Leave Your Message

YBTD Series Substation for Wind Power & Photovoltaic Generation - Reliable China Suppliers & Factory Solution

General
The YBTD series substation designed for wind power and photovoltaic generation is an innovative product developed by our company to meet the growing demands of the renewable energy sector. This product features a modern design, compact structure, and reliable performance, making it ideal for both wind and solar energy systems. With easy maintenance and robust functionality, our substations are a preferred choice among China suppliers and are manufactured in our state-of-the-art factory. Trust our YBTD series for efficient and sustainable energy solutions.

    Service conditions

    Altitude not more than 1000m;
    Ambient temperature: Max temperature 40℃, Min temperature -25℃
    Max daily average temperature not more than 35℃
    Max annual average temperature not more than 25℃
    Max daily temperature difference not more than 25℃
    The intensity of sunshine: Not more than 1000W/m2;
    Wind speed not more than 34m/s;
    Icing scope: Not more than 20mm;
    Pollution level: II class
    Installation site inclination of not more than 3 degrees;
    Anti seismic ability: Horizontal ground acceleration 0.2g;
    The vertical acceleration of the ground for 0.1g;
    Installation location: No fire, explosion, pollution, chemical corrosion and severe vibration of the place.
    When can not meet the normal use condition, we can design and manufacture as requested by customers.

    Structure features

    ● Housing structure

    • Substation skeleton was embalmed channel steel and angle steel manufacturing, and has sufficient mechanical strength and rigidity;
    • The shell material can be made of cold rolled steel plates, stainless steel plate, composite color plate , aluminum alloy plate or glass fiber reinforced cement;
    • Substation using steel plate isolation between each room, and have a lighting device;
    • Substation cover is a double-layer structure, and can effectively prevent the heat radiation;
    • Transformer room is divided into open and closed two structure. The open structure of the radiator of a transformer in an outdoor.and can effectively utilize natural wind to dissipate heat; Closed type structure of the transformer room has independent chamber.and is provided with an automatic air exhausting device, used to control the temperature of transformer room;
    • Housing door of substation adopts the low temperature type seal, and in low temperature environment can also achieve good sealing effect;
    • Surface paint of substation with high temperature paint handling, that can effectively delay the aging caused by ultraviolet ray paint;
    • The housing has a variety of colors to choose, so that it with the environment is harmonious.

    ● HV Unit

    • Various types of high-voltage switchgear can be used in the high-voltage compartment, such as XGTD9, HXGN11, XGTD6, (H)XGTD10, etc., with compact structure and convenient combination. Users can choose different switchgear according to own requirements;
    • The high-voltage switchgear has the advantages of simple structure, convenient installation & operation and strong reliability;
    • The switchgear has the complete prevention of erroneous operation function, to ensure the safety of maintenance personnel.

    ● Transformer Unit

    • Transformer using S9-M, S11-M oil immersed transformer or SCB dry type transformer;
    • The transformer has the advantages of small volume, convenient maintenance;
    • Transformer room has a good natural ventilation, or through automatic control fan to exhaust air force to reduce the temperature of the room;
    • The use of flexible connections between the low-voltage side terminal of the transformer and the busbar can effectively protect the low-voltage bushings of the transformer, preventing them from cracking or oil leakage.

    ● LV Unit

    • GGD, GCS and GCK series produced by our company can be selected for LV switchgear;
    • Metering, measuring and capacitance automatic compensation devices can be set according to users requirements;
    • Other schemes can be confirmed by engineer according to user requirements.

    ● Distribution network automation unit

    • Use automation terminal equipment, which are optimized to take full account of the hard operating environment of wind power transformer and photovoltaic substation.
    • It features strong adaptability to temperature ambient, dual-fiber ring network communication functionality, high resistance to interference, vibration, humidity, and lightning, and low power consumption.
    • Illustrations of Wind power transformer and photovoltaic substation automatic monitoring
    product-description1

    Technical data

    Item Unit Data
    HV unit Switch type Combined electrical apparatus Circuit breaker
    Rated voltage kV 40.5 40.5
    Rated frequency Hz 50 60
    Rated current A 630 1250
    1min Rated power frequency withstand voltage (for ground and phase/isolation fracture) kV 95/118 95/118
    Lightning withstand voltage (for ground and phase /isolation fracture) kV 185/215 185/215
    Rated short time withstand current kA/s 20/2 25/4
    Rated peak withstand current kA 50 63
    Rated short-circuit current kA 31.5 63
    Rated short circuit breaking current kA 31.5 25
    LV unit Rated voltage V 690/270
    Main circuit rated current A 1600~3300
    Rated ultimate short circuit breaking capacity kA 50
    Rated short-circuit breaking capacity kA 40
    Rated short-time withstand voltage kA/s 40/1
    Transformer unit Rated capacity kVA 1000~5500
    Impedance voltage % 6.5
    Tapping range % ±2X2.5; ±5
    Connected group D, yn11 or Y, d11d11
    Main body Enclosure degree of protection HV room IP33
    LV room IP33
    Transformer room IP23
    Sound level dB ≤55
    Note: The above parameters are for reference. Our company can provide customized services according to customer requirements.

    Frequently Asked Questions (FAQ)

    Q: What options are available for the substation shell housing material?

    The substation shell can be constructed from a variety of materials including cold rolled steel plates, stainless steel plates, composite color plates, aluminum alloy plates, or glass fiber reinforced cement.

    Q: Can this substation be customized for non-standard working environments?

    Yes. If your operating environment does not meet our standard service conditions (such as high altitude above 1000m or extreme temperatures), we can design and manufacture customized solutions tailored to your specific requirements.

    Q: What types of transformers are compatible with the transformer unit?

    The unit is designed to accommodate S9-M and S11-M oil-immersed transformers, as well as SCB dry-type transformers, depending on your system specifications.

    Q: What is the enclosure protection rating (IP code) for each compartment?

    The High Voltage (HV) and Low Voltage (LV) rooms feature an IP33 protection rating, while the Transformer room features an IP23 protection rating.

    Q: How is heat dissipation managed in the transformer room?

    We offer both open and closed structures. The open structure places the radiator outdoors to utilize natural wind. The closed structure features an independent chamber equipped with an automatic air exhausting device to control room temperature.

    Q: Does the automation unit support remote monitoring for wind and solar applications?

    Yes, the distribution network automation unit utilizes specialized terminal equipment optimized for harsh environments, featuring dual-fiber ring network communication functionality, high resistance to interference, and low power consumption.

    Leave Your Message