VTD5-(12/24)40.5 Vacuum Circuit Breaker for GIS - China Factory Suppliers with Electric Spring Mechanism

Product Overview
Our vacuum circuit breaker is designed with a horizontal layout, ensuring that the sealing flange plate serves as the benchmark for both installation and sealing. This advanced equipment features an electric spring operating mechanism with a three-pole linkage, allowing for versatile operation modes—both electric and manual. Sourced from reliable suppliers in China, our factory guarantees high-quality performance and durability for all your electrical needs.

    General

    For vacuum circuit breakers with a rated current of 2000 A and above, a high-strength insulating plate holding the vacuum interrupter will be used, which is mounted on the flange plate. In contrast, for those with a rated current below 1600 A, an APG enclosed-type structure is adopted. This structure fixes the vacuum interrupter (VXG) onto the flange plate using a fixed plate.
    The opening and closing operation is achieved through the connection of the vacuum interrupter's dynamic side to the insulating rod, and the stainless steel sealing bellows connecting the crank arm, rod, down crank arm, and mechanism. All secondary cables are connected to an aerial socket, which facilitates convenient secondary wiring.
    Vacuum circuit breaker has the function that open, rated current and open circuit and close short circuit current.

    Main technical parameters

    Item Unit Parameter
    Rated voltage kV 12 24 40.5
    Rated current A 630, 1250, 1600, 2000, 2500, 3150
    Rated short-circuit breaking current kA 20, 25, 31.5
    Rated insulation level 1 min rated power frequency withstand voltage (r.m.s) kV 42 65 95
    Rated lighting impulse withstand voltage (peak) kV 75 125 85
    Rated short-time withstand current (4s) kA 20, 25, 31.5
    Rated peak short-time current kA 50, 63, 80
    Rated short-circuit making current kA 50, 63, 80
    Rated operating sequence / O - 0.3s - CO - 180s - CO
    Mechanical life Times 10000

    Outline dimension and structure diagram(mm)

    Maintenance

    The vacuum circuit breaker should be subject to an annual power-off inspection and maintenance to ensure normal operation. The inspection should cover the following aspects:
    • a) Perform a power frequency withstand voltage test on the tube, measure the vacuum level, and record the results.
    • b) Conduct a power frequency withstand voltage test on the insulating components.
    • c) Test the breaker's contact gap, contact travel, and mechanical characteristics, and record the results.
    • d) Inspect the connecting bolts, nuts, and other adjustable parts of the connections for any signs of loosening, especially the small screws at the auxiliary switch lever and the locking nuts connected to the vacuum tube's moving conductor rod.
    • e) Check the retaining rings, pins, and other components at the rotating joints for any signs of loosening or disengagement; apply lubricating grease to the rotating and sliding parts.
    • f) For vacuum circuit breakers used with currents exceeding 1,600 A, perform a direct current (DC) resistance test on each pole and record the results.
    • g) If tube replacement is required, follow the instructions in the product manual. After replacement, conduct mechanical characteristic tests and withstand voltage tests.
    • h) After the annual inspection and before commissioning, perform 8 to 10 no-load operations to ensure everything is functioning normally before commissioning.

    Frequently Asked Questions (FAQ)

    What is the difference in structure for vacuum circuit breakers with different rated currents?
    For vacuum circuit breakers with a rated current of 2000 A and above, a high-strength insulating plate holding the vacuum interrupter is mounted on the flange plate. For those with a rated current below 1600 A, an APG enclosed-type structure is adopted, which fixes the vacuum interrupter onto the flange plate using a fixed plate.
    How is the opening and closing operation of the vacuum circuit breaker achieved?
    The operation is achieved through the connection of the vacuum interrupter's dynamic side to the insulating rod, and the stainless steel sealing bellows connecting the crank arm, rod, down crank arm, and mechanism.
    What are the primary functions of a vacuum circuit breaker?
    A vacuum circuit breaker has the function to open and close the rated current, as well as open and close the short-circuit current in the circuit.
    What is the mechanical life parameter of this vacuum circuit breaker?
    The mechanical life of this vacuum circuit breaker is rated at 10,000 times.
    How often should inspection and maintenance be conducted?
    The vacuum circuit breaker should be subject to a power-off inspection and maintenance annually to ensure its normal operation.
    What must be done after the annual inspection before commissioning the circuit breaker?
    After the annual inspection and before commissioning, you must perform 8 to 10 no-load operations to ensure all mechanisms are functioning normally.