A 12kV panel and a 24kV panel look almost identical from the aisle, but the BIL numbers, clearance gaps, and creepage distances under the cover tell the real story. Picking the wrong voltage class costs a substation in two places — insulation coordination failures on commissioning day, and unusable spare breakers on day 2000.
KYN28A-12(24) air-insulated withdrawable metal-clad switchgear, a 12kV / 24kV dual-rated panel built to IEC 62271-200 BIL benchmarks.The Voltage Class Stack: 12kV, 24kV, 40.5kV at a Glance
Medium-voltage switchgear is organized into three voltage classes — 12 kV, 24 kV, and 40.5 kV — that map to different positions in the distribution network. The numbers come from the IEC 60038 standard voltage series, which sets 12 kV as the standard distribution level for utility primary feeders, 24 kV as the dense urban and renewable-collection standard increasingly adopted in Asia and Europe, and 40.5 kV as the sub-transmission interface for utility-scale generation and industrial customers with on-site generation.
The class is the operating voltage the panel will see at its terminals under normal load. It is not the dielectric stress the panel must survive during a lightning strike or a switching transient. That second number is the Basic Insulation Level (BIL), and it scales faster than the voltage class itself. According to IEC 62271-200, the high-voltage switchgear and controlgear standard that defines both insulation coordination and type testing, the BIL for a 12 kV panel is 75 kVp, for 24 kV is 95 to 125 kVp depending on the insulation level chosen, and for 40.5 kV is 150 to 185 kVp.
A practical way to think about the three classes: 12 kV is the workhorse of urban distribution and small commercial; 24 kV is the dense-urban and renewable-collection sweet spot; 40.5 kV is the industrial and utility generation gateway.
Where Each Class Actually Lives in a Substation
The voltage class is not a marketing decision — it follows from the upstream transformer and the downstream load. If the upstream transformer secondary is 11 kV or 12.5 kV (typical for a 33/0.4 kV or 110/11 kV utility step-down), the switchgear must be 12 kV class. If the upstream is 22 kV or 24 kV (common in dense urban Asia, Middle East, and parts of South America), the switchgear must be 24 kV class. If the upstream is 33 kV or 35 kV (utility-scale solar PV, wind farm collection, large industrial with cogeneration), the switchgear is 40.5 kV class.
Three concrete placements illustrate how this maps in real substations. First, in a 110/10 kV urban Distribution Substation feeding residential and small commercial load, all switchgear on the 10 kV side is 12 kV class — the panel sees 10 kV operating voltage and must withstand 75 kVp BIL. Second, in a 66/22 kV industrial substation feeding a large manufacturing plant, the switchgear on the 22 kV side is 24 kV class — the panel sees 22 kV operating voltage and must withstand 95 to 125 kVp BIL depending on the chosen insulation level. Third, in a 100 MW solar farm with a 35 kV collection network, the switchgear at the pool substation is 40.5 kV class — the panel sees 35 kV operating voltage and must withstand 150 to 185 kVp BIL.
OEM documentation from manufacturers like Hitachi Energy organizes their product catalogs around exactly this three-class structure, which is a useful sanity check that the class you are specifying matches the upstream transformer.
BIL Benchmarks — The Non-Negotiable Numbers
| Voltage Class (kV) | BIL — List 1 (kVp) | BIL — List 2 (kVp) | Power Frequency Withstand (kV rms) | Switching Impulse (kVp) |
|---|---|---|---|---|
| 12 kV | 60 kVp | 75 kVp | 28 kV rms | — |
| 24 kV | 95 kVp | 125 kVp | 50 kV rms | — |
| 40.5 kV | 150 kVp | 185 kVp | 80 kV rms | — |
For most international projects outside North America, "List 2" is the default. That gives the practical benchmark most procurement specs use: 75 kVp for 12 kV, 125 kVp for 24 kV, and 185 kVp for 40.5 kV. For North American projects that reference IEEE C37.20.1 / C37.20.7 instead of IEC, the BIL numbers are slightly different but the principle is identical: BIL scales faster than operating voltage because the impulse overvoltage from a lightning strike or a capacitor switching event is not proportional to the 50/60 Hz operating voltage.
Three places where the BIL number on the spec sheet must be verified, not assumed. First, the type test report from the OEM must show the actual impulse voltage applied and the pass/fail result. Second, the BIL of the busbar system and the BIL of the circuit breaker must match — a 75 kVp breaker in a 125 kVp panel is a mismatch that shows up at the next impulse test. Third, the BIL of any cable termination or Current Transformer must be coordinated with the panel; mismatched CTs are a common source of insulation failure that has nothing to do with the panel design itself.
Why BIL Goes Up Faster Than Voltage
A frequent question from procurement engineers is why BIL rises faster than the voltage class — the ratio from 12 kV to 24 kV is 2x, but BIL rises from 75 to 125 kVp which is closer to 1.67x; the ratio from 24 kV to 40.5 kV is 1.69x but BIL rises from 125 to 185 kVp which is 1.48x. The reason is that the lightning impulse withstand is determined by the overvoltage that the network can deliver to the panel terminals, not by the operating voltage alone.
