XGTD8-12 Indoor N₂ Gas Insulation Switchgear - Reliable Eco-Friendly Solution from China Suppliers & Factory

The XGTD8-12 indoor environmental gas-insulated metal-clad switchgear, manufactured by a leading China factory, is a top-tier electrical device filled with eco-friendly gas. This advanced switchgear is designed to deliver green, sustainable performance while ensuring reliable and efficient operation. Known for its compact design, maintenance-free features, long service life, and strong adaptability to various environmental conditions, it stands out among the best switchgear solutions. As one of the trusted suppliers in China, our factory guarantees high-quality products that meet stringent environmental and safety standards, making the XGTD8-12 an ideal choice for environmentally conscious electrical infrastructure projects

    Detail introduction

    The switchgear and its primary live parts are enclosed within a stainless steel shell, effectively shielding them from external influences. It employs a modular design, allowing for flexible combinations of common-tank and extended-unit configurations to meet various schemes and arrangements. This design ensures that the switchgear can satisfy the demands of compact installations in secondary transmission and distribution substations.

    Moreover, the switchgear is widely applicable in a range of environments, including secondary small distribution substations, industrial and mining enterprises, airports, railways, commercial districts, high-rise buildings, highways, subways, tunnels, and other locations with severe conditions.

    The product's quality assurance is grounded in a robust quality system that governs research, development, design, and production. Continuous improvement is a key focus, ensuring that the switchgear fully complies with the latest versions or revisions of relevant standards—though not limited to them.

    IEC62271-200 AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV.
    EN50181 Insertion bushings for equipment rated at voltages from 1 kV to 52 kV and currents from 250 A to 2500 A.
    GB/T3906 AC metal-enclosed switchgear and controlgear for rated voltages above 3.6 kV and up to and including 40.5 kV.
    GB/T11022 Common specifications for high-voltage switchgear and controlgear standards.
    DL/T404 AC metal-enclosed switchgear and controlgear for rated voltages above 3.6 kV and up to and including 40.5 kV.
    GB/T1984 High voltage AC circuit breaker.
    GB/T1985 High-voltage alternating-current isolators and earthing switches.
    GB/T20840 Instrument transformers - Part 1: General requirements.
    GB/T11032 AC Metal oxide surge arresters without gaps.

    Service Conditions

    a. Ambient temperature: -45℃~+50℃ the daily average value shall not exceed 35℃;
    b. Altitude: Not more than 4000m (If the equipment working over 1000m, please note it for the convenience of adjustment to the inflation pressure);
    c. Relative humidity: Daily average is not more than 95%, Monthly average is not more than 90%;
    d. Seismic grade: The seismic intensity shall not exceed grade 8;
    e. Pollution control: There shall be no Corrosive, flammable gases or other pollution.
    ※ Note: if the service environment exceeds the above conditions, please consult with our company.

    Technical parameter

    Item Unit Parameters
    V: CB unit C: load switch unit
    Rated voltage kV 12
    Rated current A 630/1250 630
    Rated frequency Hz 50/60
    1 min rated power frequency withstand voltage (rms) Phase to Phase/Phase to earth kV 42
    Insulation Distance 48
    Rated Lightning impulse withstand voltage (peak) Phase to Phase/Phase to earth kV 75
    Insulation Distance 85
    Rated power frequency withstand voltage of auxiliary circuit kV 2
    Rated short circuit breaking current (rms) kA 20/25
    Rated short circuit making current (peak) kA 50/63
    Rated short time withstand current (4s) kA 20/25
    Rated peak withstand current kA 50/63
    Main circuit resistance of each phase μΩ ≤160
    N₂ gas rated operation pressure MPa 0.02
    Mechanical life CB/Load switch times 10000
    Three-position switch 5000
    Rated values of internal arc level (IAC) KA/S 25/1
    Annual leak rate of N₂ gas % ≤0.1
    Protection degrees / IP67 for gas-filled compartment, IP4X for others

    Product Features and Structure

    ● Product features

    Green and environment-friendly
    Rather than SF6, all the nitrogen or dry air insulation, vacuum extinction, no greenhouse gas emissions. Harmful chemical elements in raw materials are strictly controlled in the parts manufacturing process, which can reduce the production of harmful substances. And the recycle rate of materials can reach 90% after the retirement.
    Safe and reliable
    It adopts micro-positive pressure gas insulation to reduce the leak rate of gas. Although, leaking happen to the gas compartment, it can still keep enough insulation ability at the lowest functional pressure, and does not affect the normal operating.
    Reasonable design & Modular design
    The switchgear includes load switch unit, the circuit breaker unit(V), meter switchgear unit(M), bus PT units, etc. It can achieve many forms of combination through general full insulation and full shielding bus connection, which can meet the demand for different places, different forms, different needs of customers, and provide a variety of designs for power supply and distribution.
    Fully insulated and sealed design
    The primary live part (main bus) of the switchgear and switch itself are sealed in the gas tank of welded stainless steel plate. The main circuit is connected to external through DIN47636 standard bushing that installed on the gas tank. It can also be connected to input and output cable by full insulation, shielding all full sealed separable connector. And protection grade of the gas tank box reach IP67. The inside of the gas tank is not affected by the external environment. It also has the short-term resistance function of flood and condensation.
    The other features
    User interface and cable connection are located in the front of the body, which is convenient for user operation. Operation switchgear instructions are clear, simple and easy to understand. The status of the three-station switch can be observed through the switchgear observation window.
    Small volume
    Adopting the insulation of environment-friendly gas, retained the size advantage of gas insulation switchgear, size is small, which can saving the floor area.
    Less maintenance
    High voltage insulation is not influenced by the external environment, and hardly aging. There is no need for users to protect or detect whether the SF6 gas leaks. Also, it can reduce the total life cycle cost of the product.
    Strong adaptability to environment
    All the HV components are sealed in the gas-filled metal enclosure, and the switchgear is especially suitable for high altitude, cold, damp, salt mist, pollution and other harsh environment.

