ZGS 10kV Oil Immersed Pad Mounted Transformer - Reliable China Suppliers & Factory Solutions

General
The ZGS series oil-immersed pad-mounted transformer is an innovative solution designed for efficient power distribution. Manufactured in China, this transformer integrates essential components such as load switches and high-voltage fuses within its durable transformer box. Utilizing insulation liquid as both an insulator and a heat dissipater, it ensures optimal performance and safety. This compact and lightweight design allows for easy installation and maintenance, making it a preferred choice among suppliers and industries alike. With its high reliability and aesthetic appeal, the ZGS series transformer stands out as a top choice for modern electrical needs. Trust our factory to deliver exceptional quality and performance in power solutions.

    Uses

    It is mainly used for 10/0.4KV, 50Hz/60Hz power distribution systems, the rated capacity of transformers is 50-1600kVA, widely applicable to outdoor power supply locations such as cities, residential areas, factories and mines, hotels, hospitals, parks, oil fields, airports, docks, railways, and temporary facilities.
    The pad mounted transformer can be used in both ring network power distribution systems and as terminal power supply for radial power grids.

    Service conditions

    a. Altitude : ≤ 1000m
    b. Environmental temperature: -40 ℃ to +40 ℃
    c. Relative humidity: Daily average ≤ 95%, monthly average ≤ 90%
    d. Outdoor wind speed: ≤ 35m/s
    e. Installation location: Installed in a place without fire, explosion hazards, severe pollution, chemical corrosion, and severe vibration.
    ※ Note: If the above normal usage environment conditions are exceeded, users can negotiate with our factory to resolve the issue.

    Structure

    • The product is divided into three main parts: transformer chamber, high voltage chamber, and low voltage chamber.
    • The performance of the transformer complies with S13 or S11-M type transformers.
    • The high-voltage side is protected by a V-shaped or T-shaped load switch and a two pole fuse. The current limiting fuse is used for line protection and has a large breaking capacity. The plug-in fuse is used to protect the secondary side overload and short circuit of the transformer.
    • The load switch and fuse are installed in the transformer chamber, using the insulation liquid of the transformer as the insulation medium and heat dissipation medium.
    • The incoming line on the high-voltage side adopts high-voltage cable plugs, and the high-voltage room is fully insulated.
    • The low-voltage side of conventional products adopts direct output. According to user requirements, low-voltage metering and branch out lines can be added.
    • The box body adopts steel plate welding, corrugated sheet heat dissipation on three sides, fully sealed structure, treated with special technology, strong anti-corrosion ability, and beautiful appearance.
    • The high voltage chamber and low voltage chamber are isolated. The operable components in the high voltage chamber include load switches, transformer tap changers, high voltage incoming plugs, and plug-in fuses.
    • The box is equipped with: oil level thermometer, oil level gauge, pressure relief valve, oil drain valve, and oil sample valve. Low voltage output terminals and low-voltage metering systems equipped according to user requirements.

    Technical parameters and external dimensions

    Table 1: Parameters of Load switch
    SN Description Unit Parameter
    1 Rated voltage kV 12
    2 Rated current A 630
    3 Rated frequency Hz 50/60
    4 Rated breaking current A 630
    5 Thermal stability current kA 16/2
    6 Dynamic stable current kA 40
    7 Full load breaking times Times 20
    8 Mechanical life Times 2000
    9 1-minute power frequency withstand voltage (phase to phase and to ground) kV 42
    10 Lightning impulse level (phase to phase and to ground) kV 75
    Table 2 : Parameters of High Voltage Cable Plug
    SN Description Unit Parameter
    1 Rated voltage kV 12
    2 Rated current A 200/300/630
    3 1-minute power frequency withstand voltage kV 42
    4 Insulation resistance 2000
    5 Contact resistance of contacts μΩ ≤100
    Table 3 : Parameters of Fuse
    Rated capacity (kVA) Rated voltage 6kV Rated voltage 10kV
    Current limiting fuse (A) Model of Plug in fuse Current limiting fuse (A) Model of Plug in fuse
    50 40 12 40 6
    100 50 15 40 12
    160 80 25 50 15
    200 80 25 80 25
    250 125 25 80 25
    315 150 50 80 25
    400 150 50 100 40
    500 175 65 125 50
    630 175 100 150 50
    800 200 100 150 65
    1000 200 140 200 100
    1250 200 200 200 100
    ※ Note: The backup current limiting fuse and plug-in fuse are oil immersed type.
    Table 4: Parameters of Transformers
    Rated capacity (kVA) No-load loss (W) Load loss (W) Impedance Voltage %
    S13 S11 S13 S11
    50 100 130 910 / 870 910 / 870 4
    100 150 200 1580 / 1500 1580 / 1500
    160 200 280 2310 / 2200 2310 / 2200
    200 240 340 2730 / 2600 2730 / 2600
    250 290 400 3200 / 3050 3200 / 3050
    315 340 480 3830 / 3650 3830 / 3650
    400 410 570 4520 / 4300 4520 / 4300
    500 480 680 5410 / 5150 5410 / 5150
    630 570 810 6200 6200 4.5
    800 700 980 7500 7500
    1000 830 1150 10300 10300
    1250 970 1360 12000 12000
    ※ Note: The load loss value to the left of the slash applies to the Dyn11 or Yzn11 connection group, while the load loss values to the right of the slash applies to the Yyn0 connection group.
    ⚡ Voltage combination & Connection details
    Rated voltage of high voltage side: 11, 10.5, 10, 6.3, 6kV
    Rated voltage of low voltage side: 0.4kV
    Transformer connection group: Y, yn0 or Dyn11
    Tap range: ±5%, ± 2x2.5%, or confirmed by the user
    ※ Note: If the specified technical parameters are exceeded, please negotiate with our company.

    Frequently Asked Questions (FAQ)

    What is the rated capacity range for these pad mounted transformers?
    The rated capacity of the transformers in these power distribution systems ranges from 50 to 1600kVA.
    What are the standard environmental conditions for installation?
    The standard installation conditions require an altitude of ≤ 1000m, an ambient temperature range between -40 ℃ and +40 ℃, daily relative humidity not exceeding 95% (monthly ≤ 90%), and outdoor wind speeds of ≤ 35m/s.
    How is the high-voltage side protected in the structure?
    The high-voltage side is protected by a V-shaped or T-shaped load switch and a two-pole fuse. A current-limiting fuse is used for line protection, while a plug-in fuse protects against secondary side overload and short circuits.
    What insulation and cooling medium is used for the switch and fuse?
    The load switch and fuse are installed directly inside the transformer chamber, utilizing the insulation liquid of the transformer as both the insulation and heat dissipation medium.
    What connection groups and tap ranges are supported?
    The transformer connection groups are Y, yn0 or Dyn11. The standard tap range is ±5%, ± 2x2.5%, or it can be customized and confirmed by the user.