SC Series 10kV Dry-type Transformer
General
Application
Inquiry and order
|
Type |
||
|
Rated capacity |
kVA |
|
|
Number of phases / Frequency |
Phase |
Hz |
|
Rated voltage |
HV (kV) |
LV (kV) |
|
Tapping range |
±2x2.5%, ±5% or others |
|
|
Connection symbol |
D,yn11、Y,yn0 or others |
|
|
Short-circuit impedance kVA |
% |
|
|
Cooling method |
AN or AF |
|
|
Degrees of protection |
IP00, IP20 or IP23 |
|
|
Service conditions |
Altitude (m) |
Ambient temperature (℃) |
|
Optional accessories(Temperature thermometer and Temperature control box) |
||
|
Miscellaneous |
||
|
Quantities ordered and time delivery |
||
| Rated capacity kVA |
Level Ⅰ |
Level Ⅱ |
Level Ⅲ |
Short circuit impedance % |
|||||||||
|
No -Load Loss W |
Load Loss W |
No -Load Loss W |
Load Loss W |
No-Load Loss W |
Load Loss W |
||||||||
|
B
|
F 120℃ |
H 145℃ |
B
|
F 120℃ |
H 145℃ |
B |
F 120℃ |
H 145℃ |
|||||
| 30 |
105 |
605 |
640 |
685 |
130 |
605 |
640 |
685 |
150 |
670 |
710 |
760 |
4.0 |
| 50 |
155 |
845 |
900 |
965 |
185 |
845 |
900 |
965 |
215 |
940 |
1000 |
1070 |
|
| 80 |
210 |
1160 |
1240 |
1330 |
250 |
1160 |
1240 |
1330 |
295 |
1290 |
1380 |
1480 |
|
| 100 |
230 |
1330 |
1415 |
1520 |
270 |
1330 |
1415 |
1520 |
320 |
1480 |
1570 |
1690 |
|
| 125 |
270 |
1565 |
1665 |
1780 |
320 |
1565 |
1665 |
1780 |
375 |
1740 |
1850 |
1980 |
|
| 160 |
310 |
1800 |
1915 |
2050 |
365 |
1800 |
1915 |
2050 |
430 |
2000 |
2130 |
2280 |
|
| 200 |
360 |
2135 |
2275 |
2440 |
420 |
2135 |
2275 |
2440 |
495 |
2370 |
2530 |
2710 |
|
| 250 |
415 |
2330 |
2485 |
2665 |
490 |
2330 |
2485 |
2665 |
575 |
2590 |
2760 |
2960 |
|
| 315 |
510 |
2945 |
3125 |
3355 |
600 |
2945 |
3125 |
3355 |
705 |
3270 |
3470 |
3730 |
|
| 400 |
570 |
3375 |
3590 |
3850 |
665 |
3375 |
3590 |
3850 |
785 |
3750 |
3990 |
4280 |
|
| 500 |
670 |
4130 |
4390 |
4705 |
790 |
4130 |
4390 |
4705 |
930 |
4590 |
4880 |
5230 |
|
| 630 |
775 |
4975 |
5290 |
5660 |
910 |
4975 |
5290 |
5660 |
1070 |
5530 |
5880 |
6290 |
|
| 630 |
750 |
5050 |
5365 |
5760 |
885 |
5050 |
5365 |
5760 |
1040 |
5610 |
5960 |
6400 |
6.0 |
| 800 |
875 |
5895 |
6265 |
6715 |
1035 |
5895 |
6265 |
6715 |
1215 |
6550 |
6960 |
7460 |
|
| 1000 |
1020 |
6885 |
7315 |
7885 |
1205 |
6885 |
7315 |
7885 |
1415 |
7650 |
8130 |
8760 |
|
| 1250 |
1205 |
8190 |
8720 |
9335 |
1420 |
8190 |
8720 |
9335 |
1670 |
9100 |
9690 |
10370 |
|
| 1600 |
1415 |
9945 |
10555 |
11320 |
1665 |
9945 |
10555 |
11320 |
1960 |
11050 |
11730 |
12580 |
|
| 2000 |
1760 |
12240 |
13005 |
14005 |
2075 |
12240 |
13005 |
14005 |
2440 |
13600 |
14450 |
15560 |
|
| 2500 |
2080 |
14535 |
15445 |
16605 |
2450 |
14535 |
15445 |
16605 |
2880 |
16150 |
17170 |
18450 |
|