Shunt Capacitor Without External Fuse - Reliable Equipment from China Suppliers and Factory
Purposes
Service Conditions
-
The altitude of the installation and operation area shall not exceed 1,000m.
For exceeding 1000m, insulation correction is made as per related requirements. - Ambient temperature of the installation and operation area: - 5℃ ~ + 50℃
- The place of installation and operation shall be free from electrical conductivity, explosive dust and particles, violent mechanical vibration and harmful gas and steam.
Personal Safety
Structure
- Disconnector (or earthing switch): Used for isolation and grounding protection during the equipment power-off overhauling. Its technical index shall conform to the requirements of relevant standards and technical agreement.
- Discharge coil: Used for capacitor bank discharge as well as measurement meter and signal source of relay protection. Its technical index shall conform to the requirements of relevant standards and technical agreement.
- Zinc oxide arrester: Used for switching over-voltage protection or lightning over-voltage protection of the equipment (close to arrangement of capacitor bank as possible). Its technical index shall conform to the requirements of relevant standards and technical agreement.
- Current transformer: For current protection is used for providing signal exit for relay protection. Its technical index shall conform to the requirements of relevant standards and technical agreement.
- Series reactor: The ratio of the inductive reactance of the series reactor to the capacitive reactance of the equipment (reactance rate) is as follows: 0.5% - 1%, and 5% - 6% (or 12% - 13%). The maximum long-term operating current is 1.35 times the rated current of the equipment, and the reactance value shall not be less than 90% of the rated reactance value at this time. The series reactor will reduce the closing inrush current when the device is put into operation, prevent the instantaneous decrease of bus voltage, and restrain the influence of 5th (3rd) and above harmonic waves in the system on the equipment. Its technical index shall conform to the requirements of relevant standards and technical agreement.
Frequently Asked Questions
This equipment is designed for three-phase AC systems above 1kV with a frequency of 50Hz. It functions to increase the system's power factor, reduce network losses, and improve voltage quality.
The equipment can be installed indoors or outdoors. The installation site must have an altitude not exceeding 1,000 meters (or use insulation correction if above), an ambient temperature between -5℃ and +50℃, and be free from electrical conductivity, explosive dust, vibration, and harmful gases or steam.
Before touching any live parts, the capacitors must be grounded, short-circuited, and discharged. This is critical because capacitors store charge and cannot discharge instantly, even after being powered off for a long time.
The insulating oil is an irritant to the cornea. If it gets into the eyes, wash them immediately with clean water. While contact with other body parts is not harmful, the oil must not be ingested.
The series reactor reduces the closing inrush current when the device starts, prevents bus voltage drops, and suppresses the influence of the 5th (3rd) and higher harmonics in the system on the equipment.