Three overvoltage sources contribute to the impulse stress: lightning strikes on overhead lines entering the substation (the largest contributor in tropical and high-isokeraunic regions), capacitor bank switching transients (proportional to the operating voltage times a switching surge factor), and short-circuit fault initiation (proportional to the system voltage and the network impedance). As the voltage class rises, the lightning impulse overvoltage rises faster than the operating voltage because the strike is delivering a fixed kilovolt peak to the line regardless of the operating voltage. At higher voltage classes, the switching impulse also becomes a defining test parameter per IEC 62271-200, even though medium-voltage switchgear is rarely tested for switching impulse in the 12 kV range.
This is also why the BIL test for medium-voltage switchgear is a 1.2/50 µs lightning impulse waveform, not a continuous AC test. The waveform approximates the steep-front overvoltage from a lightning strike, and the panel must survive three positive and three negative shots at the rated BIL per IEC 62271-100. If a panel is specified at 75 kVp BIL and only tested at 60 kVp, the panel may pass commissioning but will fail the next impulse event in service.
Clearance Benchmarks — Phase-to-Phase and Phase-to-Earth
| Voltage Class (kV) | BIL (kVp) | Phase-to-Earth Min Clearance (mm) | Phase-to-Phase Min Clearance (mm) | Isolating Distance (mm) |
|---|---|---|---|---|
| 12 kV | 75 kVp | 100 mm | 110 mm | 120 mm |
| 24 kV | 125 kVp | 160 mm | 180 mm | 200 mm |
| 40.5 kV | 185 kVp | 290 mm | 320 mm | 360 mm |
These clearance numbers are the minimum values for a sea-level installation in a clean, dry switchgear room. Real installations usually specify more, not less, because panel builders round up to accommodate busbar supports, current transformer housings, and cable termination geometry. A 12 kV panel with 100 mm phase-to-earth clearance will pass the dielectric test but a 12 kV panel with 130 mm phase-to-earth clearance is the practical OEM standard for almost all withdrawable designs.
The creepage distance is the second half of the clearance story. Creepage is the shortest path along the surface of an insulating material between two conductors; it is the parameter that fails first in humid or polluted environments. For a clean indoor switchgear room, 16 mm/kV is the baseline creepage. For an outdoor or polluted indoor environment, the creepage rises to 25 mm/kV or 31 mm/kV depending on the pollution severity. A 24 kV panel in a polluted indoor environment needs at least 25 × 24 = 600 mm of creepage across the busbar support insulators, which is a real design constraint that shows up in the panel outline drawing.
Altitude, Humidity, and Pollution — How They Bend the Numbers
Three environmental factors bend the BIL and clearance numbers above. First, altitude. Above 1,000 meters, the dielectric strength of air decreases at approximately 1% per 100 meters of additional altitude because the air density drops. IEC 62271-1 publishes correction factors that the BIL clearance must be multiplied by for installations above 1,000m. A panel specified for sea level but installed at 2,500m requires either derating or a higher BIL class. The correction factor at 2,500m is 1.15, meaning a 75 kVp 12 kV panel becomes effectively a 63 kVp panel — which is below the BIL for the class.
Second, humidity. Sustained relative humidity above 80% reduces the surface resistivity of busbar supports and accelerates tracking on insulating materials. The standard mitigation is heater strips inside the switchgear cubicle, plus the creepage distance adjustment above. For tropical coastal installations where humidity regularly exceeds 90% RH, the panel should be ordered with the higher creepage class from the factory, not retrofitted in the field.
Third, pollution. Conducting pollutants (salt fog near coastlines, dust near cement plants, sulfur compounds near refineries) deposit on insulating surfaces and create creepage paths that the clean-room creepage distance does not anticipate. Per IEC 60815, pollution severity is classified from light (I) to very heavy (IV), and each step roughly doubles the required creepage distance. For a 24 kV panel in a coastal substation, the pollution severity is typically III or IV, and the creepage distance needs to be 31 mm/kV or higher, which means 31 × 24 = 744 mm minimum creepage on each insulator.
For utility-scale solar and wind installations, the most common environmental constraint is altitude combined with pollution — solar plants at 1,500m to 2,500m in dusty or coastal regions must derate for both factors. According to GE Vernova field data on renewable-collection substations, the failure mode for under-spec'd switchgear at altitude is almost always insulation breakdown, not breaker failure, because the breaker was tested at sea level but the panel was installed above the altitude factor limit.
KYN28A-12(24) Implementation: How Tianan Builds It
The KYN28A-12(24) air-insulated withdrawable metal-clad switchgear panel is a real-world implementation of the BIL and clearance numbers above. Tianan's panel is dual-rated 12 kV and 24 kV class on the same frame, with the BIL configured at 75 kVp for the 12 kV rating and 125 kVp for the 24 kV rating per the IEC 62271-200 List 2 common practice. The withdrawable circuit breaker is on a trolley that rolls out of the panel for service, which is the configuration the HV and MV switchgear category is organized around.
