Shunt Capacitor without External Fuse - Reliable Equipment from China Suppliers and Factory

General 
Our shunt capacitor equipment, made without external fuses, is expertly designed in accordance with IEC and GB standards. As a leading factory and supplier in China, we ensure that our products are not only structurally sound but also safe, reliable, and easy to install and maintain. Trust our high-quality shunt capacitors to enhance your electrical systems effectively.

    Purposes

    This equipment is used in the three-phase AC system above 1kV with the frequency of 50Hz, so as to increase the power factor of system, reduce the network losses and improve the voltage quality of system.

    Service Conditions

    This equipment is indoor (outdoor) type. The service environment conditions are as follows:
    The altitude of the installation and operation area shall not exceed 1,000m.
    For exceeding 1000m, insulation correction is made as per related requirements.
    Ambient temperature of the installation and operation area: - 5℃~ + 50℃
    The place of installation and operation shall be free from electrical conductivity, explosive dust and particles, violent mechanical vibration and harmful gas and steam.

    Personal Safety

    Since the capacitor is a kind of power storage equipment, its stored electric charge cannot be released in a short time, and the electric charge in the capacitor is easy to transfer.
    Notes:
    Grounding, short-circuiting and discharging of capacitors shall be carried out before the human body touches the live parts of capacitors, even if the capacitors are out of power for a long enough time.
    It is forbidden to contact two outgoing terminals of the capacitor with hands simultaneously at any time to avoid the impact by residual electric charge, causing unnecessary personal injuries. The capacitor out of operation shall be short-circuit grounded for a long time. Thus, it is able to avoid the impact by residual electric charge during disassembly and connection.
    product description01
    Warning: The insulating oil in the capacitor unit is an irritant liquid to the cornea, so it should be avoided from entering the eyes. Wash eyes with clean water in a timely manner after it enters. The oil will not cause harm to other parts of body by contact, but it cannot be eaten.

    Structure

    Composition of capacitor equipment
    The capacitor equipment includes shunt capacitor, disconnector (or earthing switch), ZnO arrester, discharge coil, current transformer (allocated during current protection), confluence busbar, connecting soft copper wires (copper strand), post insulators, modular steel framework laying aside capacitors, etc.
    Function for main accessories
    Disconnector (or earthing switch)
    Is used for isolation and grounding protection during the equipment power-off overhauling. Its technical index shall conform to the requirements of relevant standards and technical agreement.
    Discharge coil
    Is used for capacitor bank discharge as well as measurement meter and signal source of relay protection. Its technical index shall conform to the requirements of relevant standards and technical agreement.
    Zinc oxide arrester
    Is used for switching over-voltage protection or lightning over-voltage protection of the equipment (close to arrangement of capacitor bank as possible). Its technical index shall conform to the requirements of relevant standards and technical agreement.
    Current transformer for current protection
    Is used for providing signal exit for relay protection. Its technical index shall conform to the requirements of relevant standards and technical agreement.
    Series reactor
    The ratio of the inductive reactance of the series reactor to the capacitive reactance of the equipment (reactance rate) is as follows: 0.5% - 1%, and 5% - 6% (or 12% - 13%). The maximum long-term operating current is 1.35 times the rated current of the equipment, and the reactance value shall not be less than 90% of the rated reactance value at this time. The series reactor will reduce the closing inrush current when the device is put into operation, prevent the instantaneous decrease of bus voltage, and restrain the influence of 5th (3rd) and above harmonic waves in the system on the equipment. Its technical index shall conform to the requirements of relevant standards and technical agreement.

    Frequently Asked Questions

    What is the main purpose of this capacitor equipment?
    It is used in three-phase AC systems above 1kV with a frequency of 50Hz to increase the power factor of the system, reduce network losses, and improve overall system voltage quality.
    What are the environmental requirements for installing this equipment?
    The equipment is suitable for indoor or outdoor use. The installation altitude should not exceed 1,000m (otherwise insulation correction is required). The ambient temperature must remain within -5℃ to +50℃, and the area must be free from electrical conductivity, explosive dust, violent vibration, and harmful gases/steam.
    Why must grounding and discharging be done before touching the capacitors?
    Capacitors are power storage devices and cannot release their stored electrical charge instantly. Grounding, short-circuiting, and discharging must be carried out to prevent severe injury from residual charges, even if the equipment has been powered off for a long time.
    What safety precautions apply to the insulating oil inside the capacitor?
    The insulating oil is an irritant to the cornea. Avoid any eye contact; if it enters the eyes, wash them immediately with clean water. The oil is not harmful to skin contact but must not be consumed.
    What components make up the complete capacitor equipment structure?
    The setup includes a shunt capacitor, disconnector (or earthing switch), ZnO arrester, discharge coil, current transformer, confluence busbar, connecting soft copper wires, post insulators, and a modular steel framework.
    What is the role of the series reactor in this system?
    The series reactor reduces closing inrush currents during startup, prevents instantaneous bus voltage drops, and suppresses the influence of 5th (3rd) and higher harmonic waves in the system on the equipment.