    ● Product structure

    ● Outline structure

    product description01
    Product Structure Diagram

    Secondary meter room: For installing secondary components such as Ammeter, Voltmeter, protection device, gathering the secondary terminal of switchgear, which is convenient for maintenance and operation.

    Live display: To provide the live display data for input and output of cables.

    Gas-pressure meter: To show the safe pressure range in gas tank, and alarm contact function can be selected to achieve the operation of interlock opening and closing at low gas pressure.

    Operation switchgear: To provide switch operating indications of opening and closing, on which the corresponding switch operating instructions were printed.

    Gas tank compartment: It is fully sealed designed, which welded with the high quality stainless steel welding, and reach IP67 degree of protection.

    Pressure relief compartment: For installation cable and current transformer. At the same time, it's the guide channel for arching pressure relief, which may lead the arc to the cable trench.

    Cable room front door: It's the entrance of cable compartment, and it shall be taken apart first.

    Note: the connection of the figure between compartments is the outer cone top connection.

    ● Outline structure

    product description02
    Outline Dimensions Diagram
    Type Width(W) Height(H) Depth(D)
    C Top connection 420mm 1950mm 850mm
    Side connection 420mm 2000mm
    V Top connection 420mm 1950mm
    Side connection 420mm 2000mm
    PT Top connection 600mm 1950mm
    Side connection 600mm 2000mm
    D Top connection 420mm 1950mm
    Side connection 420mm 2000mm
    Note: the connection of the figure between compartments is the inner cone side connection, which also can be outer cone top connection as user demanded.

    Operation

    ● Operation procedures

    ● Preparation before operation
    It shall be operated with specific handle, and confirm that the installation of cable compartment front door and the correct connection of HV cable and secondary circuit.

    ● Power on operation procedure
    Ensure that circuit breaker/load switch in open position (which rotate the opening switch to open the circuit breaker/load switch), open the three position switch from earthing closing position to opening position, then operate it from isolation position to closing position. Operating isolation switch lively is forbidden. After confirming the isolation switch is closed, charging the circuit breaker/load switch mechanism with operating handle. Then rotate the closing knob, closing the circuit breaker/load switch.

    Note: There is mechanical interlock between circuit breaker/load switch mechanism and isolation mechanism to prevent mistake operation. If some operating difficulties happen, please check the condition of circuit breaker/load switch, and then do the closing or opening operation rather than operate forcibly.

    ● Power off operation procedure
    Rotate the closing knob, open the circuit breaker/load switch. Then operate the three position switch from isolation closing position to opening position with handle.

    ● Inspection operation procedure
    After confirming the cable compartment is not live, operate the three position switch from earthing opening position to closing position. Then open the front door for inspection.

    product description03
    Operation Panel Diagram

    ● Interlock logic

    a. Only when earthing switch at closing position, circuit breaker/load switch at opening position, can the cable compartment front door be opened.
    b. The earthing switch cannot be operated when the front door is open.
    c. The isolation switch and earthing switch cannot be operated when circuit breaker/load switch at closing position.
    d. When operate isolation switch and earthing switch, circuit breaker/load switch at closing position can not be operated.
    e. Only when circuit breaker/load switch at closing position can the cable compartment front door closed.

    Principle of Secondary Circuit

    ● Secondary circuit principle of the cabinet

    product description04
    Secondary Circuit of Cabinet

    ● Secondary circuit principle of the circuit breaker

    product description05
    Secondary Circuit of Circuit Breaker

    Scheme Option Table

    Single cabinet type

    product description06
    Single Cabinet Scheme Option 1
    product description07
    Single Cabinet Scheme Option 2

    Common box type

    product description08
    Common Box Scheme Option 1
    product description09
    Common Box Scheme Option 2
    product description10
    Common Box Scheme Option 3
    product description11
    Common Box Scheme Option 4

    Frequently Asked Questions

    1. What environmental conditions is this switchgear designed to withstand?

    This switchgear is designed for harsh environments. It operates in ambient temperatures ranging from -45℃ to +50℃ (daily average not exceeding 35℃), altitudes up to 4000m, relative humidity up to 95% (daily average), and seismic levels up to grade 8. It is also protected against corrosive and flammable gases.

    2. How does the switchgear achieve environmental friendliness?

    Instead of using SF6 gas, the switchgear utilizes nitrogen or dry air insulation combined with vacuum extinction, resulting in zero greenhouse gas emissions. Additionally, raw materials are strictly controlled to reduce harmful substances, allowing up to 90% of the materials to be recycled after decommissioning.

    3. What is the protection grade of the gas tank compartment?

    The primary live parts and switch are sealed inside a gas tank welded with high-quality stainless steel plate, achieving an IP67 protection rating. This prevents any external environmental impact and provides short-term resistance against floods and condensation.

    4. What is the mechanical life of the circuit breaker and switches?

    The circuit breaker (CB) and load switch units have a mechanical life of 10,000 operations, while the three-position switch has a mechanical life of 5,000 operations.

    5. What safety interlocks are integrated into the operation?

    The equipment features rigorous mechanical interlocks: the cable compartment door can only open when the earthing switch is closed and the circuit breaker is open; the earthing switch cannot operate while the door is open; and the isolation/earthing switches cannot be operated when the circuit breaker is closed.