Three design points are worth flagging for a buyer evaluating this panel. First, the BIL test certificate from the OEM must show the 75 kVp and 125 kVp impulse waveforms separately, not a single ambiguous "tested per IEC" claim. Second, the creepage distance of the busbar support insulators must be quoted in mm/kV, not just in mm, because the same physical insulator can be used at different voltage classes with different creepage performance. Third, the panel's rated altitude factor must be on the nameplate; a panel rated for 1,000m cannot be installed at 2,500m without derating or field modification.
The KYN28A-12(24) air-insulated withdrawable metal-clad switchgear product page on the Tianan Overseas site lists the panel dimensions, the BIL configuration options, and the compatible breaker ratings. For a buyer who needs to match a voltage class with the right BIL, the fastest path is to contact the Tianan engineering team with the upstream transformer secondary voltage, the installation altitude, and the indoor or outdoor classification; the team will respond with a configured panel outline that matches.
Selection Checklist: 7 Questions Before You Spec
1. What is the upstream transformer secondary voltage? The switchgear voltage class must equal or exceed the transformer secondary under all tap positions. A 22 kV transformer with a +5% tap requires a 24 kV class panel.
2. What BIL is on the type test certificate? IEC 62271-200 List 2 gives 75 / 125 / 185 kVp for 12 / 24 / 40.5 kV. List 1 gives lower values. Specify which list, not just "per IEC".
3. What is the installation altitude? Above 1,000 m, the BIL clearance must be multiplied by an altitude correction factor. Above 2,500 m, the standard correction factor exceeds 1.15.
4. What is the pollution severity? Indoor clean (I), indoor light (II), outdoor coastal (III), outdoor industrial (IV). Each step doubles the creepage distance requirement per IEC 60815.
5. What is the minimum creepage distance in mm/kV? 16 mm/kV baseline for clean indoor; 25 mm/kV for outdoor light; 31 mm/kV for outdoor heavy. The number must be on the insulator spec, not inferred from panel outline.
6. What is the panel's rated short-circuit withstand current? 25 kA / 31.5 kA / 40 kA for 1s or 3s. The breaker and the busbar must be rated to the same value, not just the panel nameplate.
7. Is the panel rated for the actual ambient temperature? Standard panels are rated for -5°C to +40°C. Above +40°C or below -15°C requires derating or special enclosure design.
For more on switchgear insulation coordination beyond the BIL/clearance basics, the standards library at the CIGRE international council on large electric systems publishes working group reports on substation design, insulation coordination, and high-voltage testing that are freely available to member utilities.
Match a voltage class with our engineers.
Send your upstream transformer voltage, installation altitude, and pollution severity:
Contact Tianan Overseas engineering →
FAQ: 12kV vs 24kV vs 40.5kV Switchgear and BIL
- What does BIL mean in switchgear selection?
- BIL (Basic Insulation Level) is the standardized lightning impulse withstand voltage a switchgear panel must survive without flashover, expressed in kilovolts peak (kVp) per IEC 62271-200. Common BIL values for medium-voltage switchgear are 75 kVp at 12 kV, 95 to 125 kVp at 24 kV, and 150 to 185 kVp at 40.5 kV. The voltage class alone does not define insulation coordination; the BIL number does.
- Is 24kV switchgear just a 12kV panel with more insulation?
- No. 24kV switchgear is engineered for higher BIL (typically 125 kVp vs 75 kVp at 12kV), larger phase-to-phase and phase-to-earth clearances, longer creepage distances, and revised internal compartment layouts. A 12kV panel rated to 24kV without redesign fails both the dielectric tests and the partial discharge tests defined in IEC 62271-200.
- When should a solar farm spec 40.5kV switchgear instead of 24kV?
- 40.5kV switchgear is typically specified for utility-scale solar farms above 50 MW where the medium-voltage collection network runs at 33kV or 35kV to limit I²R losses over long cable runs. Below 50 MW, 24kV collection is usually more cost-effective. For rooftop or small commercial solar (under 5 MW), 12kV switchgear is the standard interface to the utility feeder.
- How much does altitude change the BIL requirement?
- Above 1,000 meters, the dielectric strength of air decreases at approximately 1% per 100 meters of additional altitude. IEC 62271-1 requires the BIL clearance to be corrected for installation altitude, and switchgear ordered for sites above 1,000m typically specifies an altitude factor of 1.1 to 1.25. A switchgear panel specified for sea level but installed at 2,500m requires derating or a higher BIL class.
- KYN28A vs XGN switchgear: which to choose?
- KYN28A is a withdrawable (draw-out) air-insulated metal-clad switchgear design with the circuit breaker on a trolley, allowing quick swap-out for maintenance. XGN is a fixed-type air-insulated metal-enclosed design with the breaker bolted in place. KYN28A costs more and is larger, but reduces mean time to repair on the line; XGN is smaller and cheaper but requires full compartment de-energization for breaker service.










