50% at 40 ℃. Higher relative humidity is allowed at lower temperatures (e.g. 90% at 20 ℃). In cases where condensation may occur, ventilation or heating measures can be used in the switchgear to prevent condensation.
c. Altitude:
The altitude of the location where the switchgear is used shall not exceed 2000m. If the switchgear is installed in an area above an altitude of 2000m, the equipment should be correspondingly reduced in capacity for operation.
Main technical parameters
| Electrical parameters | Rated voltage | Rated insulation voltage Ui | AC 690V / 1000V |
|
| Rated working voltage Ue | AC 400V / 690V |
|||
| Rated impulse withstand voltage Uimp | 8kV / 12kV |
|||
| 1-minute power frequency withstand voltage | 2.5kV / 3.5kV |
|||
| Rated current | Main busbar | Rated current le | To 6300A |
|
| Rated peak withstand current lpk | To 220kA |
|||
| Rated short-time withstand current lcw | To 100kA |
|||
| Vertical busbar1 | Rated current le | To 1250A |
||
| Rated peak withstand current lpk | To 143kA |
|||
| Rated short-time withstand current lcw | To 65kA |
|||
| Rated frequency | 50Hz / 60Hz |
|||
| Structural features | Dimensions | Height (mm) | 2200 |
|
| Width (mm) | 400, 600, 800, 1000, 1200 |
|||
| Depth(mm) | 600, 800, 1000, 1200 |
|||
| Modulus | E=25mm |
|||
| Internal separation form | To 4b | |||
| Protection level | IP30, IP40, IP42, IP54 | |||
| Note 1: Vertical busbar specifically refers to the distribution busbar of drawer switchgear, the same applies below. | ||||
Frequently Asked Questions (FAQ)
1. What are the key design advantages of MNS switchgear?
MNS switchgear features a standardized, modular design offering high structural flexibility. It allows the integration of various functional components (fixed and withdrawable) within the same cabinet, saves space, provides high installation density, and ensures operator safety.
2. Which standards does the MNS switchgear comply with?
The equipment complies with IEC61439-2 ("Low voltage switchgear and control equipment"), GBIT7251.12 ("Low Voltage Switchgear and Control Equipment"), and GBIT24274 ("Low voltage withdrawable switchgear and control equipment").
3. What are the environmental operating limits for MNS switchgear?
The ambient temperature should be between -5 ℃ and 40 ℃, with a 24-hour average not exceeding 35 ℃. The relative humidity should not exceed 50% at 40 ℃, though higher humidity is permitted at lower temperatures. Clean, indoor installation is required.
4. Can MNS switchgear run at high altitudes?
Yes, but the standard installation altitude is up to 2000m. If the switchgear is installed in areas exceeding 2000m, the operational capacity of the equipment must be reduced accordingly.
5. What protection levels (IP ratings) can the MNS cabinet support?
Depending on the specific working and environmental requirements, the switchgear can be designed to meet IP30, IP40, IP42, or IP54 protection levels.
6. What is the maximum rated current for the main busbar?
The rated current for the main busbar can reach up to 6300A, with a rated peak withstand current (lpk) of up to 220kA and a rated short-time withstand current (lcw) of up to 100kA.